background image

IV. TO TURN THE UNIT ON AND OFF

To turn the unit on, press the orange ON/OFF button (See
Fig. 18). Unit will start. To stop unit operation, press the ON/
OFF button again. Unit will stop. Refer to Owner’s Manual
enclosed with the fan coil unit for full remote control operat-
ing details.

V. ADJUSTING AIRFLOW

The airflow direction may be adjusted up and down using the
remote controller, and from side to side by manually moving
the vents. For cooling only units and heat pump units when
in the cooling mode, set the louvers to discharge straight out
(parallel to the floor) (see Fig. 19). For the heat pump units
operating in heating mode, it is recommended that the air
discharge louvers be set to discharge vertically (see Fig. 19).

The swing range shown in Fig. 19 is the range in which will
provide maximum occupant comfort in each mode. It is rec-
ommended that the louvers be positioned within this range
(using the remote controller).

NOTE:

The full swing range of the mode selected will auto-

matically be used if auto. fan mode is selected.

VI. OPERATING MODE MEMORY

After the system is turned off or after a power failure, the
system remains in the last operating mode selected. When
the system is turned back on, or when power is automati-
cally restored, operation continues in the same operating mode
as when power shut down.

VII. AUTOMATIC OPERATION (AUTO) MODE

If auto mode is selected, the system automatically switches
the operating mode from heating (heat pump system only) to
cooling, or from cooling to heating (heat pump system only)
depending on the selected temperature.

NOTE:

Between the cooling cycle and the heating cycle there

is a neutral zone of approximately 2° F above and 2° F below
the selected temperature when only the fan is operating.

VIII. OPERATING FAULT DIAGNOSIS

The system includes an automatic diagnosis feature which is
activated under difficult or unacceptable operating condi-
tions. If such conditions occur, the system stops automati-
cally, the operating fault signal appears (green ‘‘UNIT ON’’

light on the front of the fan coil unit flashes), and an analysis
of the system operating conditions is initiated. The system
will then be restarted automatically, as soon as normal con-
ditions have been restored, or it will remain off. If the system
does not start again, the green ‘‘UNIT ON’’ light will flash an
error code.

IX. MICROPROCESSOR CONTROL OPERATION

This system is controlled by a microprocessor designed to give
optimum levels of comfort and operating efficiency. The con-
trol is located in the 619E unit. To operate the unit, the factory-
supplied remote controller is required.

There are 9 (619E cooling-only systems) or 11 (619E heat pump
systems) operating modes (including the off mode) for the unit.
Each mode operates as follows:

• Off Mode — When the unit is in the off mode, all functions

(compressor, outdoor fan, indoor fan, and air sweep) are
off, except the reversing valve (619E heat pump units only),
which will stay energized if the unit was last operated in
the cooling mode.

• Air Circulation Mode (Fan Operation Only) — When air

circulation mode is selected, the indoor fan will operate con-
tinuously in the selected speed (high, medium, low, or auto.).
If the auto. mode is selected, the indoor fan will operate at
low speed. The compressor and outdoor fan are off. The re-
versing valve (619E heat pump units only) will remain in
the last operating mode.

• Cooling Mode — When the cooling mode is selected, the

indoor fan will operate continuously at the selected speed
if the speed is high, medium, or low. If the indoor fan is in
auto. mode, the fan will change operating speeds depend-
ing on the difference between the room temperature and
the set point. The reversing valve (619E heat pump units
only) will be on. The compressor cannot run for 3 minutes
from the time the system starts up or for 3 minutes from
the time the compressor last operated. When the tempera-
ture of the room is equal to or greater than the selected
temperature, the compressor and outdoor fan will operate
until the room temperature is 2° F below the set point, and
then shut off. When the room temperature is less than the
selected temperature, the compressor and outdoor fan re-
main off.

• Maximum Dehumidification Mode —When the dehumidi-

fication mode is selected, the indoor fan will operate con-
tinuously at the selected speed if the speed is high, me-
dium, or low. If the indoor fan is in auto. mode, the fan will

Fig. 18 — Remote Controller

*Potential range.

†Desireable range.

NOTE: Unit is equipped with manual air vents which direct the air from
side to side. Up and down louver motion can be selected using the re-
mote controller. For maximum comfort, set louvers within the swing range.
See Adjusting Airflow section on this page for more information.

Fig. 19 — Louver Adjustments

—10—

Summary of Contents for 619E Series

Page 1: ...Danger identifies the most serious hazards which will result in severe personal injury or death Warning indicates a situation that could result in personal injury Caution is used to identify unsafe pr...

Page 2: ...in indicate quantities of more than 1 Table 2 Application Ranges COOLING MODE Maximum Minimum Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit 95 F DB 71 F WB 115 F DB 67 F DB 57 F WB 55 F DB 0 F DB...

Page 3: ...ons may be made in unit rear bottom left side or right side 4 Refrigerant is metered by AccuRater device in the fan coil unit on 538A and 538B applications A thermostatic expan sion valve is used in t...

Page 4: ...l be mounted unevenly and con densate drainage water may drip onto the floor Also a gap between the bracket and the wall may result in vi bration and noise from the indoor section 5 Mark and cut conde...

Page 5: ...d slide insulation over the piping Insulation can also be cut and placed over piping 2 Run liquid and gas refrigerant piping a Run pipes as directly as possible and avoid any un necessary turns and be...

Page 6: ...at a downward slope of at least 1 4 in per foot Refer to Fig 12 IMPORTANT Be sure the drain piping has no slack which might form a trap Do not insert a trap in the drain line the drain is internally...

Page 7: ...x strain relief clamp see Fig 13 3 Remove any factory test leads still connected to the power terminal box These leads are for factory testing only and cannot be used for power connections 4 Route the...

Page 8: ...ERMISTOR CABLE IN THE SAME CONDUIT AS THE POWER WIRING 1 One thermistor connection cord with a lead length of 24 ft is shipped with the 619E heat pump fan coil unit Run the connection cord from the lo...

Page 9: ...system operation to the owner I 619E CONTROL SYSTEM The 619E unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit wi...

Page 10: ...in the green UNIT ON light will flash an error code IX MICROPROCESSOR CONTROL OPERATION This system is controlled by a microprocessor designed to give optimum levels of comfort and operating efficienc...

Page 11: ...operate at the selected speed if the speed is high medium or low unless overridden by the coil temperature to pre vent cold drafts If the indoor fan is in auto mode the fan will change operating spee...

Page 12: ...visable to remove the batteries Consult distributor if any other equipment is turned on or shows signs of disrupted operation if you use the wireless re mote controller or if the system is turned on o...

Page 13: ...not use abrasive or petroleum based cleaners damage to unit appearance will result VI TO CLEAN INDOOR COIL To clean the coil remove indoor unit front panel and vacuum the coil fins Use care not to ben...

Page 14: ...ndicated then the system allows only limited operation until the problem is resolved If the problem resolves itself then the code is cleared and opera tion resumes A Thermistor Tests Each thermistor i...

Page 15: ...e replaced with type 90 C wire or its equivalent 2 Wire in accordance with National Electrical Code NEC and local codes 3 The CLO locks out the compressor to prevent short cy cling on compressor overl...

Page 16: ...ling Only System 538A Shown RELAY CHART Compressor K13 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identical to eac...

Page 17: ...ystem RELAY CHART Compressor K13 Rev Valve K11 Outdoor Fan K12 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identica...

Page 18: ...Copyright 1996 Carrier Corporation CATALOG NO BDP 3361 904...

Page 19: ...AS GROUND WIRE BEEN CONNECTED HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT...

Page 20: ...UNIT WITH UNIT OPERATING OUTDOOR INDOOR START UP IF UNIT HAS A CRANKCASE HEATER HAS IT BEEN ON FOR 24 HOURS MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LIN...

Reviews: