—6—

 

ACCESSORY USAGE GUIDELINE

 

*

 

For tubing line sets between 50 and 175 ft, refer to the Residential Split-System Long-Line Application Guideline.

† Only when low-pressure switch is used.
‡ Required for Low-Ambient Controller (full modulation feature) and MotorMaster Control only.

 

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

 

1.

 

Ball Bearing Fan Motor

 

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. 

SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.

2.

 

Coastal Filter

 

A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow. 

SUGGESTED USE: In geographic areas where salt damage could occur.

3.

 

Compressor Start Assist — Capacitor/Relay Type

 

Start capacitor and start relay gives “hard” boost to compressor motor at each start-up.

SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105°F (40.6°C).
Replacement installations with hard shutoff expansion valve on indoor coil.
Installations where Liquid-Line Solenoid Valve has been added.

4.

 

Compressor Start Assist — PTC Type

 

Solid state electrical device which gives a “soft” boost to compressor motor at each start-up.

SUGGESTED USE: Installations with marginal power supply.

Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.

5.

 

Crankcase Heater

 

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication 
on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. 

SUGGESTED USE: When interconnecting tube length exceeds 50 ft.

When unit will be operated below 55°F (12.8°C) outdoor air temperature. Use with Low-Ambient Controller.
All commercial installations.

6.

 

Cycle Protector

 

Solid state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has 
been interrupted for any reason, including normal room thermostat cycling. 

SUGGESTED USE: Installations in areas where power interruptions are frequent.

Where user is likely to “play” with the room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 50 ft.
High-rise applications.

7.

 

Evaporator Freeze Thermostat

 

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions. 

SUGGESTED USE: All units where Winter Start Control has been added.

8.

 

Filter Drier

 

A device for removing contaminants from refrigerant circulating in an air conditioner: 1-direction flow.

SUGGESTED USE: All split system air conditioners.

9.

 

High-Pressure Switch 

 

Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 400 ± 10 
psig and resets at  298 ± 20 psig. Provides protection against compressor damage due to loss of outdoor airflow.  To prevent rapid compressor recycling, 
Cycle Protector can be used with this switch.

SUGGESTED USE: Installations exposed to very ‘‘dirty’’ outdoor air.

Installations where condenser inlet air temperature exceeds 125°F (51.7°C).

10.

 

Liquid-Line Solenoid Valve (LSV)

 

An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) and which stops and starts refrigerant 
liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.

 

NOTE: 

 

Compressor Start Assist — Capacitor/Relay Type must also be used. Do not use with hard shutoff TXV.

SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

In certain long line-applications. Refer to Residential Split System Long-Line Application Guideline.

 

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(Below 55°F)

REQUIRED FOR

LONG-LINE

APPLICATIONS

 

*

 

(Over 50 Ft)

REQUIRED FOR

SEA COAST

APPLICATIONS
(Within 2 Miles)

 

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Winter Start Control

Yes†

No

No

Accumulator

No

No

No

Compressor Start Assist

Capacitor and Relay

Yes

Yes

No

Low Ambient Controller,

MotorMaster® Control,

or

Low-Ambient Pressure Switch

Yes

No

No

Wind Baffle

See Low-Ambient Instructions

No

No

Coastal Filter

No

No

Yes

Support Feet

Recommended

No

Recommended

Liquid-Line Solenoid Valve

or

Hard Shutoff TXV

No

See Long-Line

Application

Guideline

No

Ball Bearing Fan Motor

Yes‡

No

No

Summary of Contents for 597C (60 Hz)

Page 1: ...will last for many years All screws on cabinet exterior are coated for a long lasting rust resistant quality appearance TOTALLY ENCLOSED FAN MOTOR Provides greater reliabil ity under adverse weather conditions and dependable perfor mance for many years The permanent split capacitor type motor was designed for optimum efficiency Then under extreme conditions the motor was tested and qualified to he...

Page 2: ...3 8 15 2 15 16 26 x 32 060 F 39 13 16 30 33 5 1 16 9 11 16 27 15 16 34 3 8 7 8 16 1 2 20 3 8 15 2 15 16 26 x 32 ACCESS PANEL 1 1 4 1 Allow 30 in clearance to service end of unit 48 in above unit 6 in on one side 12 in on remaining side and 24 in between units for proper airflow Minimum outdoor operating ambient in cooling mode is 55 F unless low ambient control is used max 125 F 2 Series designati...

Page 3: ...cations Maximum Diameter 018 024 3 8 3 8 5 8 3 4 030 036 3 4 7 8 042 048 7 8 1 1 8 060 1 1 8 1 1 8 UNIT SIZE SERIES PISTON IDENTIFICATION NO 018 F 55 024 F 61 030 F 67 036 F 76 042 F 82 048 G 90 048 F 93 060 F 101 UNIT SIZE SERIES REQUIRED SUBCOOLING F 018 F 10 024 F 12 030 F 15 036 F 12 042 F 12 048 G F 11 060 F 12 CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI REGISTERED ...

Page 4: ...1 Condenser Airflow CFM 1500 2000 2000 3000 3000 3000 3300 OPTIONAL EQUIPMENT Support Feet KSASF0101AAA Coastal Filter KAACF0101SML KAACF0201MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Crankcase Heater KAACH1201AAA Start Assist Capacitor Relay Type KSAHS1501AAA KSAHS1601AAA Start Assist PTC Type KAACS0201PTC TXV RPB KAATX0201RPB KAATX0301RPB KAATX0401RPB KAATX0501RPB KAATX0601RP...

Page 5: ...er than 10 AWG is used consult applicable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2 Time delay fuse or circuit breaker Charge quantity is for 15 ft of interconnecting tubing For tubing lengths longer than 15 ft add 0 6 oz of refrigerant per ft of tube length in excess of 15 ft Do not use hard s...

Page 6: ...as where power interruptions are frequent Where user is likely to play with the room thermostat All commercial installations Installations where interconnecting tube length exceeds 50 ft High rise applications 7 Evaporator Freeze Thermostat An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze up conditions SUGGESTED USE All units where Winter Start Control ...

Page 7: ...e temperature at a remote location outdoors to be displayed at the thermostat SUGGESTED USE All corporate programmable thermostats 16 Support Feet Four stick on plastic feet which raise the unit 4 in above the mounting pad This allows sand dirt and other debris to be flushed from the unit base minimizing corrosion SUGGESTED USE Coastal installations Windy areas or where debris is normally circulat...

Page 8: ...ONE 12 20 12 20 12 20 11 10 CF5AA024 23 000 NONE 12 00 12 00 12 00 10 95 CK3BA024 23 000 NONE 12 00 12 00 12 00 10 85 CK3BA030 23 200 NONE 12 20 12 20 12 20 11 05 CK5A CK5BA024 23 000 NONE 12 00 12 00 12 00 10 85 CK5A CK5BA030 23 200 NONE 12 20 12 20 12 20 11 05 CK5A CK5BW024 23 000 NONE 12 00 12 00 12 00 10 85 CK5A CK5BW030 23 200 NONE 12 20 12 20 12 20 11 05 F A B 4ANF024 23 200 TDR 12 00 12 00 ...

Page 9: ... CE3AA036 29 800 TDR 13 50 13 50 11 80 CK3BA030 29 000 TDR 13 00 13 00 11 30 CK3BA036 29 600 TDR 13 50 13 50 11 85 CK5A CK5BA030 29 000 TDR 13 00 13 00 11 30 CK5A CK5BA036 29 600 TDR 13 50 13 50 11 85 CK5A CK5BN036 27 600 TDR 13 00 13 00 11 70 CK5A CK5BW030 29 000 TDR 13 00 13 00 11 30 COILS 333 B J AV048080 VARIABLE SPEED FURNACE CC5A CD5AA036 30 000 TDR 13 50 13 50 12 05 CE3AA036 29 800 TDR 13 5...

Page 10: ... FURNACE CC5A CD5AA042 35 400 TDR 13 00 13 00 11 65 CE3AA042 35 400 TDR 13 00 13 00 11 70 CK3BA036 35 000 TDR 13 00 13 00 11 45 CK3BA042 35 000 TDR 13 00 13 00 11 35 CK5A CK5BA036 35 000 TDR 13 00 13 00 11 45 CK5A CK5BN036 33 000 TDR 12 50 12 50 11 65 COILS 333 B J AV048080 VARIABLE SPEED FURNACE CC5A CD5AA042 35 400 TDR 13 00 13 00 11 65 CE3AA042 35 400 TDR 13 00 13 00 11 70 CK3BA036 35 000 TDR 1...

Page 11: ...R 12 00 12 00 10 50 F A B 4AN F B 048 41 500 TDR 12 20 12 20 10 70 FC4BN F B 042 41 000 TDR TXV 12 00 10 50 FC4BN F B 048 41 500 TDR TXV 12 20 10 70 FC4BNB054 43 000 TDR TXV 13 00 11 40 FG3AAA048 41 000 NONE 12 20 12 20 12 20 10 65 FK4BNB005 42 000 TDR TXV 13 50 11 75 FK4BNB006 43 000 TDR TXV 14 00 12 10 FK4BNF003 41 500 TDR TXV 13 00 11 30 FK4CNB006 43 000 TDR TXV 14 00 12 10 FK4CNF003 41 500 TDR...

Page 12: ... CK5BW048 47 500 NONE 12 00 12 00 12 00 10 60 CK5A CK5BX060 48 500 NONE 12 40 12 40 12 40 11 00 F A B 4AN F B C 048 47 500 TDR 12 00 12 00 10 55 F A B 4AN F B C 060 48 000 TDR 12 10 12 10 10 60 FC4BN F B 048 47 500 TDR TXV 12 00 10 55 FC4BN F B 060 48 000 TDR TXV 12 10 10 60 FC4BNB054 48 500 TDR TXV 12 50 11 05 FC4BNB070 48 000 TDR TXV 12 20 11 00 FG3AAA048 47 500 NONE 12 00 12 00 12 00 10 55 FG3A...

Page 13: ...00 10 65 CC5A CD5AW060 48 000 TDR 12 80 12 80 11 25 CD5AA048 47 000 TDR 12 50 12 50 10 90 CK3BA048 47 000 TDR 12 50 12 50 10 95 CK3BA060 47 000 TDR 12 50 12 50 11 20 CK5A CK5BA048 47 000 TDR 12 50 12 50 10 95 CK5A CK5BX060 48 000 TDR 12 80 12 80 11 45 COILS 355MAV060120 VARIABLE SPEED FURNACE CC5A CD5AA060 47 000 TDR 12 50 12 50 11 00 CC5A CD5AW048 47 000 TDR 12 50 12 50 10 90 CC5A CD5AW060 48 000...

Page 14: ...5 6 1 56 15 0 15 0 1 75 14 5 14 5 1 96 13 8 13 8 2 19 675 72 20 0 10 4 1 46 19 2 10 1 1 63 18 4 9 81 1 82 17 6 9 51 2 03 16 7 9 19 2 26 67 18 3 13 5 1 44 17 6 13 2 1 61 16 9 12 9 1 80 16 1 12 6 2 01 15 2 12 3 2 24 62 16 8 16 4 1 43 16 2 16 0 1 60 15 5 15 5 1 79 14 9 14 9 2 00 14 2 14 2 2 23 57 16 6 16 6 1 43 16 0 16 0 1 59 15 5 15 5 1 78 14 8 14 8 1 99 14 2 14 2 2 22 Multipliers for Determining th...

Page 15: ...3 20 9 2 17 20 4 20 3 2 38 19 5 19 5 2 6 18 7 18 7 2 91 57 21 8 21 8 1 96 21 1 21 1 2 16 20 3 20 3 2 38 19 5 19 5 2 6 18 7 18 7 2 90 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 024 1 00 1 00 COILS 333 B J AV036060 VARIABLE SPEED FURNACE 030 1 01 1 00 CC5A CD5AA 030 1 03 0 90 ...

Page 16: ...ity Power CC5A CD5AA 030 1 00 1 00 CK3BA 030 1 00 0 93 036 1 02 1 00 036 1 02 0 91 CC5A CD5AW 030 1 00 1 00 CK5A CK5BW 030 1 00 0 93 CD5AW 036 1 02 1 00 036 1 02 0 91 CE3AA 030 1 00 1 00 COILS 355MAV042040 VARIABLE SPEED FURNACE 036 1 02 1 00 CC5A CD5AA 030 1 02 0 94 CF5AA 036 1 02 1 00 036 1 03 0 93 CK3BA 030 1 00 1 00 CK3BA 030 1 00 0 96 036 1 02 1 00 036 1 02 0 95 CK5A CK5BA 030 1 00 1 00 CK5A ...

Page 17: ...2 1 01 0 93 042 100 1 00 CK3BA 036 1 00 0 92 CC5A CD5AW 042 1 00 1 00 042 1 00 0 93 CD5AW 036 1 00 1 00 CK5A CK5BA 042 1 00 0 93 CE3AA 036 0 99 1 00 CK5A CK5BW 036 1 00 0 92 042 1 01 1 00 COILS 333 B J AV060100 VARIABLE SPEED FURNACE CF5AA 036 1 01 1 00 CC5A CD5AA 042 1 01 0 93 CK3BA 036 1 00 1 00 CE3AA 042 1 01 0 93 042 1 00 1 00 CK3BA 036 1 00 0 92 CK5A CK5BA 036 1 00 1 00 042 1 00 0 92 042 1 00...

Page 18: ... 33 4 24 7 3 60 31 8 24 1 3 9 30 2 23 5 4 39 62 33 4 31 4 2 94 32 0 30 7 3 24 30 6 29 9 3 59 29 1 28 9 3 9 27 8 27 8 4 34 57 32 5 32 5 2 93 31 4 31 4 3 25 30 3 30 3 3 58 29 0 29 0 3 9 27 8 27 8 4 35 1350 72 40 3 21 0 3 03 38 5 20 4 3 33 36 9 19 8 3 69 35 1 19 2 4 0 33 2 18 5 4 47 67 36 9 27 4 3 01 35 3 26 7 3 31 33 8 26 2 3 66 32 2 25 5 4 0 30 3 24 8 4 42 62 33 9 33 1 3 00 32 5 32 2 3 29 31 2 31 2...

Page 19: ... 1 00 1 00 CK5A CK5BA 042 1 00 0 93 CC5A CD5AC 048 0 99 1 00 CK5A CK5BW 048 1 00 0 93 CC5A CD5AW 042 1 00 1 00 COILS 333 B J AV060120 VARIABLE SPEED FURNACE 048 1 00 1 00 CD5AA 048 1 00 0 92 CD5AA 048 1 00 1 00 CE3AA 048 1 00 0 92 CE3AA 042 1 00 1 00 CK3BA 042 1 00 0 93 048 1 01 1 00 048 1 00 0 93 CF5AA 048 1 01 1 00 CK5A CK5BA 042 1 00 0 93 CK3BA 042 1 00 1 00 CK5A CK5BW 048 1 00 0 93 048 1 00 1 ...

Page 20: ... CK5BA 060 0 98 0 94 CC5A CD5AC 048 0 98 0 99 CK5A CK5BW 048 0 98 0 94 CC5A CD5AW 048 0 99 1 00 CK5A CK5BX 060 1 01 0 93 060 1 01 1 00 COILS 333 B J AV060120 VARIABLE SPEED FURNACE CD5AA 048 0 99 1 00 CC5A CD5AA 060 0 98 0 94 CE3AA 048 0 99 1 00 CC5A CD5AW 048 0 98 0 94 060 1 00 1 00 060 1 01 0 94 CF5AA 048 0 99 0 99 CK3BA 048 0 98 0 94 CK3BA 048 0 99 1 00 CK5A CK5BA 060 0 98 0 94 060 1 00 1 00 CK...

Page 21: ...1 62 53 1 47 1 4 83 51 0 46 1 5 34 48 9 45 1 5 90 46 8 44 0 6 53 44 6 42 8 7 21 57 50 4 50 4 4 80 48 8 48 8 5 31 47 2 47 2 5 88 45 5 45 5 6 50 43 7 43 7 7 19 2000 72 64 8 32 5 5 09 62 3 31 6 5 62 59 7 30 6 6 20 57 0 29 7 6 84 54 2 28 6 7 50 67 59 3 41 5 5 01 57 0 40 6 5 53 54 6 39 6 6 11 52 1 38 6 6 73 49 6 37 6 7 43 62 54 2 50 2 4 94 52 0 49 1 5 46 49 8 47 9 6 02 47 6 46 6 6 65 45 4 45 1 7 34 57 ...

Page 22: ...5 0 KW 1 10 1 25 1 42 1 61 1 82 2 04 2 29 55 TCG 33 2 32 4 31 5 30 4 29 1 27 6 26 1 SDT 75 4 85 3 95 3 105 0 115 0 125 0 135 0 KW 1 07 1 22 1 39 1 59 1 80 2 03 2 27 597C030 F 30 TCG 27 5 26 3 25 0 23 7 22 4 20 9 19 4 SDT 75 0 85 0 95 0 105 0 115 0 125 0 135 0 KW 1 41 1 65 1 91 2 20 2 52 2 86 3 22 35 TCG 30 3 29 0 27 7 26 3 24 8 23 3 21 8 SDT 75 1 85 1 95 1 105 0 115 0 125 0 135 0 KW 1 36 1 60 1 86...

Page 23: ...03 3 48 3 96 4 48 5 03 35 TCG 50 9 48 6 46 3 43 9 41 5 39 0 36 4 SDT 77 0 86 5 96 1 106 0 115 0 125 0 135 0 KW 2 30 2 65 3 04 3 47 3 95 4 46 5 02 40 TCG 55 6 53 2 50 8 48 2 45 7 43 0 40 3 SDT 78 8 88 3 97 8 107 0 117 0 126 0 136 0 KW 2 33 2 68 3 07 3 51 3 98 4 50 5 05 45 TCG 60 6 58 0 55 4 52 7 50 0 47 2 44 3 SDT 80 8 90 2 99 7 109 0 119 0 128 0 138 0 KW 2 35 2 71 3 11 3 55 4 03 4 55 5 12 50 TCG 6...

Page 24: ...g refrigerant tube lengths between 50 and 175 ft consult the Residential Split System Long Line Application Guideline available from equipment distributor 7 If any refrigerant tubing is buried provide a minimum 6 in vertical rise to the valve connections at the unit Refrigerant tubing lengths up to 36 in may be buried without further consideration For buried lines longer than 3 ft consult your loc...

Page 25: ... 25 A98599 MATCHED SYSTEM ...

Page 26: ... 26 ...

Page 27: ... 27 ...

Page 28: ...t Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 597C 1 1 2 to 5 Tons Nominal Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resista...