—5—

 

SPECIFICATIONS Continued

 

* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.

† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).

The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If 
other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is 
used, consult applicable tables of the NEC (ANSI/NFPA 70).

‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.

** Fan motor with ball bearings required.

†† See low-ambient controller Installation Instructions for application.

N/A — Not Applicable.

 

NOTE: 

 

Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

 

UNIT SIZE-SERIES

042-A

048-A

060-A

 

Operating Weight (Lb)

215

217

278

 

ELECTRICAL

 

Unit Volts—Hertz—Phase

208/230-60-1

Operating Voltage Range*

187-253

Compressor—Rated Load Amps

19.9

24.4

30.1

Locked Rotor Amps

127.0

131.0

172.0

Condenser Fan Motor—Full Load Amps

1.10

1.40

1.40

Min Unit Ampacity for Wire Sizing

24.4

26.7

35.9

Min Wire Size (60°C Copper) AWG†

10

8

8

Min Wire Size (75°C Copper) AWG†

10

10

8

Max Wire Length (Ft) (60°C Copper)‡

77

97

80

Max Wire Length (Ft) (75°C Copper)‡

73

59

76

Max Branch Circuit Fuse or 

Circuit Breaker Size (Amps)

40

50

60

 

COMPRESSOR & REFRIGERANT

 

Compressor— Type

Scroll

Manufacturer

Copeland

Temperature & Current Protection

Internal Line Break

Refrigerant—Type

Puron® (R-410A)

Amount (Lb)

6.33

6.83

7.93

 

CONDENSER COIL & FAN 

 

Coil Face Area (Sq Ft)

12.16

12.16

18.3

Fins per In.—Rows—Circuits

25—1—2

25—1—2

25—1—3

Fan Motor—HP (PSC) & RPM

1/5 & 825

1/4 & 1100

1/4 & 1100

Volts—Hertz—Phase

208/230-60-1

Condenser Airflow (CFM)

2800

3400

3400

 

OPTIONAL EQUIPMENT

 

Support Feet

KSASF0101AAA

Coastal Filter

KAACF0801MED

Time Delay Relay

KAATD0101TDR

Cycle Protector

KSACY0101AAA

Crankcase Heater

KAACH1201AAA

Start Assist—Capacitor/Relay Type

KSAHS1501AAA

KSAHS1601AAA

Start Assist—PTC Type

KAACS0201PTC

TXV (Hard Shutoff)

KSATX0301HSZ

KSATX0401HSZ

KSATX0501HSZ

Piston Body

KSAPX0101PIS

Filter Drier (Suction Line) (RCD)

KH45LG141

Evaporator Freeze Thermostat††

KAAFT0101AAA

Liquid-Line Solenoid Valve

KAALS0201LLS

Winter Start Control††

KAAWS0101AAA

Low-Ambient Pressure Switch

KSALA0301410

MotorMaster® Control**

32LT660004

Ball Bearing Fan Motor (RCD)

HC38GE231

HC40GE232

Thermostat—Auto Changeover, 

Non-Programmable, °F/°C, 
1-Stage Heat, 1-Stage Cool

TSTATBBNAC01-B

Thermostat—Auto Changeover, 

7-Day Programmable, °F/°C, 
1-Stage Heat, 1-Stage Cool

TSTATBBPAC01-B

Thermidistat™ Control—

Programmable Thermostat with Humidity Control

TSTATBBPRH01-B

Builder’s Thermostat—Manual Changeover,

Non-Programmable, °F/°C, 
1-Stage Heat, 1-Stage Cool

TSTATBBBAC01-B

Outdoor Air Temperature Sensor

TSTATXXSEN01-B

Backplate for Non-Programmable Thermostat

TSTATXXNBP01

Backplate for Programmable Thermostat

TSTATXXPBP01

Backplate for Builder’s Thermostat

TSTATXXBBP01

Thermostat Conversion Kit (4 to 5 wire)—10 Pack

TSTATXXCNV10

Summary of Contents for 591B

Page 1: ...y Highly Reliable Performance Is delivered through the supe rior design of the system and componentry The reliability of the existing Quantum Plus models has been proven to provide the lowest incidence of warranty service of any product in the Bryant family in the past few years of service Long term reli ability is assured through the use of both high and low pres sure switches which will not allo...

Page 2: ...NTROL SUPPLY CONN 1 9 16 C F N G A B M A99067 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 018 A 23 13 16 22 1 2 27 1 2 2 13 16 6 15 16 13 15 16 18 3 8 5 8 8 3 16 12 1 2 14 16 1 2 2 3 8 20 x 32 024 A 27 13 16 22 1 2 27 1 2 2 13 16 6 15 16 15 15 16 22 3 8 5 8 8 3 16 12 1 2 14 16 1 2 2 15 16 20 x 32 030 A 27 13 16 22 1 2 27 1 2 2 13 16 6 15...

Page 3: ...ns 0 to 50 Ft Tube Length Long Line Applications Maximum Diameter 018 3 8 3 8 5 8 3 4 024 5 8 3 4 030 036 3 4 7 8 042 048 7 8 1 1 8 060 1 1 8 1 1 8 UNIT SIZE SERIES PISTON IDENTIFICATION NO 018 A 49 024 A 59 030 A 63 036 A 67 042 A 73 048 A 78 060 A 90 UNIT SIZE SERIES REQUIRED SUBCOOLING F 018 A 15 024 A 15 030 A 16 036 A 18 042 A 18 048 A 16 060 A 14 M A N U F A C T U R E R CERTIFIED TO ARI AS C...

Page 4: ...700 2000 2000 2500 OPTIONAL EQUIPMENT Support Feet KSASF0101AAA Coastal Filter KAACF0701SML Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Crankcase Heater KAACH1201AAA Start Assist Capacitor Relay Type KSAHS1701AAA KSAHS1501AAA Start Assist PTC Type KAACS0201PTC TXV Hard Shutoff KSATX0201HSZ KSATX0301HSZ Piston Body KSAPX0101PIS Filter Drier Suction Line KH45LG140 Evaporator Freeze Th...

Page 5: ...ircuit Fuse or Circuit Breaker Size Amps 40 50 60 COMPRESSOR REFRIGERANT Compressor Type Scroll Manufacturer Copeland Temperature Current Protection Internal Line Break Refrigerant Type Puron R 410A Amount Lb 6 33 6 83 7 93 CONDENSER COIL FAN Coil Face Area Sq Ft 12 16 12 16 18 3 Fins per In Rows Circuits 25 1 2 25 1 2 25 1 3 Fan Motor HP PSC RPM 1 5 825 1 4 1100 1 4 1100 Volts Hertz Phase 208 230...

Page 6: ...ol provides an approximate 5 minute delay after power to the compressor has been interrupted for any reason including normal room thermostat cycling SUGGESTED USE Installations in areas where power interruptions are frequent Where user is likely to play with the room thermostat All commercial installations Installations where interconnecting tube length exceeds 50 ft High rise applications 7 Evapo...

Page 7: ...nit base minimizing corrosion SUGGESTED USE For improved sound ratings Coastal installations Windy areas or where debris is normally circulating Rooftop installations 15 Thermostatic Expansion Valve TXV A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator Kit includes valve adapter t...

Page 8: ...1 0 9 60 CC5A CD5AW030 23 800 NONE 10 5 11 0 11 0 9 70 CE3AA024 23 400 NONE 10 5 11 0 11 0 9 70 CE3AA030 23 800 NONE 10 5 11 0 11 0 9 75 CF5AA024 23 400 NONE 10 5 11 0 11 0 9 65 CK3BA024 23 400 NONE 10 5 11 0 11 0 9 75 CK3BA030 23 800 NONE 10 5 11 0 11 0 9 80 CK5A CK5BA024 23 400 NONE 10 5 11 0 11 0 9 75 CK5A CK5BA030 23 800 NONE 10 5 11 0 11 0 9 80 CK5A CK5BW024 23 400 NONE 10 5 11 0 11 0 9 75 CK...

Page 9: ...V036060 VARIABLE SPEED FURNACE CC5A CD5AA030 28 000 TDR 11 5 11 5 10 10 CC5A CD5AA036 28 600 TDR 11 5 11 5 10 40 CC5A CD5AW030 28 000 TDR 11 5 11 5 10 10 CE3AA030 28 000 TDR 11 5 11 5 10 15 CE3AA036 28 600 TDR 11 5 11 5 10 25 CK3BA030 28 000 TDR 11 5 11 5 10 15 CK3BA036 28 600 TDR 11 5 11 5 10 50 CK5A CK5BA030 28 000 TDR 11 5 11 5 10 15 CK5A CK5BA036 28 600 TDR 11 5 11 5 10 50 CK5A CK5BT036 28 600...

Page 10: ...0 CK3BA036 35 000 TDR 11 5 11 5 10 15 CK5A CK5BA036 35 000 TDR 11 5 11 5 10 15 CK5A CK5BT036 35 000 TDR 11 5 11 5 10 15 COILS 333 B J AV048080 VARIABLE SPEED FURNACE CC5A CD5AA042 35 400 TDR 11 5 11 5 10 40 CC5A CD5AW036 35 000 TDR 11 5 11 5 10 30 CE3AA036 35 000 TDR 11 5 11 5 10 20 CE3AA042 35 400 TDR 11 5 11 5 10 40 CK3BA042 35 400 TDR 11 5 11 5 10 35 CK5A CK5BA042 35 400 TDR 11 5 11 5 10 35 CK5...

Page 11: ...AA048 41 000 NONE 10 5 11 0 11 0 9 80 CK3BA042 40 500 NONE 10 5 11 0 11 0 9 75 CK3BA048 41 000 NONE 10 5 11 0 11 0 9 80 CK5A CK5BA042 40 500 NONE 10 5 11 0 11 0 9 75 CK5A CK5BA048 41 000 NONE 10 5 11 0 11 0 9 80 CK5A CK5BT042 40 500 NONE 10 5 11 0 11 0 9 75 CK5A CK5BT048 41 000 NONE 10 5 11 0 11 0 9 80 CK5A CK5BW048 41 000 NONE 10 5 11 0 11 0 9 80 F A B 4AN F B C 042 40 500 TDR 11 0 11 0 9 60 F A ...

Page 12: ... 0 9 80 CC5A CD5AC048 46 000 NONE 10 5 11 0 11 0 9 70 CC5A CD5AW048 46 500 NONE 10 5 11 0 11 0 9 80 CC5A CD5AW060 48 000 NONE 10 5 11 0 11 0 10 00 CD5AA048 47 000 NONE 10 5 11 0 11 0 9 80 CE3AA048 47 000 NONE 10 5 11 0 11 0 9 90 CE3AA060 48 000 NONE 10 5 11 0 11 0 10 05 CF5AA048 47 000 NONE 10 5 11 0 11 0 9 85 CK3BA048 47 000 NONE 10 5 11 0 11 0 9 80 CK3BA060 48 000 NONE 10 5 11 0 11 0 10 05 CK5A ...

Page 13: ...AA060 46 500 TDR 11 5 11 5 10 10 CC5A CD5AW060 47 000 TDR 11 5 11 5 10 35 CE3AA060 47 000 TDR 11 5 11 5 10 40 CK3BA060 47 000 TDR 11 5 11 5 10 35 CK5A CK5BA060 47 000 TDR 11 5 11 5 10 35 CK5A CK5BT060 47 000 TDR 11 5 11 5 10 35 CK5A CK5BW048 46 000 TDR 11 5 11 5 10 15 CK5A CK5BX060 47 500 TDR 11 5 11 5 10 55 060 A CC5A CD5AW060 59 000 NONE 10 5 11 0 11 0 9 70 CC5A CD5AA060 56 000 NONE 10 3 10 8 10...

Page 14: ... Seasonal Energy Efficiency Ratio TDR Time Delay Relay TXV Puron Thermostatic Expansion Valve NOTES 1 Ratings are net values reflecting the effects of circulating fan motor heat Supplemental electric heat is not included 2 Tested outdoor indoor combinations have been tested in accordance with DOE test procedures for electric air conditioners Ratings for other com binations are determined under DOE...

Page 15: ... 15 1 55 15 39 15 39 1 76 14 61 14 61 1 99 13 77 13 77 2 25 12 85 12 85 2 53 675 72 20 11 10 86 1 43 19 70 10 82 1 63 19 10 10 72 1 85 18 19 10 44 2 09 17 08 10 06 2 35 15 81 9 60 2 64 67 19 16 13 74 1 41 18 57 13 83 1 60 17 66 13 65 1 82 16 59 13 32 2 07 15 44 12 89 2 34 14 14 12 36 2 62 62 17 82 16 94 1 39 16 89 16 67 1 59 15 93 15 93 1 81 15 13 15 13 2 04 14 25 14 25 2 30 13 30 13 30 2 58 57 17...

Page 16: ... 21 51 13 00 3 35 67 27 09 19 81 2 05 25 72 19 36 2 26 24 22 18 81 2 49 22 64 18 21 2 75 20 95 17 56 3 03 19 13 16 83 3 32 62 24 49 23 63 2 02 22 96 22 96 2 25 21 81 21 81 2 48 20 67 20 67 2 73 19 43 19 43 3 00 18 11 18 11 3 29 57 24 03 24 03 2 02 22 89 22 89 2 25 21 82 21 82 2 48 20 67 20 67 2 73 19 43 19 43 3 00 18 11 18 11 3 30 Multipliers for Determining the Performance With Other Indoor Secti...

Page 17: ... 15 2 75 26 83 26 83 3 03 25 42 25 42 3 33 23 92 23 92 3 66 22 34 22 34 4 03 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 030 0 97 0 99 CK5A CK5BA 030 0 97 0 93 036 1 00 1 00 036 0 99 0 93 CC5A CD5AW 030 0 97 0 99 CK5A CK5BT 036 0 99 0 93 036 1 00 1 00 CK5A CK5BW 030 0 97 0 93...

Page 18: ...ipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 0 99 1 00 CE3AA 036 0 99 0 93 042 1 00 1 00 042 1 00 0 93 CC5A CD5AW 036 0 99 1 00 CK3BA 042 1 00 0 93 CE3AA 036 0 99 1 00 CK5A CK5BA 042 1 00 0 93 042 1 00 1 00 CK5A CK5BT 042 1 00 0 93 CF5AA 036 0 99 1 00 CK5A CK5BW 036 0 99 0 94 ...

Page 19: ... 25 79 4 75 57 34 40 34 40 2 99 32 98 32 98 3 28 31 37 31 37 3 60 29 62 29 62 3 95 27 81 27 81 4 33 25 80 25 80 4 75 1350 72 43 46 23 44 3 12 41 56 22 80 3 42 39 45 22 06 3 75 37 09 21 25 4 11 34 48 20 36 4 49 31 55 19 31 4 90 67 40 23 29 84 3 08 38 21 29 10 3 38 35 97 28 29 3 71 33 52 27 39 4 07 30 89 26 36 4 46 28 15 25 23 4 88 62 36 33 35 44 3 06 34 27 34 27 3 37 32 49 32 49 3 70 30 76 30 76 4 ...

Page 20: ...oor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 0 99 1 00 CE3AA 042 0 98 0 93 CC5A CD5AC 048 0 99 1 00 048 0 99 0 93 CC5A CD5AW 042 0 99 1 00 CK5A CK5BA 042 0 98 0 93 048 1 00 1 00 CK5A CK5BT 042 0 98 0 93 CD5AA 048 1 00 1 00 CK5A CK5BW 048 0 99 0 93 CE3AA 042 0 99 1 00 COILS 333 B J AV060120 VARIABLE SPEED FURNACE 048 1 00 1 00 CC5A CD5AW 042 0 98 0 94 CF5AA 048 1 00 1 00 04...

Page 21: ...ndoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 1 00 1 00 CC5A CD5AW 048 0 98 0 94 CC5A CD5AC 048 0 98 0 99 060 1 00 0 94 CC5A CD5AW 048 0 99 1 00 CE3AA 048 0 98 0 95 060 1 02 1 00 060 1 00 0 95 CD5AA 048 1 00 1 00 CK3BA 060 1 00 0 94 CE3AA 048 1 00 1 00 CK5A CK5BA 060 1 00 0 94 060 1 02 1 01 CK5A CK5BT 060 1 00 0 94 CF5AA 048 1 00 0 99 CK5A CK5B...

Page 22: ...8 40 88 7 78 2000 72 70 41 38 02 5 07 67 22 36 67 5 59 63 69 35 21 6 15 59 83 33 63 6 76 55 55 31 86 7 40 50 53 29 71 8 06 67 65 69 46 32 4 99 62 45 44 98 5 51 59 00 43 56 6 08 55 22 42 01 6 69 50 99 40 29 7 32 46 36 38 32 7 98 62 59 82 54 78 4 94 56 52 53 20 5 47 53 02 51 35 6 03 49 22 49 22 6 60 45 93 45 93 7 25 42 82 42 82 7 97 57 57 09 57 09 4 92 54 55 54 55 5 43 51 94 51 94 6 00 49 04 49 04 6...

Page 23: ...80 2 83 40 TCG SDT KW 26 70 79 50 1 33 25 30 88 70 1 50 23 90 98 00 1 69 22 40 107 10 1 89 20 90 116 20 2 11 19 30 125 20 2 35 17 70 134 10 2 60 15 90 142 80 2 87 45 TCG SDT KW 29 20 81 30 1 36 27 70 90 50 1 53 26 10 99 60 1 71 24 50 108 60 1 92 22 90 117 60 2 13 21 20 126 50 2 38 19 40 135 30 2 63 17 40 143 90 2 90 50 TCG SDT KW 31 90 83 20 1 38 30 20 92 20 1 55 28 50 101 30 1 74 26 80 110 20 1 9...

Page 24: ...0 142 50 4 88 40 TCG SDT KW 47 20 82 00 2 31 44 80 90 90 2 61 42 30 99 90 2 93 39 70 108 80 3 27 37 10 117 60 3 64 34 30 126 40 4 05 31 40 135 10 4 49 28 20 143 70 4 94 45 TCG SDT KW 51 60 84 00 2 36 49 00 92 80 2 65 46 30 101 70 2 97 43 50 110 50 3 32 40 60 119 20 3 69 37 60 127 90 4 10 34 40 136 40 4 53 30 90 144 80 4 99 50 TCG SDT KW 56 30 86 20 2 40 53 40 94 90 2 69 50 40 103 50 3 01 47 40 112...

Page 25: ...not acceptable for the type of connector provided 9 Do not apply capillary tube indoor coils to these units 10 Factory supplied filter drier must be installed This must be replaced each time the refrigeration system is opened for service 11 Do not deviate from factory specified TXV s and Liquid Line Solenoids CONDENSER ONLY RATINGS Continued 591BN060 A 30 TCG SDT KW 58 20 83 60 3 22 55 10 92 50 3 ...

Page 26: ... 26 MATCHED SYSTEM A98599 ...

Page 27: ... 27 ...

Page 28: ...w Alternatives Program SNAP Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 591B 1 1 2 to 5 Tons Nominal Fans Condenser fan will be direct drive propeller type discharging air upward Condenser fan motors will be total...

Reviews: