SPECIFICATIONS
See notes on page 5.
UNIT SIZE-SERIES
018-A
024-A
030-A
036-A
Operating Weight (Lb)
168
178
188
198
ELECTRICAL
Unit Volts—Hertz—Phase
208/230-60-1
Operating Voltage Range*
187-253
Compressor— Rated Load Amps
10.3
13.5
15.4
17.9
Locked Rotor Amps
51.0
61.0
73.0
100.0
Condenser Fan Motor—Full Load Amps
0.50
0.75
0.75
1.40
Min Unit Ampacity for Wire Sizing
13.4
17.4
19.2
20.1
Min Wire Size (60°C Copper) AWG†
14
14
14
12
Min Wire Size (75°C Copper) AWG†
14
14
14
12
Max Wire Length (Ft) (60°C Copper)‡
56
44
39
52
Max Wire Length (Ft) (75°C Copper)‡
54
42
37
50
Max Branch Circuit Fuse or
Circuit Breaker Size (Amps)
20
30
30
40
COMPRESSOR & REFRIGERANT
Compressor— Type
Scroll
Manufacturer
Copeland
Temperature & Current Protection
Internal Line Break
Refrigerant— Type
Puron® (R-410A)
Amount (Lb)
4.15
4.66
5.28
6.13
CONDENSER COIL & FAN
Coil Face Area (Sq Ft)
7.27
8.72
8.72
10.9
Fins per In.—Rows—Circuits
20—1—1
25—1—2
25—1—2
25—1—2
Fan Motor—HP (PSC) & RPM
1/12 & 1100
1/10 & 1100
1/10 & 1100
1/10 & 1100
Volts—Hertz—Phase
208/230-60-1
Condenser Airflow (CFM)
1700
2000
2000
2500
OPTIONAL EQUIPMENT
Support Feet
KSASF0101AAA
Coastal Filter
KAACF0701SML
Time Delay Relay
KAATD0101TDR
Cycle Protector
KSACY0101AAA
Crankcase Heater
KAACH1201AAA
Start Assist—Capacitor/Relay Type
KSAHS1701AAA
KSAHS1501AAA
Start Assist—PTC Type
KAACS0201PTC
TXV (Hard Shutoff)
KSATX0201HSZ
KSATX0301HSZ
Piston Body
KSAPX0101PIS
Filter Drier (Suction Line)
KH45LG140
Evaporator Freeze Thermostat†† (RCD)
KAAFT0101AAA
Liquid-Line Solenoid Valve
KAALS0201LLS
Winter Start Control††
KAAWS0101AAA
Low-Ambient Pressure Switch
KSALA0301410
MotorMaster® Control** (RCD)
32LT660004
Ball Bearing Fan Motor (RCD)
HC34GE232
Thermostat—Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBNAC01-B
Thermostat—Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBPAC01-B
Thermidistat™ Control—
Programmable Thermostat with Humidity Control
TSTATBBPRH01-B
Builder’s Thermostat—Manual Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBBAC01-B
Outdoor Air Temperature Sensor
TSTATXXSEN01-B
Backplate for Non-Programmable Thermostat
TSTATXXNBP01
Backplate for Programmable Thermostat
TSTATXXPBP01
Backplate for Builder’s Thermostat
TSTATXXBBP01
Thermostat Conversion Kit (4 to 5 wire)—10 Pack
TSTATXXCNV10
Summary of Contents for 591B
Page 26: ... 26 MATCHED SYSTEM A98599 ...
Page 27: ... 27 ...