REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access
. . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel
. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)
UNIT
589A
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lb
kg
A
B
C
D
042060/080
208/230-1-60, 208/230-3-60, 460-3-60
391
178
100/45
91/41
120/55
80/36
042100/120
208/230-1-60, 208/230-3-60, 460-3-60
403
183
103/47
94/43
123/56
83/38
048080
208/230-1-60, 208/230-3-60, 460-3-60
422
192
109/50
85/39
158/72
70/32
048100/120/140
208/230-1-60, 208/230-3-60, 460-3-60
434
197
112/51
88/40
161/73
73/33
060080
208/230-1-60, 208/230-3-60
453
206
117/53
93/42
167/76
76/35
060100/120/140
208/230-1-60, 208/230-3-60
465
211
120/55
96/44
167/76
82/37
UNIT
589A
CENTER OF GRAVITY (in./mm)
X
Y
Z
042060/080
26.66/677
21.19/538
15.35/390
042100/120
26.61/676
21.21/539
15.35/390
048080
28.45/723
19.95/507
15.35/390
048100/120/140
28.35/720
19.99/508
15.35/390
060080
28.36/720
23.27/591
15.35/390
060100/120/140
27.95/710
23.23/590
15.35/390
LEGEND
CG
— Center of Gravity
COND — Condenser
LV
— Low Voltage
MAT’L
— Material
NEC
— National Electrical Code
REQ’D — Required
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
Fig. 8 — 589A042-060 Without Base Rail, Unit Dimensions
—8—