A. Units Without Base Rail
If accessory rigging brackets are to be used for rigging, in-
stall them as follows:
WARNING:
Secure screws and paint protectors sol-
idly against unit basepan to hold lifting brackets in
position.
Never use lifting brackets when the temperature is be-
low −10 F.
Never exceed 200 lbs per bracket of lifting force.
Never use lifting brackets for lifting other models of air-
conditioning units.
Lifting point should be directly over the unit center of
gravity.
1. Position brackets as close to the corners of unit as pos-
sible. Be sure brackets are well outside of center of grav-
ity. (See Fig. 2, 4, 6, 8, and 12.).
2. Position paint protectors and foam strips between screws
and painted surface of unit. Tighten screws until they
make contact with the paint protectors.
3. Secure device or hook of sufficient strength to hole in
bracket as shown in detail ‘‘A’’ of Fig. 12.
4. If wood top is available, use it for a spreader bar to pre-
vent straps from damaging unit. If wood top is not avail-
able, use spreader bars of sufficient length.
Fig. 11 — Slab Mounting Details
NOTICE TO RIGGERS
Hook rigging shackles through holes in lifting brackets, as shown in De-
tail ‘‘A.’’ Lifting brackets to be centered around the unit center of gravity.
Use wooden top skid when rigging, to prevent rigging straps from dam-
aging unit.
CAUTION:
All panels must be in place when rigging.
UNIT
588A
MAX
WEIGHT
A
B
C
Size
lb
kg
in.
mm
in.
mm
in.
mm
018
332
150
49.4
1255
24.3
618
24.85
631
024
375
170
22.4
570
24.85
631
030
384
174
22.3
565
24.85
631
036
408
185
22.0
559
24.85
631
042
447
203
22.5
571
28.85
733
048
486
220
21.0
533
34.85
885
060
525
238
21.5
545
34.85
885
UNIT
589A
024
405
184
49.4
1255
22.8
579
28.9
733
030
408
185
22.4
569
28.9
733
036
438
199
22.4
569
28.9
733
042
463
210
22.8
579
34.9
885
048
494
224
21.1
536
34.9
885
060
525
238
21.5
545
34.9
885
Fig. 12 — Suggested Rigging for Units Without
Base Rail
NOTICE TO RIGGERS
Hook rigging shackles through holes in lifting brackets, as shown in De-
tail ‘‘A.’’ Lifting brackets to be centered around the unit center of gravity.
Use wood top skid when rigging, to prevent rigging straps from damag-
ing unit. Remove 4 screws to slide wood support through rectangular
hole in rail.
CAUTION:
All panels must be in place when rigging.
UNIT
588A
MAX
WEIGHT
A
B
C
Size
lb
kg
in.
mm
in.
mm
in.
mm
018
320
145
49.4
1255
24.4
619
28.2
715
024
363
165
22.6
574
28.2
715
030
380
172
22.5
571
28.2
715
036
396
180
22.2
563
28.2
715
042
435
197
22.6
574
32.2
816
048
474
215
21.2
538
38.2
969
060
513
233
21.6
549
38.2
969
UNIT
589A
024
393
178
49.4
1255
22.9
582
32.2
816
030
396
180
22.6
574
32.2
816
036
426
193
22.5
571
32.2
816
042
451
205
22.9
582
38.2
969
048
482
219
21.3
540
38.2
969
060
513
233
21.6
549
38.2
969
Fig. 13 — Suggested Rigging for Units With
Optional Base Rail
—12—
Summary of Contents for 588A