32
Relative Humidity Sensor
(Polarized Male Connector)
J4-1 or J4-4 + 24 VDC Supply Voltage
J4-2 or J4-5 (-) 4 to 20 mA Current Loop Output
to RTU-OPEN
4-20 VAC GND 0-5V
mA or or
VDC 0-10V
SPAN
ZERO
C10839
Fig. 60 -- Duct Relative Humidity Sensor Typical Wiring
Humidistat:
Use of a field--supplied humidistat provides
the RTU Open insight to the relative humidity in the
space. The humidistat reads the RH level in the space and
compares it to its setpoint to operate a dry contact. The
humidistat is a dedicated input on the configurable input 9
and tells the RTU Open when the RH level is HIGH or
LOW. The normal condition for humidity is LOW. A
normally open humidistat is the factory default control for
the Perfect Humidity
t
option.
To wire in the field:
S
J5--8 = 24 VAC source for dry contact
S
J5--7 = Signal input
Smoke Detector/Fire Shutdown (FSD) —
On 581J*14 units equipped with factory--installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The RTU Open
controller communicates the smoke detector’s tripped status
to the BAS building control. See Figs. 47 and 48, the RTU
Open System Control Wiring Diagrams.
The
Fire
Shutdown
Switch
configuration,
MENU
Config
Inputs
input
5
,
identifies
the
normally open status of this input when there is no fire
alarm.
Connecting Discrete Inputs —
Filter Status:
The filter status accessory is a field--installed
accessory. This accessory detects plugged filters. When
installing this accessory, the unit must be configured for
filter status by setting
MENU
Config
Inputs
input 3, 5,
8, or 9
to Filter Status and normally open (N/O) or normally
closed (N/C). Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 46 and Fig. 47 or Fig. 48 for wire
terminations at J5.
Fan Status:
The fan status accessory is a field--installed
accessory. This accessory detects when the indoor fan is
blowing air. When installing this accessory, the unit must
be
configured
for
fan
status
by
setting
MENU
Config
Inputs
input 3, 5, 8, or 9
to Fan
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 46 and Fig. 47 or Fig. 48 for wire terminations at J5.
Remote Occupancy:
The remote occupancy accessory is
a field--installed accessory. This accessory overrides the
unoccupied mode and puts the unit in occupied mode.
When installing this accessory, the unit must be
configured
for
remote
occupancy
by
setting
MENU
Config
Inputs
input 3, 5, 8, or 9
to Remote
Occupancy and normally open (N/O) or normally closed
(N/C).
Also set
MENU
Schedules
occupancy source
to DI
on/off. Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 46 and Table 5 for wire
terminations at J5.
Power Exhaust (output):
The relay used by the RTU
Open board to control power exhaust is a dry contact
which means it does not have 24vac. This 24vac must be
connected to the relay to allow it to operate the power
exhaust relay in the PE accessory. A 24vac source must be
provided to J11--2 on the RTU Open control board. This
can be provided by the unit’s transformer from various
sources. The “R” terminal on the unit’s low voltage
terminal board (LVTB) is a logical source. Refer to Fig. 46
and Fig. 47 or Fig. 48 for wire terminations at J11.
581J
*14
Summary of Contents for 581Jx14 series
Page 4: ...4 C11338 Fig 2 Unit Dimensional Drawing 14 Size Unit 581J 14 ...
Page 5: ...5 C11339 Fig 2 Unit Dimensional Drawing 14 Size Unit cont 581J 14 ...
Page 8: ...8 C10772 Fig 4 Roof Curb Details 581J 14 ...
Page 26: ...26 C150061 Fig 47 RTU Open System Control Wiring Diagram 581J 14 ...
Page 27: ...27 C150062 Fig 48 RTU Open System Control Wiring Diagram with Perfect Humidityt 581J 14 ...