6
Bearings
This fan system uses bearings featuring concentric split
locking collars. The collars are tightened through a cap
screw bridging the split portion of the collar. The cap
screw has a Torx T25 socket head. To tighten the locking
collar: Hold the locking collar tightly against the inner
race of the bearing and torque the cap screw to 65
−
70
in
−
lb (7.4
−
LOCKING COLLAR
T-25 TORX SOCKET
HEAD CAP SCREW
C11505
Fig. 7
−
Tightening Locking Collar
2
−
SPEED INDOOR FAN MOTOR SYSTEM
WITH VARIABLE FREQUENCY
DRIVE (VFD)
NOTE
: The 2
−
Speed Indoor Fan option is not available
on units with Perfect Humidity
™
humidification system.
The
2
−
Speed Indoor Fan
system utilizes a Fan Speed
control board and Variable Frequency Drive (VFD) to
automatically adjust the indoor fan motor speed in
sequence with the unit’s ventilation, cooling and heating
operation. Conforming to ASHRAE 90.1 2010 Standard
Section 6.4.3.10.b, during the first stage of cooling
operation the system will adjust the fan motor to provide
two- thirds (2/3) of the design airflow rate for the unit.
When the call for the second stage of cooling is required,
the
2
−
Speed Indoor Fan
system will allow the design
airflow rate for the unit established (100%). During the
heating mode, the system will allow total design airflow
rate (100%) operation. During ventilation mode, the
system will operate the fan motor at 2/3 speed.
Identifying Factory Option
This supplement only applies to units that meet the
criteria detailed in Table 1. If the unit does not meet that
criteria, discard this document.
Table 1 — Model
−
Size / VFD Option Indicator
Model / Sizes
Position in
Model Number
VDP
FIOP Indicator
580J 17
−
28
17
G, J
NOTE
: See Appendix I for a complete model number
nomenclature display.
Unit Installation with 2
−
Speed Indoor Fan
Motor Option
580J Rooftop—
Refer to the base unit installation
instructions for standard required operating and service
clearances.
NOTE
:
The Remote VFD Keypad is a field-installed op
tion. It is not included as part of the Factory installed VFD
option. See
“Variable Frequency Drive (VFD) Installa
tion, Setup and Troubleshooting Supplement”
for wiring
schematics and performance charts and configuration. See
Fig. 8 for location of the (VFD) as mounted on the various
580J models.
Variable
Frequency
Drive (VFD)
C11531
Fig. 8
−
VFD Location for 580J 15–27.5 Units
ADDITIONAL VFD INSTALLATION
AND TROUBLESHOOTING
Additional installation, wiring and troubleshooting infor
mation for the VFD can be found in the following manu
als:
“Variable Frequency Drive (VFD) Installation, Setup
and Troubleshooting Supplement.”
Motor
To replace the motor, use the following steps. See Fig. 9.
BLOWER PULLEY
V-BELT
MOTOR PULLEY
MOTOR
MOTOR MOUNTING
BOLTS (4)
JACK BOLT
JAM NUT (2)
JACK BOLT (2)
C12034
Fig. 9
−
Replacing Belt Driven Motor
Summary of Contents for 580J D17
Page 81: ...81 APPENDIX IV WIRING DIAGRAMS cont C160042 Fig 73 580J D17 D28 Power Diagram 208 230 3 60 ...
Page 82: ...82 APPENDIX IV WIRING DIAGRAMS cont C160043 Fig 74 580J D17 D28 Power Diagram 460 3 60 ...
Page 83: ...83 APPENDIX IV WIRING DIAGRAMS cont C160044 Fig 75 580J D17 D28 Power Diagram 575 3 60 ...
Page 88: ...88 APPENDIX IV WIRING DIAGRAMS cont C160049 Fig 80 RTU OPEN Wiring Diagram ...