12
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor (if equipped).
4. Connect field L1 to black wire on connection 11 of the
compressor contactor.
5. Connect field wire L2 to yellow wire on connection 23 of
the compressor contactor.
Three--phase units:
1. Run the high--voltage (L1, L2, L3) and ground lead into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor (if equipped).
4. Connect field L1 to black wire on connection 11 of the
compressor contactor.
5. Connect field wire L3 to yellow wire on connection 13 of
the compressor contactor.
6. Connect field wire L2 to blue wire from compressor.
Special Procedures for 208--v Operation
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Make sure the power supply to the unit is switched OFF and
install lockout tag. before making any wiring changes. With
disconnect switch open, move black wire from transformer
(3/16 in. [4.8 mm]) terminal marked 230 to terminal marked
208. This retaps transformer to primary voltage of 208 vac.
!
WARNING
ELECTRICAL SHOCK FIRE/EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury or death and property damage.
Before making any wiring changes,
make sure
the gas
supply is switched off first.
Then
switch off the power
supply to the unit and install lockout tag.
!
WARNING
Control Voltage Connections
Do not use any type of power--stealing thermostat. Unit control
problems may result.
Use no. 18 American Wire Gage (AWG) color--coded, insulated
(35
_
C minimum) wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located
more than 100 ft (30.5 m) from the unit (as measured along the
control voltage wires), use no. 16 AWG color--coded, insulated
(35
_
C minimum) wires.
Standard Connection
Run the low--voltage leads from the thermostat, through the inlet
hole, and into unit low--voltage splice box.
Locate six (seven for 3--phase) 18--gage wires leaving control box.
These low--voltage connection leads can be identified by the colors
red, green, yellow, brown, blue, and white (See Fig. 10). A gray
wire is standard on 3--phase units for connection to an economizer.
Ensure the leads are long enough to be routed into the low--voltage
splice box (located below right side of control box). Route leads
through hole in bottom of control box and make low--voltage
connections (See Fig. 10). Secure all cut wires, so that they do not
interfere with operation of unit.
POWER
SUPPLY
FIELD-SUPPLIED
FUSED DISCONNECT
HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)
EQUIP GR
3-PHASE SHOWN
1-PHASE USES
TWO POWER
LEADS
CONTROL BOX
SPLICE BOX
LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)
W
Y
G
R
C
WHT(W1)
YEL(Y)
GRN(G)
RED(R)
BRN(C)
THERMOSTAT
(TYPICAL)
DH
BLU(DH)
GRA(Y2)
3-Phase
Only
A09053
Fig. 10 -- High-- and Control--Voltage Connections
Heat Anticipator Setting (Electro--Mechanical
Thermostats only)
The room thermostat heat anticipator must be properly adjusted to
ensure proper heating performance. Set the heat anticipator, using
an ammeter between the W and R terminals to determine the exact
required setting.
NOTE
: For thermostat selection purposes, use 0.18 amp for the
approximate required setting. Failure to make a proper heat
anticipator adjustment will result in improper operation, discomfort
to the occupants of the conditioned space, and inefficient energy
utilization; however, the required setting may be changed slightly
to provide a greater degree of comfort for a particular installation.
Transformer Protection
The transformer is of the energy--limiting type, however a direct
short will likely blow a secondary fuse. If an overload or short is
present, correct overload condition and check for blown fuse on
Indoor Fan board or Integrated Gas Controller. Replace fuse as
required with correct size and rating.
574D
--
--
A
Summary of Contents for 574D----A
Page 3: ...3 A09469 Fig 2 574D A24 36 Unit Dimensions 574D A ...
Page 4: ...4 A09470 Fig 3 574D A42 60 Unit Dimensions 574D A ...
Page 16: ...16 A09282 Fig 14 208 230 1 60 Connection Wiring Diagram 574D A ...
Page 17: ...17 A09282 Fig 14 Cont 208 230 1 60 Ladder Wiring Diagram 574D A ...
Page 18: ...18 A09264 Fig 15 208 230 3 60 Connection Wiring Diagram 574D A ...
Page 19: ...19 A09264 Fig 15 Cont 208 230 3 60 Ladder Wiring Diagram 574D A ...
Page 20: ...20 A09265 Fig 16 460 3 60 Connection Wiring Diagram 574D A ...
Page 21: ...21 A09265 Fig 16 Cont 460 3 60 Ladder Wiring Diagram 574D A ...
Page 25: ...25 Table 7 Cooling Charging Chart A08490 574D A ...
Page 50: ...50 A10098 Fig 45 Economizer Wiring Diagram 574D A ...
Page 51: ...51 A10075 Fig 46 Connection Wiring Diagram 230 3 574D A ...
Page 52: ...52 A10075 Fig 46 Cont Ladder Wiring Diagram 230 3 574D A ...
Page 53: ...53 A10087 Fig 47 Connection Wiring Diagram 460 3 574D A ...
Page 54: ...54 A10087 Fig 48 Ladder Wiring Diagram 460 3 574D A ...
Page 58: ...58 A10064 Fig 49 574D A 30 36 3 Phase with Economizer 574D A ...
Page 59: ...59 A10065 Fig 50 574D A 42 60 3 Phase with Economizer 574D A ...