background image

Air requirements for operation of exhaust fans, kitchen ventilation
systems, clothes dryers, and fireplaces shall be considered in
determining the adequacy of a space to provide combustion-air
requirements.

In unconfined spaces in buildings of conventional frame, brick, or
stone construction, infiltration MAY be adequate to provide air for
combustion, ventilation, and dilution of flue gases. This determi-
nation must be made on an individual installation basis and must
take into consideration the overall volume of unconfined space, the
number of windows and ventilation openings, the number of doors
to the outside, internal doors which can close off unconfined space,
and overall tightness of building construction. Consideration must
also be given to the amount of storage items (furniture, boxes, etc.)
within the unconfined space which takes away form air volume.

Many new buildings and homes (and older ones that have been
weatherized) MUST BE considered as being of tight construction,
therefore, infiltration will not be sufficient to supply necessary air
for combustion and ventilation.

A building can be considered as being of tight construction when:

1. Walls and ceilings exposed to outside atmosphere have a

continuous water vapor retarder with a rating of 1 perm or
less with openings gasketed or sealed, and/or

2. Weatherstripping has been added on operable windows and

doors, and/or

3. Caulking or sealants are applied to areas such as joints

around window and door frames; between sole plates and
floors; between wall-ceiling joints; between wall panels; at
penetrations for plumbing, electrical, and fuel lines; and at
other openings.

If combustion and ventilation air must be supplied to an uncon-
fined space from outside, an opening with a FREE AREA of not
less than 1 sq in. per 1000 Btuh of total input of all appliances
within unconfined space (but not less than 100 sq in.) must be
provided. This opening must be located such that it can not be
blocked at any time.

For a confined space, where air is taken from an interior space, 2
permanent openings of equal area are required. One opening must
be within 12 in. of ceiling and the other within 12 in. of floor. Each
opening must have a free area of at least 1 sq in. per 1000 Btuh of
total input rating but not less than 100 sq in.

If outside air is supplied to a confined space, then the 2 openings
must be equal and located as above. The free area of each must be:

1. One sq in. per 4000 Btuh of total input rating when air is

directly communicated from outdoors.

2. One sq in. per 4000 Btuh of total input rating when air is

brought in through vertical ducts.

3. One sq in. per 2000 Btuh of total input rating when air is

transferred through horizontal ducts.

When ducts are used to supply air, they must be of the same cross
sectional area as free area of openings to which they connect.

The minimum dimension of rectangular air ducts must not be less
than 3 in.

In calculating free area, consideration shall be given to blocking
effect of louvers, grilles, or screens protecting openings. Screens
used shall not be smaller than 1/4-in. mesh and shall be readily
accessible for cleaning. If free area through a design of louver or
grille is known, it shall be used in calculating size design and free
area specified. If design and free area are not known, it may be
assumed that wood louvers have 20 percent free area and metal
louvers and grilles have 60 percent free area. Louvers shall be
fixed in open position or interlocked with furnace so they open
automatically at furnace start-up and remain open during furnace
operation.

WARNING:

Do not block combustion-air openings in

the furnace. Any blockage will result in improper com-
bustion which may result in a fire hazard and/or cause
bodily harm.

The lack of a proper amount of combustion air can lead to serious
furnace operational problems. Some of these problems are:

1. Excessive oil burner after drip and oil fumes.

2. Sooting.

3. Melted oil burner couplings and/or ignitor/relay control.

4. A condition where air band or air shutter settings must be

more open than normal to achieve proper combustion.

5. Lockouts on start-up.

II.

DUCT WORK RECOMMENDATIONS

The proper sizing of warm air ducts is necessary to ensure
satisfactory furnace operation. Duct work should be in accordance
with the latest editions of NFPA-90A (Installation of Air Condi-
tioning and Ventilating Systems) and NFPA-90B (Warm Air
Heating and Air Conditioning Systems) or Canadian equivalent.

The supply duct work should be attached to flanged opening
provided at discharge end of furnace. See Fig. 7 for dimensions of
this opening.

Knock-outs are provided on both sides and bottom of furnace to
facilitate locating the panel cut-out required to connect to return
duct work. Only 1 opening should be used. Upflow installations
may use any 1 of the openings, as appropriate. For horizontal
installations, we recommend the use of bottom opening (although
side openings may be used if necessary). Furnace cutouts must be
full size specified by corner markers. (See Fig. 7.) Undersized
cut-outs adversely affect airflow capacity of furnace.

NOTE:

THE BACK MUST NOT BE CUT OUT FOR RETURN

AIR.

When the provided external filter rack is used, return-air duct
should be attached as shown in Fig. 1.

The following recommendations should be followed when install-
ing duct work:

1. Install locking-type dampers in all branches of individual

ducts to balance out system. Dampers should be adjusted to
impose proper static at outlet of furnace.

2. A flexible duct connector of noncombustible material

should be installed at unit on both supply- and return-air
systems. In applications where extremely quiet operation is
necessary, the first 10 ft (if possible) of supply and return
ducts should be internally lined with acoustical material.

3. In cases where return-air grille is located close to fan inlet,

there should be at least one 90° air turn between fan inlet
and grille. Further reduction in sound level can be accom-
plished by installing acoustical air turning vanes or lining
duct as described in item 2 above.

4. When a single air grille is used, duct between grille and

furnace must be the same size as return opening in furnace.

CAUTION:

Return-air grilles and warm air registers

must not be obstructed.

—3—

Summary of Contents for 363AAP

Page 1: ...NITY OF THIS OR ANY OTHER APPLIANCE DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT WARNING For use with...

Page 2: ...r attic installation As this unit may be installed as an upflow or horizontal furnace it may be located in a basement on the same level as area to be heated suspended or in a crawlspace In any case un...

Page 3: ...g openings Screens used shall not be smaller than 1 4 in mesh and shall be readily accessible for cleaning If free area through a design of louver or grille is known it shall be used in calculating si...

Page 4: ...chimney is properly lined and sized per the applicable codes Refer to list of codes in Safety Consid erations section II MASONRY CHIMNEY This furnace can be vented into an existing masonry chimney Th...

Page 5: ...humidifier connection See Fig 9 These terminals are energized with 115v 0 5 amp maximum during any call for heat FILTERS It is NECESSARY THAT ALL FURNACES BE EQUIPPED WITH A FILTER An external filter...

Page 6: ...SCREW FILTER RACK FILTER ACCESS PANEL REAR OF FURNACE BASE PANEL FLUSH WITH REAR OF FURNACE SIDE FILTER RACK ALIGNMENT FILTER RACK BOTTOM FILTER RACK REAR PANEL REST FLANGE ON TOP OF BOTTOM PANEL FLA...

Page 7: ...ed with damper The draft regulator should be adjusted after furnace has been firing for at least 10 minutes and stack draft should be measured and set between 0 025 and 0 035 in wc The draft should be...

Page 8: ...User s Manual FAILURE TO FOLLOW THIS WARNING COULD RESULT IN POSSIBLE DAMAGE TO THIS EQUIPMENT SERIOUS PER SONAL INJURY OR DEATH WARNING Before performing any service functions unless operations spec...

Page 9: ...dous condition which could lead to bodily harm 15 Before reassembly heat exchanger and combustion cham ber should be inspected to determine if replacement is required After cleaning place combustion c...

Page 10: ...reduces efficiency of your system causes erratic performance of controls and could result in damage to motor or heating equipment 1 Inspect filters at regular intervals depending upon dirt conditions...

Page 11: ...0 7 0 8 0 9 1 0 060210 High 2485 2395 2305 2250 2145 2075 1975 1885 1780 1675 Medium 2195 2125 2060 1990 1915 1860 1785 1700 1620 1525 Low 1640 1590 1540 1515 1460 1410 1350 1275 1190 1075 NOTES 1 Air...

Page 12: ...DUCT CLEANOUT PORTS CLEANOUT PORTS A96336 DIMENSIONS IN UNIT SIZE UNIT DIMENSIONS DUCT SUPPLY OPENING FLUE DIAMETER SIDE RETURN OPENING END BOTTOM RETURN OPENING SIDE RETURN DUCT SIZE END BOTTOM RETUR...

Page 13: ...Fig 8 Barometric Damper Locations A95117 FIG A FIG G FIG D FIG L FIG B FIG C FIG J FIG H FIG K POOR WRONG WRONG WRONG WRONG WRONG BAROMETRIC DAMPER LOCATIONS GOOD LOCATIONS BAD LOCATIONS 13...

Page 14: ...ING MUST CONFORM TO CURRENT CSA 22 1 CANADIAN ELECTRICAL CODE PART 1 AND OR LOCAL CODES 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATE...

Page 15: ...fore attempting to put your furnace into operation for the heating season you should perform the following procedures WARNING If you do not follow these instructions exactly a fire or explosion may re...

Page 16: ...eo based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays divi...

Reviews: