NOTE:

Pipe length (ft) specified for maximum pipe lengths

located in unconditioned spaces cannot exceed total allowable pipe
length as specified in Table 5.

B.

Two-Pipe Termination Kit

1. Determine location for termination.

Consideration of the following should be made when
determining an appropriate location for termination kit.

a. Comply with all clearance requirements as stated in

Table 4.

b. Termination kit should be positioned where vent vapors

will not damage plants/shrubs or air conditioning equip-
ment.

c. Termination kit should be positioned so it will not be

affected by wind eddy (such as inside building corners)
or accumulation of airborne leaves or light snow, or
allow recirculation of flue gases.

d. Termination kit should be positioned where it will not be

damaged by or subjected to foreign objects, such as
stones, balls, etc.

e. Termination kit should be positioned where vent vapors

are not objectionable.

2. Cut 2 holes, 1 for each pipe, of appropriate size for pipe size

being used.

3. Loosely install elbow in bracket and place assembly on

combustion-air pipe.

Roof terminations—Loosely install pipe coupling on prop-
erly cut vent pipe. Coupling must be positioned so bracket
will mount as shown in Fig. 31.

For applications using combustion-air pipe option, indi-
cated by dashed lines in Fig. 31, install 90° street elbow into
90° elbow, making U-fitting. A 180° U-fitting may be used.

Sidewall terminations—Install bracket as shown in Fig. 34
or 35.

For applications using vent pipe option indicated by dashed
lines in Fig. 34, rotate vent elbow 90° from position shown
in Fig. 34.

4. Disassemble loose pipe fittings. Clean and cement using

same procedures as used for system piping.

5. Check required dimensions as shown in Fig. 31, 34, or 35.

C.

Concentric Vent/Air Termination Kit

1. Determine location for termination.

Consideration of the following should be made when
determining an appropriate location for termination kit.

a. Comply with all clearance requirements as stated in

Table 4.

b. Termination kit should be positioned where vent vapors

will not damage plants/shrubs or air conditioning equip-
ment.

c. Termination kit should be positioned so it will not be

affected by wind eddy (such as inside building corners)
or accumulation of airborne leaves or light snow, or
allow recirculation of flue gases.

d. Termination kit should be positioned where it will not be

damaged by or subjected to foreign objects, such as
stones, balls, etc.

e. Termination kit should be positioned where vent vapors

are not objectionable.

2. Cut one 4-in. diameter hole for 2-in. kit, or one 5-in.

diameter hole for 3-in. kit.

3. Loosely assemble concentric vent/air termination compo-

nents together using instructions in kit.

4. Slide assembled kit with rain shield REMOVED through

hole.

NOTE:

Do not allow insulation or other materials to accumulate

inside of pipe assembly when installing it through hole.

Roof terminations—Locate assembly through roof to ap-
propriate height as shown in Fig. 32.

Sidewall terminations—Locate assembly through sidewall
with rain shield positioned no more than 1-in. from wall as
shown in Fig. 33.

5. Disassemble loose pipe fittings. Clean and cement using

same procedures as used for system piping.

6. Check required dimensions as shown in Fig. 32 or 33.

IV.

MULTIVENTING AND VENT TERMINATIONS

When 2 or more 355MAV Furnaces are vented near each other,
each furnace must be individually vented. NEVER common vent
or breach vent 355MAV furnaces. When 2 or more 355MAV

TABLE 6—MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH INSULATION IN WINTER DESIGN

TEMPERATURE AMBIENT*

UNIT

SIZE

WINTER

DESIGN TEMPERA-

TURE (°F)

MAXIMUM PIPE

DIAMETER

INSULATION THICKNESS (IN.)†

0

3/8

1/2

3/4

1

042040

20

2

21

37

42

50

57

0

2

10

22

25

30

35

-20

2

5

14

17

21

25

042060

20

2

30

55

61

70

70

0

2

16

33

38

46

53

-20

2

9

23

26

33

38

042080

060080

20

2

37

65

70

70

70

0

2

20

39

45

55

63

-20

2

11

27

31

39

45

060100

20

2-1/2

41

70

70

70

70

0

2-1/2

21

42

48

59

68

-20

2-1/2

11

28

33

41

49

060120

20

3

49

70

70

70

70

0

3

26

51

58

70

70

-20

3

15

35

40

50

59

* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as
specified in Table 5.
† Insulation thickness based on R value of 3.5 per in.

—27—

Summary of Contents for 355MAV C Series

Page 1: ...Concentric Vent and Combustion Air Termination Kit Installation 25 27 Multiventing and Vent Terminations 27 29 CONDENSATE DRAIN 29 General 29 Application 29 Condensate Drain Protection 29 SEQUENCE OF...

Page 2: ...TLET 26 15 16 28 1 2 22 5 16 19 13 16 5 8 5 16 1 39 7 8 22 1 4 TYP 11 16 7 16 24 3 16 BOTTOM INLET 18 1 4 22 11 16 2 IN COMBUSTION AIR CONN 1 2 IN DIA GAS CONN 7 8 IN DIA POWER CONN 1 2 IN DIA THERMOS...

Page 3: ...ro static potential 1 Disconnect all power to the furnace DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY S ELECTROSTATIC CHARGE TO GROUND 2 Firmly touch a...

Page 4: ...and all authorities having jurisdiction These instructions cover minimum requirements for a safe instal lation and conform to existing national standards and safety codes In some instances these inst...

Page 5: ...ing tabs inward and rotating trap 3 Remove casing hole filler cap from casing hole See Fig 2 or 6 4 Install casing hole filler cap into blower shelf hole where trap was removed 5 Install condensate tr...

Page 6: ...roper connections UPPER INDUCER HOUSING DRAIN CONNECTION Attached to the UPPER unused inducer housing drain connection is a cap and clamp This cap is used to prevent condensate leakage in this applica...

Page 7: ...ector box drain tube blue and white striped label which was pre viously plugged b Connect larger diameter drain tube factory supplied in loose parts bag to drain tube coupling extending collector box...

Page 8: ...arts bag to extend collector box pressure tube green label which was previously connected to condensate trap relief port connection 3 Connect collector box pressure tube green label to pres sure switc...

Page 9: ...The LOWER collector box pressure tube pink label is factory connected to the pressure switch and should not require any modification NOTE See Fig 9 or tube routing label on main furnace door to check...

Page 10: ...ig 11 or tube routing label on main furnace door to check for proper connections Relocate tubes as described below 1 Disconnect collector box pressure tube pink label attached to pressure switch 2 Use...

Page 11: ...alers and or new carpets are being installed make sure all combustion and circulating air requirements are followed If operation of furnace is required during construction use clean outside air for co...

Page 12: ...perated they must be equipped with a means to prevent operation of either unit unless damper is in full heat or full cool position IV HAZARDOUS LOCATIONS NOTE These furnaces are designed for a minimum...

Page 13: ...ischarge duct flanges when they interfere with mating flanges on coil on downflow subbase To remove furnace perforated discharge duct flange use wide duct pliers or duct flange tool to bend flange bac...

Page 14: ...ttom inlet is used VI BOTTOM CLOSURE PANEL These furnaces are shipped with bottom enclosure panel installed in bottom return air opening This panel MUST be in place when side return air is used To rem...

Page 15: ...bustible material 2 The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage A PREFERRED ROD LOCATION B ALTERNATE ROD LOCATION DRAIN 5 3 4 3...

Page 16: ...nection MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve NOTE The gas valve inlet press tap connection is suitable to use as test gage...

Page 17: ...STAT TERMINALS FIELD SUPPLIED FUSED DISCONNECT CONDENSING UNIT R W2 W C R G Y GND GND GND GND FIELD 24 VOLT WIRING FIELD 115 208 230 460 VOLT WIRING FACTORY 24 VOLT WIRING FACTORY 115 208 230 460 VOLT...

Page 18: ...OR PL3 5 CIRCUIT BLOWER MTR CONNECTOR PL4 2 CIRCUIT HSI CONNECTOR PL5 6 CIRCUIT MODEL PLUG PL6 3 CIRCUIT COMM CONNECTOR PL7 12 CIRCUIT INDUCER MTR CONNECTOR PL9 2 CIRCUIT HSI CONNECTOR PL10 9 CIRCUIT...

Page 19: ...stripped end into factory supplied white leads s butt connector and crimp to secure NOTE If desired cut butt connectors off factory leads and strip insulation approximately 1 4 in and use field suppli...

Page 20: ...I COMBUSTION AIR AND VENT PIPING A General Combustion air and vent pipe fittings must conform to American National Standards Institute ANSI standards and American Society for Testing and Materials AST...

Page 21: ...y in well ventilated areas Avoid breathing in vapor or allowing contact with skin or eyes Failure to follow this warning could result in fire property damage personal injury or death TABLE 4 COMBUSTIO...

Page 22: ...20 ft with 3 elbows but only 10 ft with 5 elbows Therefore 2 in diameter pipe must be used for both vent and combustion air pipes since larger required diameter must always be used for both pipes If...

Page 23: ...In Concentric 1 1 2 42 37 32 27 22 17 2 70 70 70 70 70 70 042060 2 Pipe or 2 In Concentric 1 1 2 42 37 32 27 22 17 2 70 70 70 70 70 70 042080 060080 2 Pipe or 2 In Concentric 1 1 2 25 20 15 10 5 NA 2...

Page 24: ...6 65 63 62 60 59 042060 2 Pipe or 2 In Concentric 1 1 2 32 27 22 17 12 7 2 66 65 63 62 60 59 042080 060080 2 Pipe or 2 In Concentric 1 1 2 18 13 8 NA NA NA 2 66 65 63 62 57 52 060100 2 Pipe or 2 In Co...

Page 25: ...Apply second coat 9 While cement is still wet twist pipe into socket with 1 4 turn Be sure pipe is fully inserted into fitting socket 10 Wipe excess cement from joint A continuous bead of cement will...

Page 26: ...AIN 12 IN CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE WHICHEVER IS GREATER 90 VENT 12 IN SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM OF VENT BRACKET COUPLING 12 MINIMUM OVERHANG...

Page 27: ...vent vapors will not damage plants shrubs or air conditioning equip ment c Termination kit should be positioned so it will not be affected by wind eddy such as inside building corners or accumulation...

Page 28: ...m Separation A93056 COMBUSTION AIR VENT VENT A Fig 40 Sidewall Termination of More Than 12 in Dimension A is Touching or 2 In Maximum Separation A85183 VENT A COMBUSTION AIR COMBUSTION AIR Fig 38 Conc...

Page 29: ...pment s drain See Fig 41 for example of possible field drain attachment using 1 2 in CPVC or PVC tee for vent and A C or humidifier drain connection Outdoor draining of the furnace is permissible if a...

Page 30: ...holds gas valve open and begins blower on delay period NOTE Ignition sequence repeats 3 additional times before a lockout occurs Lockout automatically resets after 3 hr or can be manually reset by tu...

Page 31: ...r operates in continuous fan speed and indoor coil freeze up may occur 3 Electronic Air Cleaner The EAC 1 terminal is energized whenever blower operates 4 Cooling unit The cooling unit stops when ther...

Page 32: ...is closed red microprocessor LED briefly comes on Then green LED comes on for 1 sec followed by 1 sec where both green and yellow LEDs are on During this time the microprocessor is checking itself 2...

Page 33: ...ements Position these setup switches for the appropriate requirement 1 Remove main furnace door and blower access panel 2 Locate setup switches on the control center See Fig 25 3 See Table 9 for setup...

Page 34: ...c gravity for local gas supply c Verify the furnace model Table 11 can only be used for model 355MAV Furnaces d Find natural gas heat value and specific gravity in Table 11 e Follow heat value line an...

Page 35: ...furnace locked in low heat operation c Turn low heat adjusting screw 5 64 hex Allen wrench counterclockwise out to decrease input rate or clock wise in to increase rate When adjusting input rate DO N...

Page 36: ...as started and furnace is operating in low heat TABLE 11 MODEL 355MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT RATE Tabulated Data Based on Altitude Up to 2000 ft and 20 000 Btuh High Heat...

Page 37: ...g properly fault code 42 will flash on the control center approximately 10 sec after the thermostat switch is closed If either fault code 31 or 32 is TABLE 12 GAS RATE CU FT HR SECONDS FOR 1 REVOLUTIO...

Page 38: ...ay tools and instruments Clean up debris 2 Verify manual reset switch has continuity 3 Verify that blower and control access doors are properly installed 4 Cycle test furnace with room thermostat 5 Ch...

Page 39: ...e Sloped To Furnace Pipe Insulation ________ Over Ceilings ________ Low Ambient Exposed Pipes Condensate Drain ________ Unit Level or Pitched Forward ________ Internal Tubing Connections Free of Kinks...

Page 40: ...sing popular video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that...

Reviews: