background image

2. Inspect the venting system for proper size and horizontal

pitch as required in the National Fuel Gas Code, ANSI
Z223.1 or the CAN/CGA B149 Installation Codes and these
instructions. Determine that there is no blockage or restric-
tion, leakage, corrosion, and other deficiencies which could
cause an unsafe condition.

3. In so far as is practical, close all building doors and

windows and all doors between the space in which the
appliance(s) connected to the venting system are located
and other spaces of the building. Turn on clothes dryers and
any appliance not connected to the venting system. Turn on
any exhaust fans, such as range hoods and bathroom
exhausts, so they shall operate at maximum speed. Do not
operate a summer exhaust fan. Close fireplace dampers.

4. Follow the lighting instructions. Place the appliance being

inspected in operation. Adjust thermostat so appliance shall
operate continuously.

5. Test for draft hood equipped appliance spillage at the draft

hood relief opening after 5 minutes of main burner opera-
tion. Use the flame of a match or candle.

6. After it has been determined that each appliance connected

to the venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, fireplace damp-
ers, and any other gas-burning appliance to their previous
conditions of use.

7. If improper venting is observed during any of above tests,

the venting system must be corrected.

Vent system or vent connectors may need to be resized. For any
other appliances when resizing vent systems or vent connectors,
system or connector must be sized to approach minimum size as
determined using appropriate table found in the NFGC or NSC-
NGPIC.

II.

COMBUSTION-AIR AND VENT PIPING

A.

General

Combustion-air and vent pipe fittings must conform to American
National Standards Institute (ANSI) standards and American
Society for Testing and Materials (ASTM) standards D1785
(schedule-40 PVC), D2665 (PVC-DWV), D2241 (SDR-21 and
SDR-26 PVC), D2661 (ABS-DWV), F628 (schedule-40 ABS), or
F891 (PVC-DWV cellular core). Pipe cement and primer must
conform to ASTM standards D2564 (PVC) or D2235 (ABS). See
Table 7 for maximum pipe lengths and Fig. 22, 23, 24, 25, and 26
for exterior piping arrangements.

In Canada construct all combustion-air and vent pipes for this unit
of CSA or ULC certified schedule-40 PVC, PVC-DWV or
ABS-DWV pipe and pipe cement. SDR pipe is NOT approved in
Canada.

TABLE 5—ELECTRICAL DATA

UNIT

SIZE

VOLTS—
HERTZ—

PHASE

OPERATING

VOLTAGE RANGE

MAX

UNIT

AMPS

UNIT

AMPACITY†

MIN

WIRE

SIZE

MAX WIRE

LENGTH

(FT)‡

MAX FUSE

OR CKT BKR

AMPS**

Max*

Min*

036080

115—60—1

127

104

7.6

10.4

14

36

15

048080

115—60—1

127

104

10.0

13.4

14

28

15

060080

115—60—1

127

104

14.1

18.4

12

31

20

* Permissible limits of voltage range at which unit will operate satisfactorily.
† Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load

amps.

‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
** Time-delay type is recommended.

Fig. 17—Control Center

A95086

C

OM

24V

HUM

G

R

Y

W

3-AMP FUSE

HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX)

LED OPERATION &
DIAGNOSTIC LIGHT

HARNESS CONNECTOR

24-V TRANSFORMER SEC-2

SPARE-1

SPARE-2

EAC-1

EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1.5 AMP MAX)

EAC-2

115-VAC (L2) NEUTRAL
CONNECTION

24-V THERMOSTAT
TERMINALS

BLOWER SPEED
SELECTION TERMINALS

INDUCER MOTOR
CONNECTOR

115-VAC (L1)

POWER SUPPLY

HOT SURFACE

IGNITOR CONNECTOR

HEAT

COOL

SEC-1

TEST/TWIN

—15—

Summary of Contents for 351DAS

Page 1: ...all repair or service heating equipment Untrained personnel can perform basic maintenance functions such as clean ing and replacing air filters All other operations must be per formed by trained servi...

Page 2: ...9 7 8 11 16 24 3 16 INLET 18 1 4 22 11 16 2 IN COMBUSTION AIR CONN 1 2 IN DIA GAS CONN 7 8 IN DIA POWER CONN 1 2 IN DIA THERMOSTAT ENTRY 2 IN VENT CONN 30 1 2 OUTLET FLANGE AS SHIPPED REMOVE IN FIELD...

Page 3: ...EARANCE TO COMBUSTIBLE CONSTRUCTION Mimimum front clearance for service 30 inches 762mm For installation on combustible floors only when installed on special base No KGASB0201ALL Coil Assembly Part No...

Page 4: ...ome Construction and Safety Standard Title 24 CFR Part 3280 or when such standard is not applicable the ANSI A225 1 Standard for Manufactured Home Installation Manufactured Home Sites Communities and...

Page 5: ...base part number Secure floor base to structure and attach furnace to floor base RECOMMENDED METHODS OF SECURING FOR TYPI CAL INSTALLATION SEE FIG 3 ALL MOUNTING HARDWARE IS FIELD SUPPLIED 1 Secure co...

Page 6: ...Connect collector box upper pressure tube to condensate trap c Clamp tube to prevent any condensate leakage 2 Refer to Condensate Drain section for recommendations and procedures for installing field...

Page 7: ...X TO TRAP RELIEF PORT 5 8 OD COLLECTOR BOX DRAIN CONNECTION 1 2 IN PVC OR CPVC SCREW HOLES FOR DOWNFLOW OPTIONAL 1 4 2 7 8 1 8 7 WIRE TIE GUIDES WHEN USED 1 2 1 3 4 1 3 4 FRONT VIEW SIDE VIEW FURNACE...

Page 8: ...n or ventilation air This furnace must be installed so electrical components are protected from water Locate furnace as close to center of air distribution system as possible Locate furnace so combust...

Page 9: ...manufacturer Part No KGASB0201ALL is used Accessory floor base is not required when this furnace is installed on manufacturer s Coil Assembly Part No CD5 or CK5 or Coil Box Part No KCAKC is used 1 Det...

Page 10: ...Downflow Applications on Combustible Flooring Using KGASB Subbase Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box 18 5 8 19 20 1 4 20 3 8 Downflow Applications on Combustible Floori...

Page 11: ...all gas piping with appropriate straps hangers etc Use a minimum of 1 hanger every 6 ft Joint compound pipe dope should be applied sparingly and only to male threads of joints Pipe dope must be resist...

Page 12: ...wing typical field 115 v and 24 v wiring Check all factory and field electrical connections for tightness WARNING Blower access panel door switch opens 115 v power to control center No component opera...

Page 13: ...th 24v 0 5 amp maximum after inducer motor prepurge period NOTE A field supplied 115 v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operati...

Page 14: ...PL5 2 CIRCUIT HSI PCB CONNECTOR PRS PRESSURE SWITCH SPST N O SW1 2 BLOWER OFF DELAY TEST TWIN COMPONENT TEST TWIN TERMINAL TRAN TRANSFORMER 115VAC 24VAC JUNCTION UNMARKED TERMINAL PCB TERMINAL FACTOR...

Page 15: ...C NGPIC II COMBUSTION AIR AND VENT PIPING A General Combustion air and vent pipe fittings must conform to American National Standards Institute ANSI standards and American Society for Testing and Mate...

Page 16: ...d watertight Pipes must also terminate exactly as shown in Fig 22 23 24 25 or 26 Failure to follow this warning could result in property damage personal injury or death NOTE The minimum combustion air...

Page 17: ...ric 2 38 33 21 16 15 6 2 1 2 70 70 68 67 66 64 7001 to 8000 036080 048080 060080 2 Pipe or 2 In Concentric 2 36 31 19 14 12 NA 2 1 2 66 65 63 62 60 59 8001 to 9000 036080 048080 060080 2 Pipe or 2 In...

Page 18: ...ould be routed to open condensate drain for furnace and A C if used and should be trapped See Fig 21 c Insert perforated disk assembly factory supplied in loose parts bag in intake housing where combu...

Page 19: ...nations may be extended beyond area shown in Fig 25 or 26 in outside ambient by insulating pipes as indicated in Table 8 1 Determine combustion air and vent pipe diameters as stated above using total...

Page 20: ...ION AIR COUPLING ROOF VENT BRACKET VERTICAL SEPARATION BETWEEN COMBUSTION AIR AND VENT 8 3 4 FOR 3 KIT 6 3 4 FOR 2 KIT MAINTAIN 12 IN MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL MAXIMUM OF...

Page 21: ...heat tape between sides of condensate trap back See Fig 28 3 Use wire ties to secure heat tape in place Wire ties can be positioned in notches of condensate trap sides See Fig 28 4 Wrap field drain p...

Page 22: ...ower speed heating speed to cooling speed When thermostat cooling call is satisfied R Y opens and blower operates an additional 90 sec at cooling speed before reverting back to continuous operation he...

Page 23: ...ve NOTE Be sure to record the status code which is flashed 4 times at start of component test for further troubleshooting 6 After component test is completed and furnace is operating properly release...

Page 24: ...Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure U S A and Canada U S A 775 43 3 8 42 3 2 42 3 3 42 3 4 42 3 5 Altitudes 800 43 3 5 43 3 7 43 3 8 42 3 2 42 3 3 2...

Page 25: ...No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure U S A Only 700 43 3 6 43 3 7 42 3 2 42 3 3 42 3 4 725 43 3 4 43 3 5 43 3 6 43 3 7 43 3 8 750 44 3 6 44 3 7 43 3 4 43 3 5...

Page 26: ...L GAS 0 58 0 60 0 62 0 64 0 66 Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure U S A Only 600 43 3 8 42...

Page 27: ...ualifi e est responsable d installer correctement cette fournaise confor ment ces instructions L installation n est ni correcte ni compl te tant que le fonctionnement de l appareil converti n a pas t...

Page 28: ...horized factory parts distributor j Remove natural gas orifices from manifold and place them in the bag supplied marked Natural Gas Orifices Manufactured mobile home installations are required to have...

Page 29: ...nclosure front and verify adjusted gas input rate using method outlined in item 5 f Look through sight glass in burner enclosure and check burner flame Burner flame should be clear blue almost transpa...

Page 30: ...ill an orifice A burr free and squarely aligned orifice hole is essential for proper flame characteristics 3 Change orifice if required or proceed to Item 4 a Turn off gas and electrical supplies to f...

Page 31: ...operate furnace more than 1 minute to check inlet gas pressure as conversion is not complete at this time g Jumper R and W thermostat connections to call for heat h When main burners have ignited conf...

Page 32: ...ay result in condensing or overheating the heat ex changers Determine and adjust air temperature rise as follows 1 Place thermometers in return and supply ducts as close to furnace as possible Be sure...

Page 33: ...r to furnace 6 Reconnect inducer motor leads reinstall main furnace door and turn on 115 v power supply CHECKLIST 1 Put away tools and instruments Clean up debris 2 Verify manual reset switch has cont...

Page 34: ...Sloped To Furnace Pipe Insulation ________ Over Ceilings ________ Low Ambient Exposed Pipes Condensate Drain ________ Unit Level or Pitched Forward ________ Internal Tubing Connections Free of Kinks...

Page 35: ...35...

Page 36: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays d...

Reviews: