background image

24

115-VOLT FIELD-

SUPPLIED

FUSED

DISCONNECT   

JUNCTION

BOX   

CONTROL

BOX

24-VOLT

TERMINAL

BLOCK  

THREE-WIRE

HEATING-

ONLY   

FIVE

WIRE

   

NOTE 2

NOTE 1

1-STAGE

THERMOSTAT

TERMINALS

   

FIELD-SUPPLIED

FUSED DISCONNECT

CONDENSING

UNIT   

FURNACE

COM

R

W

C

Y

R

G

GND   

GND   

FIELD 24-VOLT WIRING

FIELD 115-, 208/230-, 460-VOLT WIRING

FACTORY 24-VOLT WIRING

FACTORY 115-VOLT WIRING   

Connect Y/Y2-terminal as shown for proper operation.

Some thermostats require a "C" terminal connection as shown.

If any of the original wire, as supplied, must be replaced, use

same type or equivalent wire.

208/230- OR

460-VOLT

THREE

PHASE   

208/230-

VOLT

SINGLE

PHASE   

WHT   

BLK   

WHT   

BLK   

W/W1

W2

Y/Y2

G

NOTES:

1.

2.

3.

A95236

Fig. 25 -- Field Wiring Diagram

 

24-V THERMOSTAT 

TERMINALS 

PL2 

 HOT SURFACE 

IGNITER & INDUCER 

MOTOR CONNECTOR 

115-VAC (L2) NEUTRAL 

CONNECTIONS  

115-VAC (L1) LINE 

VOLTAGE  CONNECTIONS  

EAC-1 TERMINAL 

 (115-VAC 1.0 AMP MAX.)  

PL1 

 LOW VOLTAGE MAIN 

HARNESS CONNECTOR 

AND ECM BLOWER 

HARNESS CONNECTOR 

TRANSFORMER 24-VAC 

CONNECTIONS  

3-AMP FUSE  

STATUS AND COMM 

LED LIGHTS  

SW1 SETUP 

SWITCHES AND 

BLOWER OFF-

DELAY 

MODEL PLUG 

CONNECTOR 

AIR CONDITIONING 

(A/C) AIRFLOW 

SETUP SWITCHES 

COMMUNICATION 

CONNECTOR 

CONTINUOUS FAN 

(CF) AIRFLOW 

SETUP SWITCHES 

OUTDOOR 

AIR TEMP 

CONNECTOR 

HUMIDIFIER 

TERMINAL (24-VAC 

0.5 AMP MAX. 

FLASH 

UPGRADE 

CONNECTOR 

(FACTORY 

ONLY) 

SW4 SETUP 

SWITCHES 

SOFTWARE 

VERSION  

PART NUMBER AND 

DATE CODE WWYY  

ACRDJ 

 AIR 

CONDITIONING 

RELAY DISABLE 

JUMPER 

A11618

Fig. 26 -- Variable Speed Furnace Control for ECM Blower Motor

314AA

V

Summary of Contents for 314A

Page 1: ...tment 13 Supply Air Connections 14 Upflow and Horizontal Furnaces 14 Downflow Furnaces 14 Return Air Connections 20 Downflow Furnaces 20 Upflow and Horizontal Furnaces 20 GAS PIPING 20 ELECTRICAL CONN...

Page 2: ...jury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation 1 Use only with type of gas approved for this furnace Refe...

Page 3: ...3 A10269 Fig 1 Clearances to Combustibles 314AAV...

Page 4: ...on DC 20001 www AGA org Combustion and Ventilation Air Section 9 3 NFPA 54 ANSI Z223 1 2012 Air for Combustion and Ventilation Duct Systems Air Conditioning Contractors Association ACCA Manual D Sheet...

Page 5: ...20 in 508 mm round or 14 1 2 x 19 1 2 in 368 x 495 mm rectangle c For 1600 CFM 22 in 559 mm round or 14 1 2 x 22 1 16 in 368 x 560mm rectangle d For airflow requirements above 1800 CFM see Air Deliver...

Page 6: ...all combustion and circulating air requirements are met in addition to all local codes and ordinances WARNING The following types of furnace installations may require OUTDOOR AIR for combustion due t...

Page 7: ...aining the furnace This prevents a negative pressure condition as created by the circulating air blower causing a flame rollout and or drawing combustion products into the structure The furnace is con...

Page 8: ...2 200 62 2 3 300 93 4 4 400 124 5 5 500 155 7 6 600 186 8 7 700 218 0 0 20 3 150 89 1 4 200 118 9 5 250 148 6 3 300 93 4 4 950 140 1 6 600 186 8 8 250 233 6 9 900 280 3 11 550 327 0 0 10 6 300 178 3...

Page 9: ...combined input of all gas appli ances in the space per Table 1 and b Not less than the sum of the areas of all vent connect ors in the space CIRCULATING AIR DUCTS 6 MIN FRONT CIRCULATING AIR DUCTS VEN...

Page 10: ...nt ventilation and dilution of flue gases However in buildings with unusually tight construction additional air MUST be provided using the methods de scribed in the Outdoor Combustion Air Method secti...

Page 11: ...d this panel when bottom return air is used To remove bottom closure panel perform the following 1 Tilt or raise furnace and remove 2 screws holding bottom filler panel See Fig 9 2 Rotate bottom fille...

Page 12: ...and discard this panel when bottom return air is used To remove bottom closure panel perform the following 1 Tilt or raise furnace and remove two screws holding bot tom filler panel See Fig 9 2 Rotat...

Page 13: ...Filter Arrangement CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death Never operate a furnace without a filter or with filter access door removed...

Page 14: ...All accessories MUST be connected to duct external to furnace main casing NOTE For horizontal applications the top most flange may be bent past 90_ to allow the evaporator coil to hang on the flange t...

Page 15: ...ROD 8 203mm MIN FOR DOOR REMOVAL OUTER DOOR ASSEMBLY A10130 Fig 15 Horizontal Unit Suspension METHOD 2 USE 4 8 x 3 4 19 mm SHEET METAL SCREWS FOR EACH STRAP THE STRAPS SHOULD BE VERTICAL AGAINST THE...

Page 16: ...IONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS STUDS OR FRAMING GAS ENTRY 17 3 4 451mm OVERALL 4 3 4 121mm UNDER DOOR 1 25mm UNDER FURNACE EXTEND OUT 12 305mm FROM FACE OF DOO...

Page 17: ...17 A02163 Fig 19 Downflow Return Air Configurations and Restrictions A02162 Fig 20 Horizontal Return Air Configurations and Restrictions 314AAV...

Page 18: ...25 1280 1210 OFF OFF ON 640 See note 4 OFF ON OFF 840 775 700 640 See note 4 OFF ON ON 1045 980 920 860 805 750 690 640 See note 4 ON OFF OFF 1220 1175 1120 1075 1025 970 925 875 820 775 ON OFF ON 139...

Page 19: ...1180 1085 1015 935 880 805 ON OFF ON 1670 1605 1540 1480 1425 1350 1280 1220 1135 1070 ON ON OFF 2040 1985 1930 1880 1830 1775 1715 1660 1595 1510 ON ON ON 2520 2455 2405 2350 2290 2195 2090 1965 181...

Page 20: ...ximum length shall not exceed 36 in 915 mm 3 When lever handle type manual equipment shutoff valves are used they shall be T handle valves 4 The use of copper tubing for gas piping is NOT approved by...

Page 21: ...oor switch opens 115 v power to control No component operation can occur Do not bypass or close switch with panel removed WARNING See Fig 25 for field wiring diagram showing typical field 115 v wiring...

Page 22: ...Do NOT remove green ground screw inside J Box See Fig 23 2 Cut wire tie on loop in furnace wires attached to J Box 3 Move J Box to desired location 4 Fasten J Box to casing with the two screws removed...

Page 23: ...ation service or maintenance could cause this fuse to blow If fuse replacement is required use ONLY a 3 amp fuse of identical size ACCESSORIES 1 Electronic Air Cleaner EAC Connect an accessory Electro...

Page 24: ...W2 Y Y2 G NOTES 1 2 3 A95236 Fig 25 Field Wiring Diagram 24 V THERMOSTAT TERMINALS PL2 HOT SURFACE IGNITER INDUCER MOTOR CONNECTOR 115 VAC L2 NEUTRAL CONNECTIONS 115 VAC L1 LINE VOLTAGE CONNECTIONS EA...

Page 25: ...system or vent connectors may need to be resized Vent systems or vent connectors must be sized to approach minimum size as determined using appropriate table found in the current edition of NFGC Gene...

Page 26: ...these figures A03180 Fig 29 Two Stage Furnace with Single Speed Heat Pump Dual Fuel See notes 1 2 3 4 6 8 9 10 12 13 and 15 on the page following these figures A03178 Fig 30 Two Stage Furnace with Tw...

Page 27: ...urnace and Two Speed Heat Pump See notes 2 11 and 12 on the page following these figures A03183 Fig 33 Two Stage Thermostat with Two Stage Furnace and Two Speed Air Conditioner See notes 1 and 2 on th...

Page 28: ...iguration Option No 10 Dual Fuel Selection must be turned ON in all dual fuel applications 10 NO connection should be made to the furnace HUM terminal when using a Thermidistat 11 Optional connection...

Page 29: ...nt fuel oil residue Is liner and top seal in good condition Is chimney property lined with clay tile liner Crown condition Missing mortar or brick Rebuild crown Yes Yes No No No Reline Yes Repair Yes...

Page 30: ...al information on condensate drains b Indicates the chimney exceeds the maximum permiss ible size in the tables the chimney should be rebuilt or relined to conform to the requirements of the equip men...

Page 31: ...ces A field supplied 4 in 102 mm to 5 in 127 mm or 4 in 102 mm to 6 in 152 mm sheet metal increaser fitting is required when 5 in 127 mm or 6 in 152 mm vent connector is used See Fig 36 48 Venting Ori...

Page 32: ...8 9 on the pages following these figures A03209 Fig 37 Upflow Application Vent Elbow Right SEE NOTES 1 2 3 4 5 7 8 9 on the page following these figures A03210 Fig 38 Downflow Application Vent Elbow U...

Page 33: ...low Application Vent Elbow Up then Right SEE NOTES 1 2 4 7 8 9 on the page following these figures A03213 Fig 42 Horizontal Left Application Vent Elbow Left SEE NOTES 1 2 4 5 7 8 9 on the page followi...

Page 34: ...actory approved Downflow Vent Guard Kit is used in the downflow position See Product Data Sheet for accessory listing 4 Type B vent where required refer to Note 1 above 5 A 4 in 102 mm single wall 26...

Page 35: ...SAFETY CHECK General FIRE HAZARD Failure to follow this warning could result in personal injury death or property damage This furnace is equipped with manual reset limit switches in the gas control ar...

Page 36: ...Test Remove Blower Access Door Disconnect the thermostat R lead from furnace control board Manually close blower door switch Turn Setup DIP switch SW1 6 ON See Fig 26 55 and Table 52 NOTE The furnace...

Page 37: ...per ton Adjust OFF Allows additional CFM per ton selections when used with SW 1 5 325 CFM per ton nominal when SW 4 3 ON and SW 1 5 OFF 350 CFM per ton nominal when SW 4 3 OFF and SW 1 5 OFF 370 CFM p...

Page 38: ...rrect input rate 2 Determine the correct orifice and manifold pressure adjust ment All models in all positions use Table 12 22 000 Btuh per burner See input listed on rating plate a Obtain average yea...

Page 39: ...meter b Move setup switch SW1 2 to ON position This keeps furnace locked in low heat operation c Jumper R to W W1 d Run furnace for 3 minutes in low heat operation e Measure time in sec for gas meter...

Page 40: ...W W1 circuit Accurate amp draw readings can be obtained at the wires normally connected to ther mostat subbase terminals R and W The thermostat anticipator should NOT be in the circuit while measur in...

Page 41: ...41 A13214 Fig 55 Wiring Diagram 314AAV...

Page 42: ...23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231...

Page 43: ...4 43 3 4 1 5 43 3 5 1 5 43 3 6 1 6 925 44 3 5 1 5 43 3 2 1 4 43 3 3 1 4 43 3 4 1 5 950 44 3 4 1 5 44 3 5 1 5 44 3 6 1 6 43 3 2 1 4 975 44 3 2 1 4 44 3 3 1 4 44 3 4 1 5 44 3 5 1 5 1000 45 3 7 1 6 45 3...

Page 44: ...0 47 3 5 1 5 47 3 6 1 6 47 3 8 1 6 46 3 4 1 5 ALTITUDE RANGE FT M AVG GAS HEAT VALUE AT ALTITUDE BTUH CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 58 0 60 0 62 0 64 Orifice No Manifold Pressure High Low Or...

Page 45: ...surface igniter glows when inducer motor is disconnected shut down furnace immediately e Determine reason pressure switch did not function properly and correct condition f Turn off 115 v power to furn...

Page 46: ...urrence 1 To retrieve status codes proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 v power to furnace turned on b...

Page 47: ...vice as neces sary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust If necessary have furnace and burner serviced by a qualified service agency 5 Inspe...

Page 48: ...and set screw contacts the flat portion of the motor shaft Loosen set screw on blower wheel and reposition if neces sary 12 Spin the blower wheel by hand to verify that the wheel does not rub on the h...

Page 49: ...nd of spring cable and crimp tight with crimping tool or crimp by striking with ball peen hammer TIGHTNESS IS VERY IMPORTANT NOTE The materials needed in item 9 can usually be purchased at local hardw...

Page 50: ...s based upon the stored history of the length of previous gas heating periods of the single stage thermostat The furnace will start up in either low or high heat If the furnace starts up in low heat t...

Page 51: ...furnace control CPU will switch the inducer motor IDM speed from low to high The high heat pressure switch relay HPSR is de energized to close the NC contact When sufficient pressure is available the...

Page 52: ...ll drop the blower airflow to 90 percent of low cooling airflow which is the true on board CF continuous fan selection as shown in Fig 53 b High cooling When the R to G and Y Y2 circuit is closed and...

Page 53: ...stem problem in the case of a component fail ure To initiate the component test procedure ensure that there are no thermostat inputs to the control and all time delays have expired Turn on setup switc...

Page 54: ...ransformer phasing Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch Replace transformer Does the control respond to W W1 W2 Y1 Y Y...

Page 55: ...at the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items...

Page 56: ...PL4 is missing and there is no valid model stored in permanent memory This will happen if you forget to install the model plug PL4 on a service replacement control Thermostat call with SW1 1 ON Therm...

Page 57: ...ATION ON PARTS Consult your installing dealer or classified section of your local telephone directory under Heating Equipment or Air Conditioning Contractors and Systems headings for dealer listing by...

Page 58: ...tinue or change at any time specifications or designs without notice and without incurring obligations EBryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Edition Date 09 13 Replace...

Reviews: