52

which is the true on--board CF selection as shown in Fig. 53.
If the furnace control CPU switches from low--cooling to
high--cooling, the furnace control CPU will energize the air
conditioning relay ACR. When the air conditioning relay ACR is
energized the R--to--Y1--and--Y2 circuits switch the outdoor unit
to high--cooling speed, and the R--to--G--and--Y1--and--Y/Y2
circuits transition the furnace blower motor BLWM to
high--cooling airflow. High--cooling airflow is based on the A/C
selection shown in Fig. 53.

NOTE

: When transitioning from low--cooling to high--cooling

the outdoor unit compressor will shut down for 1 minute while
the furnace blower motor BLWM transitions to run at
high--cooling airflow.
The electronic air cleaner terminal EAC--1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R--to--G--and--Y circuit are
opened. The outdoor unit stops, and the furnace blower BLWM
and electronic air cleaner terminal EAC--1 will remain energized
for an additional 90 seconds. Jumper Y1 to DHUM to reduce the
cooling off--delay to 5 seconds. (See Fig. 26.)

c. Two--Stage Thermostat and Two--Speed Cooling

See Fig. 33 for thermostat connections

NOTE

: The air conditioning relay disable jumper ACRDJ must

be disconnected to allow thermostat control of the outdoor unit
staging. (See Fig. 26.)
The thermostat closes the R--to--G--and--Y1 circuits for

low--cooling or closes the R--to--G--and--Y1--and--Y2 circuits for
high--cooling. The R--to--Y1 circuit starts the outdoor unit on

low--cooling speed, and the R--to--G--and--Y1 circuit starts the

furnace blower motor BLWM at low--cooling airflow which is the
true on--board CF (continuous fan) selection as shown in Fig. 57.

The R--to--Y1--and--Y2 circuits start the outdoor unit on
high--cooling speed, and the R--to-- G--and--Y/Y2 circuits start the

furnace blower motor BLWM at high--cooling airflow.

High--cooling airflow is based on the A/C (air conditioning)
selection shown in Fig. 53.

The electronic air cleaner terminal EAC--1 is energized with 115
vac whenever the blower motor BLWM is operating.

When the thermostat is satisfied, the R--to--G--and--Y1 or R--to--

G--and--Y1--and--Y2 circuits are opened. The outdoor unit stops,
and the furnace blower BLWM and electronic air cleaner terminal

EAC--1 will remain energized for an additional 90 seconds.
Jumper Y1 to DHUM to reduce the cooling off--delay to 5

seconds. (See Fig. 26.)

4.

Thermidistat Mode

See Fig. 27--29 for thermostat connections.
The dehumidification output, DHUM on the Thermidistat

should be connected to the furnace control thermostat ter-
minal DHUM. When there is a dehumidify demand, the

DHUM input is activated, which means 24 vac signal is
removed from the DHUM input terminal. In other words,
the DHUM input logic is reversed. The DHUM input is

turned ON when no dehumidify demand exists. Once 24
vac is detected by the furnace control on the DHUM input,

the furnace control operates in Thermidistat mode. If the
DHUM input is low for more than 48 hours, the furnace
control reverts back to non--Thermidistat mode.

The cooling operation described in item 3. above also ap-
plies to operation with a Thermidistat. The exceptions are

listed below:

a.

Low cooling

--When the R--to--G--and--Y1 circuit is

closed and there is a demand for dehumidification, the

furnace blower motor BLWM will drop the blower
airflow to 90 percent of low--cooling airflow which is

the true on--board CF (continuous fan) selection as
shown in Fig. 53.

b.

High cooling

--When the R--to--G--and Y/Y2 circuit is

closed and there is a demand for dehumidification, the

furnace blower motor BLWM will drop the blower
airflow to 90 percent of high--cooling airflow. High--
cooling airflow is based on the A/C (air conditioning)

selection shown in Fig. 53.

c.

Cooling off--delay

--When the “call for cooling” is

satisfied and there is a demand for dehumidification,
the cooling blower--off delay is decreased from 90
seconds to 5 seconds.

5.

Continuous Blower Mode

When the R--to--G circuit is closed by the thermostat, the

blower motor BLWM will operate at continuous blower
airflow. Continuous blower airflow selection is initially
based on the CF (continuous fan) selection shown in Fig.

53. Factory default is shown in Fig. 53. Terminal EAC--1
is energized as long as the blower motor BLWM is ener-

gized.
During a call for heat, the furnace control CPU will trans-

ition the blower motor BLWM to continuous blower air-
flow, low--heat airflow, or the mid--range airflow,
whichever is lowest. The blower motor BLWM will re-

main ON until the main burners ignite then shut OFF and
remain OFF for the blower--ON delay (45 seconds in low--

heat, and 25 seconds in high--heat), allowing the furnace
heat exchangers to heat up more quickly, then restarts at
the end of the blower--ON delay period at low--heat or

high--heat airflow, respectively.
The blower motor BLWM will revert to continuous--

blower airflow after the heating cycle is completed. In
high--heat, the furnace control CPU will drop the blower

motor BLWM to low--heat airflow during the selected
blower--OFF delay period before transitioning to continu-
ous--blower airflow.

When the thermostat “calls for low--cooling”, the blower
motor BLWM will switch to operate at low--cooling air-

flow. When the thermostat is satisfied, the blower motor
BLWM will operate an additional 90 seconds at low--cool-
ing airflow before transitioning back to continuous--

blower airflow.
When the thermostat “calls for high--cooling”, the blower

motor BLWM will operate at high cooling airflow. When
the thermostat is satisfied, the blower motor BLWM will
operate an additional 90 seconds at high--cooling airflow

before transitioning back to continuous--blower airflow.
When the R--to--G circuit is opened, the blower motor

BLWM will continue operating for an additional 5
seconds, if no other function requires blower motor

BLWM operation.

Continuous Blower Speed Selection from Thermostat

To select different continuous--blower airflow from the

room thermostat, momentarily turn off the FAN switch or
push button on the room thermostat for 1--3 seconds after

the blower motor BLWM is operating. The furnace control
CPU will shift the continuous--blower airflow from the
factory setting to the next highest CF selection airflow as

shown in Fig. 53. Momentarily turning off the FAN switch
again at the thermostat will shift the continuous--blower

airflow up one more increment. If you repeat this proced-
ure enough you will eventually shift the continuous--
blower airflow to the lowest CF selection as shown in Fig.

53. The selection can be changed as many times as desired
and is stored in the memory to be automatically used fol-

lowing a power interruption.

NOTE

: If the blower--off delay is set to the maximum, the

adjustable continuous--fan feature is locked (i.e., fan speed cannot
be changed from its current setting).

314AA

V

Summary of Contents for 314A

Page 1: ...tment 13 Supply Air Connections 14 Upflow and Horizontal Furnaces 14 Downflow Furnaces 14 Return Air Connections 20 Downflow Furnaces 20 Upflow and Horizontal Furnaces 20 GAS PIPING 20 ELECTRICAL CONN...

Page 2: ...jury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation 1 Use only with type of gas approved for this furnace Refe...

Page 3: ...3 A10269 Fig 1 Clearances to Combustibles 314AAV...

Page 4: ...on DC 20001 www AGA org Combustion and Ventilation Air Section 9 3 NFPA 54 ANSI Z223 1 2012 Air for Combustion and Ventilation Duct Systems Air Conditioning Contractors Association ACCA Manual D Sheet...

Page 5: ...20 in 508 mm round or 14 1 2 x 19 1 2 in 368 x 495 mm rectangle c For 1600 CFM 22 in 559 mm round or 14 1 2 x 22 1 16 in 368 x 560mm rectangle d For airflow requirements above 1800 CFM see Air Deliver...

Page 6: ...all combustion and circulating air requirements are met in addition to all local codes and ordinances WARNING The following types of furnace installations may require OUTDOOR AIR for combustion due t...

Page 7: ...aining the furnace This prevents a negative pressure condition as created by the circulating air blower causing a flame rollout and or drawing combustion products into the structure The furnace is con...

Page 8: ...2 200 62 2 3 300 93 4 4 400 124 5 5 500 155 7 6 600 186 8 7 700 218 0 0 20 3 150 89 1 4 200 118 9 5 250 148 6 3 300 93 4 4 950 140 1 6 600 186 8 8 250 233 6 9 900 280 3 11 550 327 0 0 10 6 300 178 3...

Page 9: ...combined input of all gas appli ances in the space per Table 1 and b Not less than the sum of the areas of all vent connect ors in the space CIRCULATING AIR DUCTS 6 MIN FRONT CIRCULATING AIR DUCTS VEN...

Page 10: ...nt ventilation and dilution of flue gases However in buildings with unusually tight construction additional air MUST be provided using the methods de scribed in the Outdoor Combustion Air Method secti...

Page 11: ...d this panel when bottom return air is used To remove bottom closure panel perform the following 1 Tilt or raise furnace and remove 2 screws holding bottom filler panel See Fig 9 2 Rotate bottom fille...

Page 12: ...and discard this panel when bottom return air is used To remove bottom closure panel perform the following 1 Tilt or raise furnace and remove two screws holding bot tom filler panel See Fig 9 2 Rotat...

Page 13: ...Filter Arrangement CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death Never operate a furnace without a filter or with filter access door removed...

Page 14: ...All accessories MUST be connected to duct external to furnace main casing NOTE For horizontal applications the top most flange may be bent past 90_ to allow the evaporator coil to hang on the flange t...

Page 15: ...ROD 8 203mm MIN FOR DOOR REMOVAL OUTER DOOR ASSEMBLY A10130 Fig 15 Horizontal Unit Suspension METHOD 2 USE 4 8 x 3 4 19 mm SHEET METAL SCREWS FOR EACH STRAP THE STRAPS SHOULD BE VERTICAL AGAINST THE...

Page 16: ...IONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS STUDS OR FRAMING GAS ENTRY 17 3 4 451mm OVERALL 4 3 4 121mm UNDER DOOR 1 25mm UNDER FURNACE EXTEND OUT 12 305mm FROM FACE OF DOO...

Page 17: ...17 A02163 Fig 19 Downflow Return Air Configurations and Restrictions A02162 Fig 20 Horizontal Return Air Configurations and Restrictions 314AAV...

Page 18: ...25 1280 1210 OFF OFF ON 640 See note 4 OFF ON OFF 840 775 700 640 See note 4 OFF ON ON 1045 980 920 860 805 750 690 640 See note 4 ON OFF OFF 1220 1175 1120 1075 1025 970 925 875 820 775 ON OFF ON 139...

Page 19: ...1180 1085 1015 935 880 805 ON OFF ON 1670 1605 1540 1480 1425 1350 1280 1220 1135 1070 ON ON OFF 2040 1985 1930 1880 1830 1775 1715 1660 1595 1510 ON ON ON 2520 2455 2405 2350 2290 2195 2090 1965 181...

Page 20: ...ximum length shall not exceed 36 in 915 mm 3 When lever handle type manual equipment shutoff valves are used they shall be T handle valves 4 The use of copper tubing for gas piping is NOT approved by...

Page 21: ...oor switch opens 115 v power to control No component operation can occur Do not bypass or close switch with panel removed WARNING See Fig 25 for field wiring diagram showing typical field 115 v wiring...

Page 22: ...Do NOT remove green ground screw inside J Box See Fig 23 2 Cut wire tie on loop in furnace wires attached to J Box 3 Move J Box to desired location 4 Fasten J Box to casing with the two screws removed...

Page 23: ...ation service or maintenance could cause this fuse to blow If fuse replacement is required use ONLY a 3 amp fuse of identical size ACCESSORIES 1 Electronic Air Cleaner EAC Connect an accessory Electro...

Page 24: ...W2 Y Y2 G NOTES 1 2 3 A95236 Fig 25 Field Wiring Diagram 24 V THERMOSTAT TERMINALS PL2 HOT SURFACE IGNITER INDUCER MOTOR CONNECTOR 115 VAC L2 NEUTRAL CONNECTIONS 115 VAC L1 LINE VOLTAGE CONNECTIONS EA...

Page 25: ...system or vent connectors may need to be resized Vent systems or vent connectors must be sized to approach minimum size as determined using appropriate table found in the current edition of NFGC Gene...

Page 26: ...these figures A03180 Fig 29 Two Stage Furnace with Single Speed Heat Pump Dual Fuel See notes 1 2 3 4 6 8 9 10 12 13 and 15 on the page following these figures A03178 Fig 30 Two Stage Furnace with Tw...

Page 27: ...urnace and Two Speed Heat Pump See notes 2 11 and 12 on the page following these figures A03183 Fig 33 Two Stage Thermostat with Two Stage Furnace and Two Speed Air Conditioner See notes 1 and 2 on th...

Page 28: ...iguration Option No 10 Dual Fuel Selection must be turned ON in all dual fuel applications 10 NO connection should be made to the furnace HUM terminal when using a Thermidistat 11 Optional connection...

Page 29: ...nt fuel oil residue Is liner and top seal in good condition Is chimney property lined with clay tile liner Crown condition Missing mortar or brick Rebuild crown Yes Yes No No No Reline Yes Repair Yes...

Page 30: ...al information on condensate drains b Indicates the chimney exceeds the maximum permiss ible size in the tables the chimney should be rebuilt or relined to conform to the requirements of the equip men...

Page 31: ...ces A field supplied 4 in 102 mm to 5 in 127 mm or 4 in 102 mm to 6 in 152 mm sheet metal increaser fitting is required when 5 in 127 mm or 6 in 152 mm vent connector is used See Fig 36 48 Venting Ori...

Page 32: ...8 9 on the pages following these figures A03209 Fig 37 Upflow Application Vent Elbow Right SEE NOTES 1 2 3 4 5 7 8 9 on the page following these figures A03210 Fig 38 Downflow Application Vent Elbow U...

Page 33: ...low Application Vent Elbow Up then Right SEE NOTES 1 2 4 7 8 9 on the page following these figures A03213 Fig 42 Horizontal Left Application Vent Elbow Left SEE NOTES 1 2 4 5 7 8 9 on the page followi...

Page 34: ...actory approved Downflow Vent Guard Kit is used in the downflow position See Product Data Sheet for accessory listing 4 Type B vent where required refer to Note 1 above 5 A 4 in 102 mm single wall 26...

Page 35: ...SAFETY CHECK General FIRE HAZARD Failure to follow this warning could result in personal injury death or property damage This furnace is equipped with manual reset limit switches in the gas control ar...

Page 36: ...Test Remove Blower Access Door Disconnect the thermostat R lead from furnace control board Manually close blower door switch Turn Setup DIP switch SW1 6 ON See Fig 26 55 and Table 52 NOTE The furnace...

Page 37: ...per ton Adjust OFF Allows additional CFM per ton selections when used with SW 1 5 325 CFM per ton nominal when SW 4 3 ON and SW 1 5 OFF 350 CFM per ton nominal when SW 4 3 OFF and SW 1 5 OFF 370 CFM p...

Page 38: ...rrect input rate 2 Determine the correct orifice and manifold pressure adjust ment All models in all positions use Table 12 22 000 Btuh per burner See input listed on rating plate a Obtain average yea...

Page 39: ...meter b Move setup switch SW1 2 to ON position This keeps furnace locked in low heat operation c Jumper R to W W1 d Run furnace for 3 minutes in low heat operation e Measure time in sec for gas meter...

Page 40: ...W W1 circuit Accurate amp draw readings can be obtained at the wires normally connected to ther mostat subbase terminals R and W The thermostat anticipator should NOT be in the circuit while measur in...

Page 41: ...41 A13214 Fig 55 Wiring Diagram 314AAV...

Page 42: ...23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231...

Page 43: ...4 43 3 4 1 5 43 3 5 1 5 43 3 6 1 6 925 44 3 5 1 5 43 3 2 1 4 43 3 3 1 4 43 3 4 1 5 950 44 3 4 1 5 44 3 5 1 5 44 3 6 1 6 43 3 2 1 4 975 44 3 2 1 4 44 3 3 1 4 44 3 4 1 5 44 3 5 1 5 1000 45 3 7 1 6 45 3...

Page 44: ...0 47 3 5 1 5 47 3 6 1 6 47 3 8 1 6 46 3 4 1 5 ALTITUDE RANGE FT M AVG GAS HEAT VALUE AT ALTITUDE BTUH CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 58 0 60 0 62 0 64 Orifice No Manifold Pressure High Low Or...

Page 45: ...surface igniter glows when inducer motor is disconnected shut down furnace immediately e Determine reason pressure switch did not function properly and correct condition f Turn off 115 v power to furn...

Page 46: ...urrence 1 To retrieve status codes proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 v power to furnace turned on b...

Page 47: ...vice as neces sary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust If necessary have furnace and burner serviced by a qualified service agency 5 Inspe...

Page 48: ...and set screw contacts the flat portion of the motor shaft Loosen set screw on blower wheel and reposition if neces sary 12 Spin the blower wheel by hand to verify that the wheel does not rub on the h...

Page 49: ...nd of spring cable and crimp tight with crimping tool or crimp by striking with ball peen hammer TIGHTNESS IS VERY IMPORTANT NOTE The materials needed in item 9 can usually be purchased at local hardw...

Page 50: ...s based upon the stored history of the length of previous gas heating periods of the single stage thermostat The furnace will start up in either low or high heat If the furnace starts up in low heat t...

Page 51: ...furnace control CPU will switch the inducer motor IDM speed from low to high The high heat pressure switch relay HPSR is de energized to close the NC contact When sufficient pressure is available the...

Page 52: ...ll drop the blower airflow to 90 percent of low cooling airflow which is the true on board CF continuous fan selection as shown in Fig 53 b High cooling When the R to G and Y Y2 circuit is closed and...

Page 53: ...stem problem in the case of a component fail ure To initiate the component test procedure ensure that there are no thermostat inputs to the control and all time delays have expired Turn on setup switc...

Page 54: ...ransformer phasing Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch Replace transformer Does the control respond to W W1 W2 Y1 Y Y...

Page 55: ...at the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items...

Page 56: ...PL4 is missing and there is no valid model stored in permanent memory This will happen if you forget to install the model plug PL4 on a service replacement control Thermostat call with SW1 1 ON Therm...

Page 57: ...ATION ON PARTS Consult your installing dealer or classified section of your local telephone directory under Heating Equipment or Air Conditioning Contractors and Systems headings for dealer listing by...