background image

5

Final Tubing Check

IMPORTANT

: Check to be certain factory tubing on both indoor

and outdoor unit has not shifted during shipment. Ensure tubes
are not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes
are secure and tight.

Make Electrical Connections

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Do not supply power to unit with compressor terminal box

cover removed.

Be sure field wiring complies with local and national fire, safety,

and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction

of improper voltage. See unit rating plate for recommended
circuit protection device.

NOTE

: Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do
not install system where voltage may fluctuate above or below
permissible limits.

NOTE

: Use copper wire only between disconnect switch and unit.

NOTE

: Install branch circuit disconnect of adequate size per NEC

to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440--14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires

from disconnect through power wiring hole provided and into
unit control box.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault

should occur. The ground may consist of electrical wire or

metal conduit when installed in accordance with existing

electrical codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for

safety. Connect power wiring to contactor as shown in Fig. 6.

DISCONNECT
PER N. E. C. AND/OR

LOCAL CODES

CONTACTOR

GROUND LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

A91056

Fig. 6

---

Line Connections

Connect Control Wiring

Route 24v control wires through control wiring grommet and
connect leads to control wiring. See Thermostat Installation

Instructions for wiring specific unit combinations.
Use No. 18 AWG color--coded, insulated (35

°

C minimum) wire.

If thermostat is located more than 100 ft/30.48 m from unit, as
measured along the control voltage wires, use No. 16 AWG

color--coded, insulated wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from
incoming power leads.
Use furnace transformer, fan coil transformer, or accessory
transformer for control power, 24v/40va minimum.

NOTE

: Use of available 24v accessories may exceed the minimum

40va power requirement. Determine total transformer loading and
increase the transformer capacity or split the load with an accessory
transformer as required.

Final Wiring Check

IMPORTANT

: Check factory wiring and field wire connections

to ensure terminations are secured properly. Check wire routing
to ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hr before starting unit. To furnish power to heater

only, set thermostat to OFF and close electrical disconnect to
outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than
80 ft/24.38 m. Refer to the Long Line Guideline--Residential

Split--System Air Conditioners and Heat Pumps.

Install Electrical Accessories

Refer to the individual installation instructions packaged with kits
or accessories when installing.

Check OAT Thermistor and OCT Thermistor

Attachments

Outdoor Air Temperature (OAT) Thermistor is factory installed
by inserting the nibs on either sides of the thermistor body

through a keyhole in the bottom shelf of the control box and
locking it in place by turning it 90 degrees, such that the spherical

end of a nib faces the front of the control box.
Check to make sure the OAT is locked in place. See Fig. 7.

OAT Thermistor must be locked in

place with spherical nib end facing

towards the front of the control box

A05408

Fig. 7

---

Outdoor Air Thermistor (OAT) Attachment

264A

/265A

Summary of Contents for 264A

Page 1: ...than 1 disconnect switch Lock out and tag switch with a suitable warning label IMPORTANT Maximum liquid line size is 3 8 in OD for all residential applications including long line IMPORTANT Always in...

Page 2: ...B C 29 1 2 X 33 749 3 X 838 2 10 1 16 255 6 5 5 8 142 9 23 3 4 603 3 36 1 2 X 40 927 1 X 1016 9 5 8 244 5 6 13 16 173 0 28 3 4 730 3 A05177 Fig 2 Tiedown Knockout Requirements On rooftop applications...

Page 3: ...mended No Recommended For tubing line sets between 80 and 200 ft 24 38 and 60 96 m and or 20 ft 6 09 m vertical differential refer to Residential Split System Longline Application Guideline Table 2 Re...

Page 4: ...esult in equipment damage or improper operation Installation of filter drier in liquid line is required Install Liquid Line Filter Drier Indoor Refer to Fig 4 and install filter drier as follows 1 Bra...

Page 5: ...ELD POWER WIRING A91056 Fig 6 Line Connections Connect Control Wiring Route 24v control wires through control wiring grommet and connect leads to control wiring See Thermostat Installation Instruction...

Page 6: ...l regulations require that you do not vent refrigerant to the atmosphere Recover during system repair or final unit disposal Follow these steps to properly start up system 1 After system is evacuated...

Page 7: ...wer will run an additional 90 seconds to increase system efficiency Heating On a call for heating a standard thermostat non communicating makes circuits R Y and R G Circuit R Y energizes contactor sta...

Page 8: ...ed with a non communicating thermostat the utility relay should be wired between R and Y Low Ambient Cooling When this unit is operating below 55_F 12 78_C outdoor temperature provisions must be made...

Page 9: ...emperature do not meet the above requirements an abbreviated 30 second de frost will occur QUIET SHIFT This feature must be enabled by selecting the 3rd position of the 3 position dip switch for a non...

Page 10: ...control will energize the compressor contactor every 15 minutes If the thermal protector closes at the next 15 minute interval check the unit will resume operation If the thermal cutout trips for thr...

Page 11: ...flow Control Fault 45 Outdoor unit control board has failed Control board needs to be replaced Brown Out 24 v 46 The control voltage is less than 15 5v for at least 4 seconds Com pressor and fan oper...

Page 12: ...perating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detec...

Reviews: