Bryant 180CNV024 Installation Instructions Manual Download Page 7

7

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Federal regulations require that you do not vent

refrigerant to the atmosphere. Recover during system

repair or final unit disposal.

Follow these steps to properly start up the system:

1. After system is evacuated, close the disconnects to energize

the ID and OD units to assess the user interface (UI),

Keep

system in off mode

. Under the Advanced function menu,

assess the REQUIRED CHARGE CALCULATION screen.

Enter the lineset length and vapor tube diameter. The wall
control will now display the required charge adjustment

(see Fig. 7) for the lineset and an adjustment for a large in-
door coil if recognized as such by the wall control.

2. Add or remove the required charge adjustment for lineset

length to liquid service valve.

Note:

If lineset is less than 15 feet (--9.4

_

C), charge re-

moval may be necessary.

3. Fully open liquid and vapor service valves.

A170295

Fig. 7 -- Required Charge Adjustment

Calculated in wall control

4. Set wall control to operate cooling in CHARGING mode

(see Fig.7). Charging mode operates system compressor
speed and fan speeds to proper conditions to check the re-
frigerant charge.

NOTE

: Do not check charge in a mode other than CHARGING.

5. Select service valve subcool.
6. Wait for the specified stabilization time, depending on line-

set length. Then Compare measured subcooling at liquid
line service valve to target service valve subcool as shown

on CHARGING screens (see Fig. 8).

A170296

Fig. 8 -- Liquid Line Subcooling Target

Step 11 — System Functions And Sequence Of

Operation

The 180CNV models utilize an Evolution communicating wall
control. With a call for cooling, the outdoor fan and compressor are

energized to run at lowest cooling demand. If this does not satisfy
cooling demand, the system will ramp up in stages until it satisfies

the demand. After coping with the higher demand, the unit returns

to lower capacity operation until the demand is satisfied or until an
increase in demand.
When all demand is satisfied, the compressor will shut off. As the
unit operates at lower capacity, system vapor (suction) pressure will

be higher than it is during a standard single--stage system operation

or during a higher capacity operation.
When the outdoor ambient is more the 100

_

F (37.8

_

C), the

outdoor fan will continue to run for one minute after compressor
shuts off. This reduces pressure differential for easier starting in

the next cycle.
The conventional thermostat input is designed to work for

emergency operation only. Connections are Y, and C. The system

will only operate at maximum capacity.
The wall control displays the operation mode and fault codes as

specified in the troubleshooting section. See Table 7 for codes and
definitions.

NOTE:

Only one code will be displayed on the outdoor unit

control board (the most recent, with the highest priority). The
latest codes are stored and can be access via the wall control.

Crankcase Heater Operation

This unit has an internal crankcase heater that will be energized

during the off cycle and is intelligently demanded by the system to
prevent the compressor from being the coldest part of the system

thus enhancing the reliability. The crankcase heater will function

as needed any time the outdoor unit is powered. The indoor unit
and UI do not need to be installed for the crankcase heater to

operate properly.

NOTE

:

Contactor may close intermittently without the unit

starting. This is done to determine whether the control needs to
energize the crankcase heater. Closing the contactor powers the
inverter and allows the system to check compressor temperature.

Summary of Contents for 180CNV024

Page 1: ...distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this product Refer to the individual instructions...

Page 2: ...susceptible to lineset transmitted noise inside the dwelling and in extreme cases tubing breakage CAUTION INSTALLATION RECOMMENDATIONS In some cases noise in the living area has been traced to gas pu...

Page 3: ...shipment is damaged or incomplete Locate unit rating plate on unit corner panel It contains information needed to properly install unit Check rating plate to be sure unit matches job specifications St...

Page 4: ...ft 24 38 m substantial capacity and performance losses can occur Follow the pipe sizing recommendations in the 180CNV Product data to manage these losses Refer to Table 1 for field tubing diameters Re...

Page 5: ...heck should include all field and factory joints Evacuate Refrigerant Tubing and Indoor Coil CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operat...

Page 6: ...r has an internal crankcase heater Furnish power to the unit a minimum of 24 hr before starting the unit for the first time To furnish power to heater only set thermostat to OFF and close electrical d...

Page 7: ...e energized to run at lowest cooling demand If this does not satisfy cooling demand the system will ramp up in stages until it satisfies the demand After coping with the higher demand the unit returns...

Page 8: ...ons S Two minute time delay to return to standby operation from last valid communication S One minute time delay of outdoor fan at termination of cooling mode when outdoor ambient is greater than or e...

Page 9: ...th the control board and drives the compressor to the demanded RPM When the contactor closes it powers the inverter with line voltage The inverter changes the line voltage to 410 volts DC 3 phase and...

Page 10: ...n 187v for at least 4 seconds the contactor and fan relay are de energized Compressor and fan operation are not allowed until voltage is a minimum of 190v The control will flash the appropriate fault...

Page 11: ...e CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation In order to minimize the ambient influence make sure the thermistor curved surface hugs...

Page 12: ...long flashes indicating the second digit of the error code The short flash is 0 25 seconds ON and the long flash is 1 0 second ON Time between flashes is 0 25 seconds Time between short flash and firs...

Page 13: ...1 BRN RED SEC1 SEC2 PWM2 PWM1 INVERTER PL1 PL2 RVS CC PL11 PL4 PL6 OCT OAT SPT OST A B C NO USE UTIL LS Y C O COMM STATUS YEL BLU EXV PL5 PL3 HPS Utility Interface A11544 Fig 16 Variable Speed Control...

Page 14: ...14 Table 7 Troubleshooting...

Page 15: ...ld hose when charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pre...

Page 16: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations E2017 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Edition Date 12...

Reviews: