background image

5

Outdoor Unit Connected to Factory--Approved Indoor

Unit

Outdoor unit contains correct system refrigerant charge for

operation with factory--approved, AHRI--rated smallest indoor unit

when connected by 15 ft. (4.57 m) of field--supplied or

factory--accessory tubing, and factory--supplied filter drier. Check
refrigerant charge for maximum efficiency.

NOTE:

If the indoor furnace coil width is more than the furnace

casing width, refer to the indoor coil Installation Instructions for
transition requirements.

Install Liquid--Line Filter Drier Indoor

Refer to Fig. 4 and install filter drier as follows:

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in unit damage or

improper operation.
Installation of filter drier in liquid line is required.

1. Braze 5--in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5--in. (127 mm) liquid tube.
4. Connect and braze liquid refrigerant tube to the filter drier.

A05227

Fig. 4 -- Liquid--Line Filter Drier

Refrigerant Tubing connection Outdoor

Connect vapor tube to fitting on outdoor unit vapor service valves
and connect the liquid tube to fitting on outdoor unit liquid service

valve. See Table 1 for allowable sizes.

Sweat Connections

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.

S

Use a brazing shield

S

Wrap service valves with wet cloth or heat sink material.

Use refrigerant grade tubing. Service valves are closed from factory

and ready for brazing. After wrapping service valve with a wet

cloth, braze sweat connections using industry accepted methods
and materials. Consult local code requirements. Refrigerant tubing

and indoor coil are now ready for leak testing. This check should
include all field and factory joints.

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate

triple evacuation method may be used. See Service Manual for
triple evacuation method. Always break a vacuum with dry

nitrogen prior to opening the refrigerant system for servicing.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gauge capable of

accurately measuring this vacuum depth. The deep vacuum method
is the most positive way of assuring a system is free of air and

liquid water. (See Fig. 5)

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET
TIGHT

DRY SYSTEM

2000

MI

CRONS

2500

3000

3500

4000

4500

5000

A95424

A95424

Fig. 5 -- Deep Vacuum Graph

Final Tubing Check

IMPORTANT:

Check to be certain factory tubing on both indoor

and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.

Step 7 — Make Electrical Connections

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Do not supply power to unit with compressor terminal box

cover removed.

Be sure field wiring complies with local and national fire, safety,

and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of

improper voltage. See unit rating plate for recommended circuit

protection device.

NOTE:

Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not

Summary of Contents for 180CNV024

Page 1: ...distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this product Refer to the individual instructions...

Page 2: ...susceptible to lineset transmitted noise inside the dwelling and in extreme cases tubing breakage CAUTION INSTALLATION RECOMMENDATIONS In some cases noise in the living area has been traced to gas pu...

Page 3: ...shipment is damaged or incomplete Locate unit rating plate on unit corner panel It contains information needed to properly install unit Check rating plate to be sure unit matches job specifications St...

Page 4: ...ft 24 38 m substantial capacity and performance losses can occur Follow the pipe sizing recommendations in the 180CNV Product data to manage these losses Refer to Table 1 for field tubing diameters Re...

Page 5: ...heck should include all field and factory joints Evacuate Refrigerant Tubing and Indoor Coil CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operat...

Page 6: ...r has an internal crankcase heater Furnish power to the unit a minimum of 24 hr before starting the unit for the first time To furnish power to heater only set thermostat to OFF and close electrical d...

Page 7: ...e energized to run at lowest cooling demand If this does not satisfy cooling demand the system will ramp up in stages until it satisfies the demand After coping with the higher demand the unit returns...

Page 8: ...ons S Two minute time delay to return to standby operation from last valid communication S One minute time delay of outdoor fan at termination of cooling mode when outdoor ambient is greater than or e...

Page 9: ...th the control board and drives the compressor to the demanded RPM When the contactor closes it powers the inverter with line voltage The inverter changes the line voltage to 410 volts DC 3 phase and...

Page 10: ...n 187v for at least 4 seconds the contactor and fan relay are de energized Compressor and fan operation are not allowed until voltage is a minimum of 190v The control will flash the appropriate fault...

Page 11: ...e CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation In order to minimize the ambient influence make sure the thermistor curved surface hugs...

Page 12: ...long flashes indicating the second digit of the error code The short flash is 0 25 seconds ON and the long flash is 1 0 second ON Time between flashes is 0 25 seconds Time between short flash and firs...

Page 13: ...1 BRN RED SEC1 SEC2 PWM2 PWM1 INVERTER PL1 PL2 RVS CC PL11 PL4 PL6 OCT OAT SPT OST A B C NO USE UTIL LS Y C O COMM STATUS YEL BLU EXV PL5 PL3 HPS Utility Interface A11544 Fig 16 Variable Speed Control...

Page 14: ...14 Table 7 Troubleshooting...

Page 15: ...ld hose when charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pre...

Page 16: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations E2017 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Edition Date 12...

Reviews: