GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor--mounted, air--cooled, split--system air conditioner unit
suitable for ground or rooftop installation. Unit consists of a hermetic
compressor, an air--cooled coil, propeller--type condenser fan, and a
control box. Unit will discharge supply air upward as shown on
contract drawings. Unit will be used in a refrigeration circuit to match
up to a packaged fan coil or coil unit.

Quality Assurance

— Unit will be rated in accordance with the latest edition of

AHRI Standard 210.

— Unit will be certified for capacity and efficiency, and

listed in the latest AHRI directory.

— Unit construction will comply with latest edition of

ANSI/ ASHRAE and with NEC.

— Unit will be constructed in accordance with UL

standards and will carry the UL label of approval. Unit

will have c--UL approval.

— Unit cabinet will be capable of withstanding Federal Test

Method Standard No. 141 (Method 6061) 500--hr salt
spray test.

— Air--cooled condenser coils will be leak tested and

pressure tested.

— Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

— Unit will be shipped as single package only and is stored

and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

— U.S. and Canada only.

PRODUCTS

Equipment

— Factory assembled, single piece, air--cooled air

conditioner unit. Contained within the unit enclosure is
all factory wiring, piping, controls, compressor,
refrigerant charge Puron

r

(R--410A), and special features

required prior to field start--up.

Unit Cabinet

— Unit cabinet, including louvered coil guard, will be

constructed of galvanized steel, bonderized, and coated
with a powder coat paint.

Fans

— Condenser fan will be direct--drive propeller type,

discharging air upward.

AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER

180B

2 TO 5 NOMINAL TONS

— Condenser fan motors will be totally enclosed, 1--phase

type with class B insulation and permanently lubricated

bearings. Shafts will be corrosion resistant.

— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated

steel wire safety guards.

Compressor

— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration

isolators.

Condenser Coil

— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically

bonded to copper tubes which are then cleaned,
dehydrated, and sealed.

Refrigeration Components

— Refrigeration circuit components will include liquid--line

shutoff valve with sweat connections, vapor--line shutoff
valve with sweat connections, system charge of Puron

r

(R--410A) refrigerant, and compressor oil.

— Unit will be equipped with high--pressure switch, low

pressure switch and filter drier for Puron refrigerant.

Operating Characteristics

— The capacity of the unit will meet or exceed _____ Btuh

at a suction temperature of _____

_

F/

_

C. The power

consumption at full load will not exceed _____ kW.

— Combination of the unit and the evaporator or fan coil

unit will have a total net cooling capacity of _____ Btuh
or greater at conditions of _____ CFM entering air

temperature at the evaporator at _____

_

F/

_

C wet bulb

and _____

_

F/

_

C dry bulb, and air entering the unit at

_____

_

F/

_

C.

— The system will have a SEER of _____ Btuh/watt or

greater at DOE conditions.

Electrical Requirements

— Nominal unit electrical characteristics will be _____ v,

single phase, 60 hz. The unit will be capable of

satisfactory operation within voltage limits of _____ v to
_____ v.

— Unit electrical power will be single point connection.
— Control circuit will be 24v.

Special Features

— Refer to section of this literature identifying accessories

and descriptions for specific features and available

enhancements.

180B

Summary of Contents for 180B Series

Page 1: ...1 6 14 5 EER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 66 dBA S Electronic ECM ball bearing outdoor condenser fan motor S Compressor sound hood S Forward swept condenser fan blade S Quiet mount split post compressor grommets Comfort S System supports Evolutiont Control or standard 2 stage thermostat controls Reliability S ...

Page 2: ...e and air flow may reduce energy efficiency and shorten equipment life Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program For verification of certification for individual products go to www ahridirectory org STANDARD FEATURES FEATURES MODEL UNIT SIZE SERIES 180BNA 024 A 036 B 048 A 060 A Puron Refrigerant X X X X Maximum SEER Rating 21 0 20 0 17 7 16 7 2 Stag...

Page 3: ...ant Maximum Total Equivalent Length Outdoor unit ABOVE Indoor Vertical Separation ft m 25 7 6 26 50 7 9 15 2 51 75 15 5 22 9 76 100 23 2 30 5 101 125 30 8 38 1 126 150 38 4 45 7 151 175 46 0 53 3 176 200 53 6 61 0 024 AC with Puron 3 8 1 4 100 125 175 200 225 250 250 250 5 16 250 250 250 250 250 250 250 250 3 8 250 250 250 250 250 250 250 250 036 AC with Puron 3 8 5 16 225 250 250 250 250 250 250 ...

Page 4: ...oss Total Equivalent Line Length ft m 26 50 7 9 15 2 51 80 15 5 24 4 81 100 24 7 30 5 101 125 30 8 38 1 126 150 38 4 45 7 151 175 46 0 50 3 176 200 53 6 60 0 201 225 61 3 68 6 226 250 68 9 76 2 024 2 Stage Puron AC 3 8 5 8 0 1 1 2 3 3 4 4 5 3 4 0 0 0 0 1 1 1 1 1 7 8 0 0 0 0 1 1 1 1 1 036 2 Stage Puron AC 3 8 5 8 1 2 4 5 6 7 9 10 11 3 4 0 0 1 1 2 2 3 3 4 7 8 0 0 0 0 1 1 1 1 2 048 2 Stage Puron AC 3...

Page 5: ...vice panel for voltage drop not to exceed 2 Time Delay fuse FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection Complies with 2010 requirements of ASHRAE Standards 90 1 A W...

Page 6: ...ne system SYSTXBBSMS01 Evolution Smart Sensor Optional wall control used to monitor temperature and or fan control in an individual zone SYSTXBBRRS01 Evolution Remote Room Sensor Monitors temperature in an individual zone SYSTXBBRWF01 Evolution System Access Module Hardware for wireless access and control via phone or internet SYSTXBBNIM01 Evolution Network Interface Module Connects Heat Recovery ...

Page 7: ...ce heater which mounts to the base of the compressor to keep the lubricant warm during off cycles Improves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all commercial applications 3 Outdoor Air Temperature Sensor Designed for use with Bryant Thermostats list...

Page 8: ...8 DIMENSIONS 180BNA 2 5 TON ENGLISH 180B ...

Page 9: ...9 DIMENSIONS 180BNA 2 5 TON SI 180B ...

Page 10: ...ervice 24 609 6 Service 24 609 6 Service 24 609 6 24 609 6 24 609 6 12 304 8 12 304 8 12 304 8 12 304 8 6 152 4 Note Numbers in mm IMPORTANT When installing multiple units in an alcove roof well or partially enclosed area ensure there is adequate ventilation to prevent re circulation of discharge air A07833 180B ...

Page 11: ...tioning Heating Refrigeration Institute EER Energy Efficiency Ratio SEER Seasonal Energy Efficiency Ratio TDR Time Delay Relay In most cases only 1 method should be used to achieve TDR function Using more than 1 method in a system may cause degradation in performance Use either the accessory Time Delay Relay KAATD0101TDR or a furnace equipped with TDR Most Bryant furnaces are equipped with TDR UI ...

Page 12: ... 32 01 17 15 1 52 30 74 16 72 1 68 29 36 16 26 1 86 27 88 15 77 2 04 26 27 15 24 2 25 24 53 14 67 2 49 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7 CFM EWB F C Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Total Sens To...

Page 13: ...72 22 2 44 34 24 04 2 12 42 76 23 53 2 35 41 01 22 97 2 59 39 08 22 36 2 87 36 94 21 69 3 17 34 55 20 95 3 51 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7 CFM EWB F C Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Total ...

Page 14: ...72 22 2 58 20 31 12 2 95 56 17 30 49 3 29 53 85 29 77 3 66 51 25 28 96 4 07 48 30 28 04 4 53 44 95 26 97 5 04 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7 CFM EWB F C Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Total ...

Page 15: ... 22 2 71 82 38 55 3 99 69 03 37 63 4 39 65 88 36 60 4 81 62 41 35 46 5 27 58 54 34 19 5 78 54 26 32 81 6 34 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7 CFM EWB F C Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Total Se...

Page 16: ...27_C or add 835 Btuh 245 kW per 1000 CFM 480 L S of indoor coil air per degree above 80_F 27_C Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210 240 2008 If additional tubing length and or indoor unit is located above outdoor unit a slight variation in capacity may occur System kw is total of indoor and outdoor unit kilowatts EWB Entering ...

Page 17: ... 73 50 83 20 92 90 102 50 112 20 121 80 131 40 KW 0 61 0 74 0 87 1 01 1 16 1 34 1 54 1 78 45 7 22 TCG 19 10 18 80 18 30 17 70 17 00 16 10 15 10 13 90 SDT 64 70 74 40 84 10 93 80 103 40 113 00 122 60 132 10 KW 0 62 0 75 0 88 1 02 1 18 1 35 1 56 1 79 50 10 0 TCG 21 40 21 00 20 50 19 90 19 10 18 10 17 10 15 80 SDT 65 80 75 50 85 10 94 70 104 30 113 80 123 40 132 90 KW 0 65 0 77 0 90 1 04 1 19 1 37 1 ...

Page 18: ...0 81 20 90 50 99 90 109 20 118 40 127 50 136 70 KW 1 94 2 22 2 52 2 85 3 22 3 62 4 07 4 59 45 7 22 TCG 51 40 50 30 48 90 47 30 45 40 43 30 40 80 38 00 SDT 73 50 82 70 92 00 101 20 110 40 119 60 128 70 137 70 KW 1 98 2 27 2 57 2 90 3 26 3 67 4 13 4 65 50 10 0 TCG 56 70 55 40 53 90 52 20 50 20 47 90 45 20 42 20 SDT 75 20 84 30 93 50 102 60 111 80 120 80 129 90 138 80 KW 2 03 2 32 2 62 2 95 3 32 3 73...

Page 19: ...0 131 10 139 90 KW 2 87 3 22 3 59 3 98 4 40 4 86 5 37 5 93 180BNA060 A LOW 30 1 11 TCG 33 20 32 20 30 90 29 40 27 70 25 80 23 80 21 60 SDT 66 20 75 90 85 50 95 10 104 60 114 10 123 60 133 10 KW 1 66 1 98 2 31 2 67 3 07 3 53 4 07 4 70 35 1 67 TCG 37 20 36 00 34 60 33 00 31 10 29 10 26 90 24 50 SDT 67 50 77 10 86 70 96 20 105 70 115 10 124 50 134 00 KW 1 66 1 97 2 29 2 64 3 04 3 49 4 02 4 64 40 4 44...

Page 20: ...COOLED SPLIT SYSTEM AIR CONDITIONER 180B 2 TO 5 NOMINAL TONS Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with coated steel wire safety guards Compressor Compressor will be hermetically sealed Com...

Page 21: ...reater than 80 ft 23 4 m and or 35 ft 10 7 m vertical differential consult Residential Piping and Longline Guideline and Service Manual available from equipment distributor 6 If any refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise to the valve connections at the unit Refrigerant tubing lengths up to 36 in 914 4 mm may be buried without further consideration Do not bury refrigeran...

Page 22: ...continue or change at any time specifications or designs without notice and without incurring obligations EBryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Edition Date 09 12 Replaces PDS180B 04 Catalog No PDS180B 05 180B ...

Reviews: