Form: 2405
Universal Communication Gateway Reference Manual
Date: 01-25-2019
Revision: 8
Bryan Steam LLC, 783 North Chili Avenue, Peru, IN 46970
Web:
Phone:
765.473.6651
Fax:
765.473.3074
E-mail:
19
3.2.5
SIEMENS LMV5…
3.2.5.1
PASSCODE
You may need a passcode. The passcode
can be dependent on the burner
manufacturer. The LMV5… passcode is
“9876” or “WES”. If the passcode is
incorrect, check inside the burner control
box panel. You may need to contact the
burner manufacturer for the correct
passcode.
3.2.5.2
BMS ACTIVATION
Activation takes place with the AZL5 menus.
•
Operation
•
OptgModeSelect
•
GatewayBASon
When GatewayBASon is activated, plant
operation and diagnostics via the AZL… are
still possible.
The internal load controller must be turned
on for controlling the load with BMS. Use
the display menus as shown to activate the
internal load controller.
•
Params&Display
•
LoadController
•
Configuration
•
LC_OptMode
•
IntLCbus
3.2.5.3
ADDRESS
The address can be selected via the AZL
menu. The address can be set between 1
and 247.
•
Params&Display
•
AZL
•
Modbus
•
Address
3.2.5.4
TRANSMISSION PARAMETERS
The Baud Rate can be set via the AZL menu.
This can be set to 9600 bit/s or 19200 bit/s.
•
Params&Display
•
AZL
•
Modbus
•
Baud Rate
The Parity can also be setup via the AZL
menu.
•
Params&Display
•
AZL
•
Modbus
•
Parity
This can be set to “none”, “even”, or “odd”
3.2.5.5
TIMEOUT COMMUNICATION
FAILURE
The AZL will timeout when there is no
communication from the BMS. The time can
be set from 0 to 7200 seconds. When this
time has elapsed the BMS control mode will
change from remote to local control. This
can be changed via the AZL menu.
•
Params&Display
•
AZL
•
Modbus
•
Timeout