41
Bryan Steam, LLC
www.bryanboilers.com
Phone: 765-473-6651
783 N Chili Ave, Peru, IN 46970 [email protected]
See Appendix F for boiler water flow pressure drop
data and Appendix E for piping.
1. Water Flow Rates (
Variable Primary Pumping
Systems
)
a. Variable primary pumping systems shall
be capable of delivering no less than the
minimum and no more than the maximum
specified in Table 20 and Table 21 for each
boiler connected in the system.
Table 20: Minimum Water Flow Rates for
Variable Primary Pumping
Free Flex
Model
Minimum Flow Rate
gpm
Δ P (ft)
High Fire Δ
T (°F)
1000
19
.51
100
1500
29
.37
100
2000
38
.65
100
2500
48
.8
100
3000
57
1.15
100
3500
67
.42
100
4000
76
.42
100
4500
86
.42
100
5000
95
.5
100
5500
105
.58
100
6000
114
.67
100
Note: not for sizing constant volume pump
Table 21: Maximum Water Flow Rate for
Variable Primary Pumping
Free Flex
Model
Maximum Flow Rate
gpm
Δ P (ft)
High Fire Δ
T (°F)
1000
95
12.7
20
1500
143
9.2
20
2000
190
16.3
20
2500
238
20
20
3000
285
28.7
20
3500
333
11.33
20
4000
380
15.17
20
4500
428
25.17
20
5000
475
33.5
20
5500
523
37.25
20
6000
570
37.92
20
Note: not for sizing constant volume pump
2. Water Flow Rates (
Primary/Secondary Systems
)
a.
Each boiler connected to a secondary loop
of a primary / secondary pumping system
shall have a constant volume pump sized in
accordance with Table 22 or Table 23.
Table 22: Water Flow Rates for Primary/
Secondary Pumping at 20°F ΔT
Free Flex
Model
20°F ΔT Flow Rate
gpm
ΔP (ft) High Fire Δ
T (°F)
Low Fire
ΔT (°F)
1000
95
12.7
20
4
1500
143
9.2
20
4
2000
190
16.3
20
4
2500
238
20
20
4
3000
285
28.7
20
4
3500
333
11.33
20
4
4000
380
15.17
20
4
4500
428
25.17
20
4
5000
475
33.5
20
4
5500
523
37.25
20
4
6000
570
37.92
20
4
Table 23: Water Flow Rates for Primary/
Secondary Pumping at 40°F ΔT
Free Flex
Model
40°F ΔT Flow Rate
gpm
ΔP (ft) High Fire Δ
T (°F)
Low Fire
ΔT (°F)
1000
48
3.18
40
8
1500
71
2.3
40
8
2000
95
4.08
40
8
2500
119
5
40
8
3000
143
7.18
40
8
3500
166
2.67
40
8
4000
190
3.17
40
8
4500
214
6.25
40
8
5000
238
7.92
40
8
5500
261
9.25
40
8
6000
285
9.42
40
8