Form: 2435
Revision: 9
Free Flex Installation and Operation Manual
Date: 9-1-2017
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970
Web:
www.
bryanboilers
.com
Phone:
765-473-6651
Fax:
765-473-3074
Email:
30
Magnesium Sulphate
(MgSO4)
Corrosion
Silicon Dioxide (SiO2)
Hard Scale
It should be noted that water boilers may well
need chemical treatment for the first filling
plus additional periodic chemical treatment,
depending on system water losses and the
makeup requirements.
All water introduced into the boiler should be
softened and should include an oxygen
scavenger like sodium sulfite. This is required
to remove dissolved oxygen from the water.
Dissolved oxygen will cause severe system
corrosion.
Dissolved Oxygen
< 0.007 ppm
Total Iron
≤ 0.1 ppm
Total Copper
≤ 0.05
Total Hardness
≤
9
ppm
≤ 0.5
grains/gal
pH
8.3 – 10.0
Nonvolatile TOC
< 1 ppm
Oily Matter
< 1 ppm
Table 14 Recommended Feed Water
Limits
CAUTION
Bryan Steam Standard Warranty does not
cover problems caused by oxygen
contamination of boiler water.
Bryan Steam Standard Warranty does not
cover problems caused by scale build-up.
When using Glycol products, all Glycol
manufacturers’ requirements, including
rust inhibitors, must be adhered. Max
50% Glycol.
WARNING
Chemicals used in treating boiler water
are toxic and/or harmful. Always use
protective clothing and equipment when
working with/near chemicals. Contact
local authorities to determine if treated
boiler water can be discharged into local
waste water system.