Operation & Installation Manual RFP V2 Series
MA225 Rev 1
28 of 50
Note: It is essential that DIP switch 3 is set to “ON” position if SUB1012 is situated
in the last position on the zone. Outgoing termination point is to be left empty.
Note: The end of line device SUB360 must be fitted in the termination board for
unused zones.
Take special care to check DIP Switch 3 during installation or expanding the system.
There can only be one Smoke/Heat Alarm that is set as the EOL device in each zone
and it must be on the last Alarm for that zone. If this is set incorrectly, the panel will
indicate with the fault LED lit on that zone.