background image

 

Instruction Manual 

FAC20  

Rev 0 

 

 

 

   

 

 

                                             

 

Figure 6 FAC20 Alarm Locate 

2.  If 

the “TEST” LED is flashing RED, it means the source of alarm is from the external 

alarm trigger e.g. sprinkler, panic, etc. connected to this FAC20. The FAC20 cannot 
control the alarm condition generated by external input. 

3.  If ALL three LEDs are flashing RED as shown in Figure 7 below, the system is being 

controlled by the second FAC20 (if additional FAC20 is used in the circuit). 

 

Figure 7 Second FAC20 indication 

3.2 

Locate the source Alarm(s) 

When one Alarm activates, all the A

larms in the system will sound and the “LOCATE” LED 

will be flashing red as shown in Figure 8. 

Press the “LOCATE” button to locate the source of fire signal, the LED will change to steady 
red  as  shown  in  Figure  8,  all  the  Alarms  in  the  system  will  be  silenced  except  the  active 
Alarm(s). 

The “SILENCE” LED will flash RED to prompt the occupant to press the “SILENCE” 

button. 

To cancel the locate function, press the "LOCATE" button for approximately 3 seconds. 

Summary of Contents for FAC20

Page 1: ...Instruction Manual FAC20 Rev 0 FIRE ALARM CONTROLLER FAC20 MA455 Mar 2022...

Page 2: ...This page has deliberately been left blank...

Page 3: ...Locate the source Alarm s 9 3 3 Silence the source Alarms s 10 3 4 Fault Indications 11 4 GUARANTEE 12 5 REVISION HISTORY 13 Table of figures Figure 1 Fire Alarm Controller front and rear view 3 Figur...

Page 4: ...o generate false alarms With interconnected smoke heat CO Alarms when one Alarm senses smoke heat CO all Alarms will sound The FAC20 is a three button Alarm Controller intended to provide the occupant...

Page 5: ...44RC EIB141RC EIB160e Series EIB166e EIB161e 1 5 Specifications On Board Power Supply 230V AC 50Hz 20mA Operating Temperature 10 to 40 degree C Dimensions 117 5H x 75W x 30D mm see Figure 2 Interconne...

Page 6: ...Instruction Manual FAC20 Rev 0 4 The rear and side view of the controller are shown in Figure 2 below Figure 2 Dimensions of FAC20...

Page 7: ...controller to any non compatible Alarms apart from those listed above or to any other device produced by another manufacturer Doing so may risk damage and malfunction to the interconnected devices and...

Page 8: ...nnect FAC20 to the next Alarm in the circuit 5 If the external clean contact is required to activate the sounders of the Alarms e g sprinkler system N O contact Panic input etc connect the N O contact...

Page 9: ...th Do not use an Earth wire for the Interconnect line The interconnect wire must be treated as a mains powered conductor It should be suitably rated and double insulated Earthing of the FAC20 controll...

Page 10: ...as shown in Figure 5 below and all Alarms will sound 2 Press and hold TEST button for approximately 3 seconds to terminate the test the TEST LED will extinguish and all the Alarms in the system will s...

Page 11: ...FAC20 if additional FAC20 is used in the circuit Figure 7 Second FAC20 indication 3 2 Locate the source Alarm s When one Alarm activates all the Alarms in the system will sound and the LOCATE LED will...

Page 12: ...SILENCE button as shown in Figure 9 below after a delay the Alarm s will stop sounding The SILENCE LED will turn on RED for 10 minutes to indicate the source Alarm s will be silenced for 10 minutes Th...

Page 13: ...n open circuit fault is detected on the External Trigger Input wiring to the FAC20 Contact a licensed electrician to check the wiring Note The monitoring resistor is 4 7K ohm Figure 10 Wiring fault of...

Page 14: ...careless handling or where repairs have been made or attempted by others No other guarantees written or verbal are authorised to be made on behalf of Brooks All other conditions and warranties whether...

Page 15: ...Instruction Manual FAC20 Rev 0 13 5 Revision history Issue Date Description Written By Checked By 0 28 7 21 Initial revision BC AS HN...

Page 16: ...9 71 Victoria Crescent Abbotsford VIC 3067 Ph 03 9879 5294 SA P O Box 101 Woodville SA 5011 729A Port Road Woodville SA 5011 Ph 08 8347 0000 QLD P O Box 511 Archerfield QLD 4108 2 49 Boyland Ave Coope...