Operation & Installation Manual RFS1 V2
MA365 Rev 3
15 of 46
3
Residential Fire Safety Panel
3.1
RFS1 V2 Specifications
Table 2 RFS1 V2 Specifications
Feature
Specification
Enclosure
Zink steel 1.2mm powder coated oyster
Dimensions 280mm H x 305mm W x 75mm D
Power Supply
Input voltage 88-264V
AC
, 50W switch mode power supply
Output 13.5-16.5V
DC
adjustable
Nominal voltage 14.5V
DC
, Typical 13.8V
DC
on battery terminals
Standby Supply
12V
DC
/ 7AH (or 9AH) Sealed lead acid battery
Current Draw
Quiescent: 33mA with only end of line module
Alarm: 100mA
Operating Temperature 0°C to +50°C
No. of zones
Single zone fully supervised by an active end of line device
No. of Devices
A maximum combination of 15 devices is allowed inclusive of the
combination of the following:
•
15 smoke/heat alarms or
•
2 MCP or
•
2 Sprinkler Clean Contact, or
•
2 Strobe Modules or
•
2 Vibration Patrice Modules
Note:
current consumption must be calculated using “Battery
capacity calculation sheet” Chapter 9 page 37.
Alarm Output
Supervised 12V
DC
/ 1A fused output
1 set of changeover clean contact
Fault / Defect Output
1 set of changeover clean contact
Fault / Defect Mode
Initiated by abnormal system condition:
1. Power Supply fault, mains fail, battery low or removed, etc.
2. Alarm circuit wiring open or short circuit
3. Supervised alarm output open or short
4. Head removed
5. Communications fault
6. Memory fault
Control Switches
Ack
Silences panel buzzer until another event occur.
Locate
Silences all Smoke / Heat Alarms except those that have
actuated, restores after approximately 5 minutes. Locate
LED illuminates during the 5 minutes timer
Mute
Silences active Smoke / Heat Alarms, restores after
approximately 10 minutes. Mute LED illuminates during the
10 minutes timer
Test
Activates all Smoke / Heat Alarm sounders, vibration pad
and strobes, during test, the test LED illuminates
Visual Indications
Power ON
LED, mains power available
Alarm
LED, Common alarm
Defect
LED, common defect / fault
Keypad
One keypad per panel and one optional remote keypad or
1. 2 remote keypads without panel keypad.
2. Four wires (RS485) required for remote keypad.
1
To add additional display, additional current is 20mA quiescent and 40mA active.