51
10.15
ALARM LIST, PROBLEM AND POSSIBLE SOLUTIONS
Alarm Code
Description
Problem
Possible solution
AL1
BLACK OUT
The stove has been temporarily
without electric current.
Press button 4 for a few seconds and let the final cleaning
stage finish. The boiler will come back to the turn-off status.
AL 2
SMOKE PROBE
Problem with the smoke probe.
Check the probe connection or replace it.
AL 3
TEMP. SMOKE
The smoke temperature is higher
than 270ºC.
Regulate the pellet loading and/or the extractor speed.
Verify the type of fuel that has been used.
AL 4
BREAKDOWN
EXTRACTOR
Problem with the smoke
extractor.
Check the extractor electrical connection or replace it.
AL 5
START-UP FAILURE
The fuel does not fall or burn.
Check the geared motor and the ignitors correct operation.
Check a possible blockage of the auger feeder. Verify that
there is actually fuel in the tank.
AL 6
NO PELLET
There is no fuel in the hopper or
it does not fall inside the burner.
Refill tank. Check the augers operation. Check the fuel
characteristics and that it has not become compacted.
Clean the bottom of the hopper.
AL 7
THERMAL ALARM
The fuel thermal security
thermostat has shot up.
Restart the thermostat manually. Check the reason why the
temperature is excessive and provoked the overheating (fuel
load, excess draw , fuel type.)
AL 8
DEPRESSION
The combustion chamber has a
lack of draw.
Verify that the chamber is hermetic : check locks, gaskets…
etc. Check that the gas installation is correct (excess of
horizontal sections, elbow joint, etc). Possible fuel blockage.
AL 9
LACK OF FLOW
Lack of primary air or installation
not appropriate.
Check the primary air inlet. Verify installation (excess of
horizontal section, curves, dirtiness, etc).
AL
DIRTY FLOWMETER
The flow meter sensor is dirty.
Clean the flow sensor to get a proper reading. .
AL
FLOWMETER FAILURE
The flow sensor is broken.
Replace the flow sensor.
AL
WATER PROBE
Problem with the water probe.
Check the probe connection or replace it.
AL A
HOT WATER
The water temperature is high.
Check the pump is working. Check the water system
installation. Purge properly.
AL E
WATER PRESSURE
Problems with the hydraulic
circuit pressure. Pressure over
2.5 bars or under 0.4 bars.
Check the hydraulic pressure of installation. Working
pressure should be between 1 and 1,5 bars.
INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS
HYDRO SERIES RADIOFREQUENCY
EN