Operation with servo motor

Reset:

• Insert into the slot on the servomotor appropriate key supplied and turn it clockwise until the indicator in position 

90 ° 

• Perform a fast rotating counterclockwise to lock the actuator in the open position

Manual opening (test):

• Insert into the slot on the servomotor appropriate key supplied and turn it counter-clockwise approximately ½ turn 

in order to engage the return spring that will bring in automatic servo motor in the closed position and the indicator 

at 0 ° position

Motorized opening (test):

• Turn the lever on the thermoelectric fuse located next to the servomotor or disconnect power.

MECHANICAL FUSE REPLACEMENT

CAUTION!

All operations of connection or maintenance must be carried out with the damper closed and de-energized.

Operation

Fuse replacement is required every time the peak temperature within the duct, has exceeded the specified degrees 

Celsius on the same fuse. A tab shows the status of the fuse (fig. 9), when the body disappears into the plastic fuse 

holder (fig. 10), it is necessary to replace the fuse.

Procedure:

• Make sure the damper is unarmed 

verifying visibly that the indicator on 

the lever indicates the symbol] - [on 

the carter. Otherwise, act on the test 

button to manually open the damper. 

• Remove the clear plastic cover by 

unscrewing the central fixing screw 

(fig. 11) 

• Unscrew the 2 screws and remove the 

release mechanism from the plate. 

• Replace the fuse by compressing the 

spring and hooking the two protrud-

ing pins (fig. 12)

fig. 9

fig. 10

fig. 11

fig. 12

Central fixing screw

Fixing screw 
release mechanism

Clear plastic cover