7
FIRE DAMPERS
CERTIFIED ACCORDING TO EN 15650
SERIES MDF 25
CONTENTS
SPECIFICATIONS/GENERAL INFORMATION
pag 7
NORMATIVE REFERENCES
7
PRECAUTIONS FOR HANDLING AND INSTALLATION
8
MAINTENANCE 8
WALL INSTALLATION
8
OPERATING CONTROLS
9
MECHANICAL FUSE REPLACEMENT
10
OPERATION DATA AND WIRING MANUAL CONTROLS
11
OPERATION DATA AND WIRING MOTORIZED CONTROLS
11
SPECIFICATIONS/GENERAL INFORMATION
Fire damper suitable for installation on a wall, made from duct and galvanized steel components , calcium silicate
blade mono slab sp. 25 mm with perimeter seals to ensure sealing requirements to cold and hot smoke. The control
device ( manual with electromagnetic release or motorized ) consists of a plate removable and replaceable even after
installation, on which they are installed all the elements necessary for the proper operation and functioning of the fire
damper; the particular geometry of the control mechanism, prevents that the pressure present in the duct (up to 500
Pa) opening the blade if not acting directly from the reset lever. When installation is completed, the command will be
out of the masonry simplify any post-installation actions. The dampers, installed according to the instructions in this
manual , are used in HVAC systems by restoring the partitioning between two rooms, ensuring perfect insulation from
heat and smoke seal.
The installer has the obligation to follow the installation procedures and use of the equipment described in this
manual, in order to comply with the same conditions as the samples to be tested. Any deviation from the instruc-
tions, affect the validity of the certification of the product and the declaration of correct installation
NORMATIVE REFERENCES
Fire dampers tested according EN 1366/2 and classified according to EN 13501/3
CLASSIFICATION OF RESISTANCE
SUPPORT
EI 120 S - 500 Pa
EI 90 S - 500 Pa
LOW DENSITY RIGID WALL
SP.MIN. 100
(V
e
i
o)
da 100x200 a 800x600 MA / SE
da 100x200 a 800x600 MA / SE
Legenda
E = integrity
I = thermal insulation
S = smoke seal
V
e
= vertical installation
h
o
= horizontal installation
i
o = side exposed to fire indifferent
MA = manual reset device
SE = device with servomotor