WARNING  

 

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, 

OBSERVE THE FOLLOWING:

1. Installation work and electrical wiring must be done by a qualified 

 

person(s) in accordance with all applicable codes and standards, including fire-

rated construction codes and standards.

2.  Validated performance testing certified for use with BEST, Broan, and Broan Elite 

range hoods.  

3.  This unit is not designed to provide combustion air for fuel-burning appliances.  
4.  Do not connect the unit directly to a combustion appliance of any type.  
5.  Sufficient air is needed for proper combustion and exhausting of gases through 

the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the 

heating equipment manufacturer’s guideline and safety standards such as those 

published by the National Fire Protection Association (NFPA), and the American 

Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and 

the local code authorities.

6.  Before servicing or cleaning unit, switch power off at service panel and lock the 

service disconnecting means to prevent power from being switched on accidentally. 

When the service disconnecting means cannot be locked, securely fasten a 

prominent warning device, such as a tag, to the service panel.

7.  When performing installation, servicing or cleaning the unit, it is recommended to 

wear safety glasses and gloves.

8.  During extreme weather events including snow storms, ensure that the intake 

area for the outside air duct is not blocked and able to provide a clear pathway for 

outside air to enter the system.

9.  When cutting or drilling into wall or ceiling, do not damage electrical wiring or other 

hidden utilities.

10. When notching or drilling into framing including floor supports, rim joists, and wall 

studs, comply with code and manufacturer limitations on allowable modifications 

to these structural members.

11. This unit is intended to be installed within the home in a location protected from 

moisture.  

12. This unit must be in an accessible location which allows for inspection of the unit.  
13. Use this unit only in the manner intended by the manufacturer. If you have 

questions, contact the manufacturer at the address or telephone number listed in 

this document.

14. When federal, provincial or state legislation comprises more restrictive installation 

and/or certification requirements, the aforementioned requirements prevail on 

those of this document and the installer agrees to conform to these at his own 

expense.

AUTOMATIC MAKE-UP AIR DAMPER WITH 

TRANSFORMER & PRESSURE SWITCH

READ AND SAVE THESE INSTRUCTIONS

!

  FOR RESIDENTIAL USE ONLY 

!

CAUTION  

!

1.  Do not locate outside air inlet near hazardous materials or explosives.
2.  Unit shall not be installed to introduce air from crawlspaces, garages, attics, 

adjacent dwelling units, or other locations within the building shell.  Unit shall be 

installed to introduce air directly from outdoors.

3.  Do not run the outside air duct directly above or closer than 2 ft to any furnace or 

its supply plenum, boiler, or other heat producing appliance. 

4.  Any ductwork used in conjunction with the Damper must be installed in compliance 

with all local and national codes that are applicable.

5.  Do not operate the Damper for fresh air introduction until all system filters, 

including the central duct system filter, have been installed per the system design.

6.  Please read the unit specification label on the product for further information and 

requirements.  

7.  The Damper’s outdoor air intake, ducting, and any filters should be inspected and 

maintained on a regular basis.

8.  Insulate the duct and damper to prevent build-up of condensation in cold weather 

climates. Vapor barriers on both sides of insulation are recommended.

PLAN THE INSTALLATION

Planning the installation first requires selecting the most appropriate installation ap-

proach.  The chart below offers suggestions for the most effective installation approach 

by considering a few important factors. Further details on the two main types of instal-

lations are provided below.

 

Yes

• House has central duct work?

Yes

• Return-air side of duct work is 

accessible -either the return-air trunk 

or return- air plenum?

Damper connected to 

return side of central 

duct system

No

No

Damper  ducted directly 

to a ceiling, floor, or wall 

register

Outside Air Intake Location

Proper design and location of the outside air intake location is critical in ensuring that 

the Damper can safely and reliably provide an opening for fresh air to enter the home.  

The following requirements for the location of the outside air intake must be met:
•  Outside air intake is located a minimum of 10’ from combustion appliance vents, 

chimneys, plumbing stacks, and bathroom or kitchen exhaust vents.  If local codes 

have more stringent separation requirements, they shall apply.

•  Outside air intake is placed high enough above grade to prevent blockage from 

snow or other debris such as leaves, and at a minimum of 1’ above grade.

•  Make-up air damper should not draw air from crawlspaces, garages, attics, adja-

cent dwelling units, or any enclosed part of the building.  The Damper should be 

installed to draw air directly from outdoors.

Outside Air Intake Opening Protection

Because the Damper, together with the end cap and outside air duct which are installed 

with it, will allow outdoor air into the indoor environment, it is important to meet the 

following requirements:
•  Model 641FA (6”) and 643FA (8”) fresh air inlet wall caps include protective bird 

screens to keep out animals and outside debris. Clean screens often and do not 

remove.

•  If a protective bird screen other than the screen provided is used, it must cover the 

entire opening of the outside air duct.  This screen must also have openings of at 

least ¼” but no larger than ½”.

•  The outdoor air intake opening should meet local code provisions for the protection 

of openings in exterior walls, including steps to prevent moisture intrusion around 

the opening.  

Note that the screen over the outside air opening is not a filter.  It is intended to prevent 

the intake of leaves, animals, or debris into the outside air duct.  A downstream filter is 

necessary to remove pollen, dust, and other airborne particles.  Potential filter locations 

are shown below in the Typical Installations section.

Minimum Return Air Temperature Requirements

HVAC equipment manufacturers may have minimum requirements for the air tempera-

ture in the return air plenum.  Introducing outdoor air to the return side of the central 

duct system may impact this temperature.  The installer should adjust both the size of 

the outside air duct and the location of its connection to the return side of the central 

duct system in a manner so that minimum air temperature requirements are satisfied 

under design conditions. 

WHAT IS INCLUDED IN THE PACKAGE

- Motorized Damper
- Transformer
- Pressure Switch Kit which includes:
    - Pressure Switch
    - Probe
    - 12” PVC tubing 1/4” I.D.
    - Gasket
    - (6) Sheet Metal Screws

TOOLS REQUIRED

- 1/4” Socket Drive 
- Flathead or Phillips Screw Driver
- 3/8” Drill Bit
- Duct Tape
- Low Voltage Wire (2 Conductor)
- (2) 1/4” Female Spade Terminals
- Wire Nuts

MODELS  

MD6TU • MD8TU • MD10TU

Register this product at www.broan.com/register. For Warranty Statement, or to order 

Service Parts: go to www.broan.com and type the Model in the “Model Search” field 

at the top of the page.

Broan, 926 W. State Street, Hartford, WI 53027  800-637-1453

Summary of Contents for MD10TU

Page 1: ...Insulate the duct and damper to prevent build up of condensation in cold weather climates Vapor barriers on both sides of insulation are recommended PLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation ap proach The chart below offers suggestions for the most effective installation approach by considering a few important factors Further details...

Page 2: ...re It may not operate at low speeds since the pressure is below this limit MULTIPLE DAMPERS More than one damper may be required to balance the system If more than one is required use 1 MD6TU or MD8TU and then use the MD6 or MD8 dampers as ad ditional dampers INSTALLATION OF PRESSURE SWITCH AND PROBE For the probe pressure switch to work effectively the roof or wall cap must have a spring loaded d...

Page 3: ...ion and venting of all combustion equipment in the home FALSE TRIPPING Under certain extreme conditions there could be false tripping of the damper opening when the range hood blower is off If false tripping is encountered place an in line backdraft damper 7 model no 97 8 model no 438 10 model no 421 between the probe and the roof or wall cap SERVICE PARTS 97018853 Pressure Switch Kit 97013273 24V...

Page 4: ... the home by a range hood Range hoods are designed to pull out pollutants like cooking odors or moisture at the source so they don t linger in the home Because these fans pull air out of the house this air needs to be replaced with new air from outdoors Normally this make up air enters the home through cracks and holes in the shell of the building But modern homes are air sealed much more thorough...

Page 5: ...SERVER POUR USAGE RÉSIDENTIEL SEULEMENT MODÈLES MD6TU MD8TU MD10TU EMPLACEMENT DE LA PRISE D AIR EXTÉRIEUR La conception et l emplacement adéquats de la prise d air extérieur sont indispensables au bon fonctionnement et à la fiabilité du clapet pour faire pénétrer de l air frais dans la maison Il importe de respecter les exigences suivantes lors du positionnement de la prise d air La prise d air e...

Page 6: ...me Si vous utilisez plusieurs clapets choisissez un 1 clapet MD6TU ou MD8TU puis utilisez les modèles MD6 ou MD8 comme clapets additionnels INSTALLATION DU MANOCONTACTEUR ET DE LA SONDE Pour que la sonde et le manocontacteur fonctionnent correctement le capuchon mural ou de toit doit avoir un clapet à ressort Les produits Broan suivants sont recommandés MODÈLES DE CAPUCHON DE TOIT 437 Haute capaci...

Page 7: ...stion Effectuez le câblage tel qu illustré NOIR LIGNE BLANC NEUTRE VERT TERRE CLAPET D AIR DE COMPENSATION TRANSFORMATEUR 24V MANOCONTACTEUR DIAGRAMME DE CÂBLAGE CLAPETS MULTIPLES CLAPET D AIR DE COMPENSATION 24V 24V 24V 24V 20V BORNES 24V CÂBLAGE DUTRANSFORMATEUR DÉCLENCHEMENT INDÉSIRABLE Dans certaines conditions extrêmes le clapet peut se déclencher alors qu il ne le devrait pas s ouvre alors q...

Page 8: ...e stagnent pas dans la maison Puisque ces ventilateurs évacuent l air de la maison celui ci doit être remplacé par de l air neuf de l extérieur Normalement cet air de compensation entre dans l habitation par les ouvertures et les fentes de l enveloppe de l édifice Or les maisons modernes sont beaucoup plus étanches et ne présentent plus autant de fentes et d ouvertures De plus certains ventilateur...

Page 9: ...our éviter la condensation Il est conseillé de placer un coupe vapeur des deux côtés de l isolant REGULADOR DE AIRE AUTOMÁTICO DE REPUESTO CON TRANSFORMADOR E INTERRUPTOR DE PRESIÓN LEA Y CONSERVE ESTAS INSTRUCCIONES SOLO PARA USO RESIDENCIAL UBICACIÓN DE LA ENTRADA DEL AIRE EXTERIOR El diseño y el sitio adecuados de la ubicación de la entrada de aire exterior son vitales para garantizar que el re...

Page 10: ...ADORES Tal vez se requiera más de un regulador para equilibrar el sistema Si se requiere más de uno use 1 MD6TU o MD8TU y luego use los reguladores MD6 o MD8 como reguladores adicionales INSTALACIÓN DEL INTERRUPTOR DE PRESIÓN Y SONDA Para que la sonda y el interruptor de presión funcionen con eficacia la tapa para techo o pared debe tener un regulador cargado por resorte Se recomiendan los siguien...

Page 11: ... que se abre el regulador Apague la campana y compruebe que se cierra el regulador Un contratista calificado en HVAC también debe asegurarse la operación adecuada y la ventilación de todo el equipo de combustión en la casa Cablee el sistema como se ilustra 24V 20V CONTACTOS DE 24 V CABLEADO DELTRANSFORMADOR DISPARO EN FALSO Bajo ciertas condiciones extremas podría haber el disparo en falso del reg...

Page 12: ...as están diseñadas para extraer contaminantes como olores de cocinado o humedad en la fuente de tal manera que no perduren en la casa Debido a que estos ventiladores extraen el aire de la casa es necesario reemplazar este aire con aire nuevo del exterior Normalmente este aire de repuesto entra a la casa a través de grietas y orificios en la armazón del edificio Pero las casas modernas están mucho ...

Reviews: