background image

- 6 -

With airflow measuring stations permanently installed,

balancing is done by measuring airflow on one side of the
heat recovery ventilator and then the other. Adjustments
can then be made to the damper to equalize airflows.

When using the temporary method, an FMS is installed

in one air duct of the heat recovery ventilator and the flow
recorded. The FMS is then relocated to the other air duct
and the airflow is recorded again. Dampers can then be
adjusted to equalize airflow. This procedure should be
repeated to ensure that the unit is balanced properly.

Balancing Procedure

Before proceeding with balancing, all windows, over-

head doors and walk-in doors should be closed and
exhaust systems should be turned off.

The connections between the flow stations and the

ducts must be sealed with tape. Mount the magnehelic
gauge in a convenient location where it is level and will
not vibrate or be bumped. Zero the gauge. Measure the
exhaust air first as it is often the lowest due to a longer
duct system.

With the fan speed at maximum, connect the hoses

from the FMS to the magnehelic gauge. If the needle falls
below zero, reverse the hose connections. Ensure that
the damper is wide open. Take a reading from the mag-
nehelic gauge and record it. Remove the FMS and place
it in the supply duct. This process is not necessary if the
FMS is to be permanently mounted.

Repeat the procedure. If the reading is higher in the

supply duct, adjust the damper until the reading is the
same. If the reading is lower, return the FMS to the
exhaust duct and adjust the damper to obtain the same
reading as the supply duct.

System Service

Bi-Monthly Maintenance

Bi-monthly maintenance should include:

Air Filters

The standard foam filters are washable. Under normal

conditions it is recommended that they be cleaned every
two months. More frequent cleaning may be required
under extremely dirty operating conditions. Use a vacuum
cleaner to remove the heaviest portion of accumulated
dirt, then wash with warm water.

A medium efficiency filter for the supply airstream is

available from your supplier. This filter is disposable and
should be replaced when it becomes dirty.

Drain Pans and Interior of Unit

With the filters removed from the unit, the foil faced

insulation surfaces and drain pans should be wiped clean
with a soft cloth and mild cleaning solution. Ensure that
the drain fittings are free from dirt and draining freely.

Annual Maintenance

Annual maintenance should include:

Air Filters

Vacuum and wash standard foam filters. Replace

medium efficiency filter if present.

Drain Pans and Interior of Unit

Wash the foil faced insulation surfaces and wipe the

drain pans with a soft cloth and mild cleaning solution.
Check the drain fittings to ensure they are draining freely.

Flat Plate Heat Exchanger

The flat plate heat exchanger must be handled with

care. In order to ensure maximum efficiency of the parti-
tions, it is recommended that it be washed once a year
following the season of most intense use. Allow the flat
plate heat exchanger to soak for three hours in warm
water  and mild soap. Rinse under a heavy stream of
water. When replacing the flat plate heat exchanger sec-
tions, make sure the flutes on the heat exchanger are
positioned in the supply airstream. Failure to do so will
result in low airflow on the exhaust airstream due to sys-
tem pressure trapping or holding condensate in the flutes.

WARNING

Disconnect power before maintaining the unit.

WARNING

Disconnect power before maintaining the unit.

Washable Foam Filter or
MEF Filter - optional

Washable Foam Filter

Washable Foam Filter

MEF Filter - optional

Figure 1: 600 cfm and 1

150

 cfm

Figure 2: 700 cfm

Summary of Contents for HRV1150

Page 1: ...Installation Operation and Maintenance Instructions HRV650 HRV700 HRV1150 HRV1150...

Page 2: ...t and Balancing Flow Station Positions 5 Balancing Procedure 6 System Service Bi Monthly Maintenance 6 Annual Maintenance 6 Appendix A Mounting Diagrams 8 Appendix B Unit Dimensions 9 Appendix C Flow...

Page 3: ...talling the unit keep in mind that access to the control panel may be required Supply and exhaust ducts to outside may have 1 to 2 25 to 51mm of insulation on them Rubber vibration isolation may be re...

Page 4: ...s to be used ensure not to solder to the 3 4 19mm coupler while it is attached to the plastic drain fitting as deformation may occur Ensure adequate slope is present to allow good drainage minimum 1 4...

Page 5: ...Remote Wall Control Optional Remote mounted wall control options are solid state controls that can be used to control the ventilators from a remote location The connection from the ventilator to the...

Page 6: ...able Under normal conditions it is recommended that they be cleaned every two months More frequent cleaning may be required under extremely dirty operating conditions Use a vacuum cleaner to remove th...

Page 7: ...rol functions are not working properly Ensure that power is reaching the board Test the blower motors and damper actuators for operation when directly connected to the appropriate power voltage If the...

Page 8: ...connection of drain lines with adequate slope for drainage Wooden Curb Supplied by others Bolt to Floor Rubber Vibration Isolator Supplied by others U Channel Supplied by others 3 8 10mm Threaded Rod...

Page 9: ...uction is required for removal of heat recovery cores fans etc The access door can be removed from the cabinet with only 2 000 51 of clearance CONTROL PLATE ACCESS DOOR HEAT RECOVERY CORE REVERSED DOO...

Page 10: ...15 000 381 clearance from any obstruction is required for removal of heat recovery cores fans etc The access door can be removed from cabinet with only 2 000 51 of clearance 8 000 203 8 000 203 14 10...

Page 11: ...ruction is required for removal of heat recovery cores fans etc The access door can be removed from the cabinet with only 2 000 51 of clearance EXHAUST AIR SUPPLY AIR LEFT SIDE VIEW Dimensions in are...

Page 12: ...81 clearance from any obstruction is required for removal of heat recovery cores fans etc The access door can be removed from cabinet with only 2 000 51 of clearance REVERSED DOOR OPTION EXHAUST AIR T...

Page 13: ...203 15 250 387 2 000 51 LINE VOLTAGE IN NOTE A minimum of 12 000 305 clearance from any obstruction is required for power hook up low voltage remote connection and control panel access NOTE A minimum...

Page 14: ...Option Exhaust Air From Building Fresh Air From Outside Min 8 203mm Optional Canvas Vibration Isolator Min 12 305mm Min 12 304mm Flow Measuring Station FMS Balancing Damper not supplied Canvas Vibrati...

Page 15: ...1 25mm Min 3 76mm Plastic Drain Fitting To Drain Copper or Plastic Pipe Min 3 76mm Min 1 25mm 3 4 NPT Coupler Water Trap Plastic Hose To Drain NOTE All hose pipe and couplers to be supplied by others...

Page 16: ...12 VDC Low Voltage Controls All other terminals are dry contacts Low voltage terminal control consists of the following Wall Control 4 wire LVT 24 gauge minimum Occupied Night Setback Timer Sensor 24...

Page 17: ...trol and 24VAC power supply Use of 24VAC circuit requires isolating contacts ex thermostat to prevent interconnection of Class 2 outputs Occupancy control is achieved by connection to the terminal int...

Page 18: ...PJ2003 PJ2014 PJ1007 PJ1001A UCB1021 CR1029 CR1023 1 2 3 4 5 6 A B COM NC NO PJ2011 PJ1001 CR1024 CR1026 1 0 4 8 2 6 1 0 4 8 2 6 FILTRAN NOTE Low speed motor selection may be replaced by medium speed...

Page 19: ...472 9 9 14 1 15 7 7 4 11 7 13 3 5 0 9 3 10 9 2 6 6 9 8 5 0 2 4 4 6 1 900 425 8 5 12 4 13 8 6 4 10 2 11 7 4 3 8 1 9 6 2 2 6 0 7 5 0 1 3 9 5 4 800 377 7 0 10 4 11 7 5 2 8 6 9 9 3 4 6 8 8 2 1 7 5 0 6 4...

Page 20: ...st air Check filters and heat exchangers for blockage Check balance of airflows Outdoor temperature very cold Install electric duct heater if necessary Unit makes annoying noise Blower wheel out of al...

Reviews: