CAT.
PRC700B
ARCHITECTURAL AND ENGINEERING SPEC
TECHNICAL SPECS
SHIPPING SPECS
INSTALLATION OF ALARM
The smoke and CO combination alarm shall be a BRK Model PC1200 (cat. no. PRC700B)
and shall provide at a minimum the following features and functions:
1. A Photoelectric smoke sensing chamber and an electrochemical CO sensor.
2. The unit shall have an “10 Year End of Life” signal. This signal should be capable
of temporarily being silenced for up to 2 days. After about 2 days, the signal will
resume. After about 2-3 weeks the signal cannot be silenced.
3. Fully screened smoke sensing chamber to resist entry of small insects thereby
reducing the probability of unwanted alarms and be capable of self restoring.
4. Powered by replaceable 2 AA alkaline batteries and a solid state piezo horn rated at
85dB at 10 ft.
5. A visual LED power-on indicator to confirm unit is receiving power or is alarm.
6. A full function test button should check all alarm functions by simulating a smoke
and CO condition, causing the unit to alarm.
7. Two Silence features - Low Battery Silence: Silence low battery chirp for up to 8
hours. Alarm Silence: Temporarily silence unwanted nuisance alarms.
8. Tamper resistant locking pin that locks alarm to mounting bracket to prevent
removal of batteries.
9. The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and
relative humidity between 10% and 95%.
10. The unit shall contain mounting hardware and shall be listed for wall or ceiling
mounting.
11. The unit shall at a minimum meet the requirements of UL217, UL2034, CSFM, NFPA
72, NFPA 720, NFPA 101, ICC
Alarm Dimensions: 5.7”Dia. x 1.28”H
Weight:
7.5 oz
Operating Voltage:
3V Battery Powered (2 AA Alkaline)
Temperature Range: 40°F (4°C) to 100°F (38°C)
Humidity Range:
10% to 95% relative humidity (RH)
Audio Alarm:
85dB at 10 feet
Test/Silence:
Electronically simulates smoke and CO conditions,
causing the unit to alarm. Press and hold test/silence
button.
Alarm Reset:
Automatic when smoke clears
Smoke Sensor:
Photoelectric
CO Sensor:
Electrochemical
Indicator Lights/Sounds:
DC Power:
Intermittent Green LED
Local Alarm:
Audio alarm and rapidly flashing Red LED
Listing:
Listed to UL217 and UL2034 Standards
Individual Carton Dimensions
5.75 ”L x 1.38”D x 5.75”H
Weight
0.57 lbs.
Cube
0.03 ft3
UPC
0 29054 01497 9
Master Carton Dimensions
8.88 ”L x 6.06”W x 6.31”H
Master Pack
6
Weight
3.8 lbs.
Cube:
0.20 ft3
I2of5:
600 29054 01497 1
Pallet Information
Cases per Layer
32
Number of Layers:
8
Cases per Pallet:
256
Units per Pallet:
1,536
Cube:
55.8 ft3
Weight:
1,035 lbs.
©2014 BRK Brands, Inc. a Jarden Corporation
Company (NYSE: JAH)
3901 Liberty Street Road
Aurora, IL 60504-8122
All rights reserved
First Alert is a registered trademark of the First Alert Trust
BRK is a registered trademark of BRK Brands, Inc.
CM3206
brkelectronics.com
Installation of this alarm must conform to NFPA 72 and 720. Always check your local
building codes. Follow all instructions for placement as outlined in the user’s manual in
sections titled “Recommended Locations for Smoke Alarms” and “Locations to Avoid for
Smoke Alarms”.
THE PARTS OF THIS ALARM
1. Test/Silence button
2. LED alarm light
3. Install AA batteries here
4. Locking tab slot (Break out Tab)
5. Mounting bracket
6. Mounting Slots
7. Horn
MOUNTING
BRACKET
TOP VIEW
SIDE VIEW
5.7”
1.28”
3
4
5
6
4
6
1
2
7