INSTALLATION OF ALARM
Installation of this smoke alarm must conform to all Canadian
electrical codes. It is recommended that all units be on the same
fuse or circuit breaker. If codes do not permit, be sure the neutral
wire is common to both phases.
©2019 BRK Brands, Inc. All rights reserved. Distributed
by BRK Brands, Inc. 3901 Liberty Street, Aurora, Illinois
60504. BRK Brands, Inc. is a subsidiary of Newell
Brands Inc. (NYSE: NWL). BRK is a registered trademark
of BRK Brands, Inc.
brkcanada.ca
1. Smoke /CO Alarm
2. Ceiling or Wall
3. Power Connector
4. Wire Nut
5. Junction Box
6. Neutral Wire (White)
7. Interconnect Wire (Orange)
8. Hot Wire (Black)
THE PARTS OF THIS ALARM
TECHNICAL SPECS
Alarm Dimensions:
5.6” dia x 2”H
Weight:
8.5 oz
Operating Voltage:
120V AC 60Hz w/ Locked Lithium Battery Backup
Operating Current:
.09 amps (standby/alarm)
Temperature Range:
40° F (4° C) to 100° F (38° C)
Humidity Range:
10% to 95% relative humidity (RH)
Audio Alarm:
85dB at 10 feet
Test/Silence:
Electronically simulates a smoke or carbon
monoxide condition, causing the unit to alarm.
Press and hold the test/silence button.
Alarm Reset:
Automatic when Smoke and/or CO clears
Interconnections:
Up to 18 Units of First Alert BRK Smoke, CO and
Heat Alarms. Maximum of 12 smoke alarms.
See user’s manual for details.
Smoke Sensor:
Dual Ionization
CO Sensor:
Electrochemical
Indicator Lights/Sounds:
AC Power:
Constant Green LED
DC Power:
Intermittent Green LED
Local Alarm:
Red LED flashes rapidly Remote Alarm:
Red LED out
Latching Alarm:
Red LED flashes 2 sec. on/2 sec. off after
local alarm
Low Battery Latch:
Green LED flashes on for 2 seconds,
off for 2 seconds
End-of-Life Signal:
Alarm “chirps” 3 times with 5 green LED flashes
once per minute
Listing:
Listed to ULC S531 and CSA 6.19 Standards
SHIPPING SPECS
Individual Carton Dimensions: 5.69”L x 2.25”W x 5.59”H
Weight:
.63 lbs.
Cube:
.04 ft
3
UPC:
0 29054 01758 1
Master Carton Dimensions:
14.43”L X 6.19”W X 12.63”H
Master Pack:
12
Weight:
8.1 lbs.
Cube:
.65 ft
3
I2of5:
100 29054 01758 8
Pallet Information:
Cases per Layer:
19
Number of Layers:
3
Cases per Pallet:
57
Units per Pallet:
684
Cube:
42.2 ft
3
Weight:
527 lbs.
1. Mounting bracket
2. Mounting Slots
3. Locking Pins
4. Hot (Black) AC Wire
5. Neutral (White) AC Wire
6. Interconnect (Orange) Wire
7. Battery Drawer Latch
8. Battery Drawer - Install 9V
battery here
9. 9. Quick-Connect Plug
CAT.
SC9120LBLA
A. Unswitched 120VAC 60 Hz source
B. To additional units; Maximum = 18 total
(Maximum 12 Smoke Alarms)
MOUNTING
BRACKET
TOP VIEW
SIDE VIEW
5.6”
2.0”
ARCHITECTURAL AND ENGINEERING SPECS
The combination smoke and CO alarm shall be a BRK Model SC9120LBLA and shall provide
at a minimum the following features and functions:
1. An ionization smoke sensing chamber and an electrochemical CO sensor.
2. Powered by 120V AC, 60Hz and have a monitored 10-Year Locked Lithium Battery Backup and a solid
state piezo horn rated at 85dB at 10 ft. and be capable of self restoring.
3. The unit shall perform self diagnostic tests and issue a malfunction warning (three chirps) if the unit
malfunctions.
4. The unit shall have an “End of Life” signal. This signal should be capable of temporarily being silenced
for up to 2 days. After about 2 days, the signal will resume. After about 2-3 weeks the signal cannot
be silenced.
5. A visual power-on indicator to confirm unit is receiving AC power or has switched to battery backup
mode. Separate LED’s to indicate a smoke or CO alarm.
6. The CO sensor is adjusted not to detect CO levels below 30 PPM and will not alarm when exposed to
constant levels of 30 PPM for 30 days. It will alarm at the following levels: 400 PPM CO between 4 and
15 minutes, 150 PPM CO between 10 and 50 minutes and 70 PPM CO between 60 and 240 minutes.
7. Two Latching features: Alarm Latch to easily identify initiating alarm after alarm condition has subsided.
Low battery latch: to visually identify which unit is in low battery condition. Silence Feature: Alarm
Silence to temporarily silence nuisance alarms.
8. Two Locking features - tamper resistant locking pins that lock battery drawer and/or alarm to mounting
bracket. Battery drawer is shipped pre-locked so battery will not be discarded prematurely.
9. The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and relative humidity
between 10% and 95%.
10. The unit shall have a plug in connector and be capable of interconnection of up to 18 alarms, 12 of which
can be smoke alarms.
11. The unit shall at a minimum meet the requirements of ULC S531 and CSA 6.19.
1
2
3
5
6
4
2
3
9
7
8
678
43
1
5
2
A
B
}
}
43
1
5