background image

Install the outdoor unit on a firm rigid base to prevent excess noise and vibration.
Set the direction of the unit to ensure optimal condenser air circulation.
If there is risk of exposure to strong prevailing winds such as in coastal applications, ensure
that the unit is placed at 90 degrees to the wind direction, or provide protection from the wind
by the use of shields.
In particularly windy applications, install the unit to prevent adverse interaction with the unit.
If mounting on a wall or structure, the installation bracket should be adequately sized to support
the unit fully. The installation wall should be solid brick, concrete or similar construction, or
action must be taken to reinforce and/or support the unit.
The connection between bracket, wall and unit should be firm, stable and reliable.
Make sure that no obstacles restrict the condenser air flow or block any heat radiation.

Strong
wind

Strong
wind

Barrier

Incorrect

Correct

Seal

Drain joint

Base pan hole
of outdoor unit

(A)

(B)

The condensate drain joints differ slightly according to the

different size outdoor units in the range.
For the condensate drain joint with a seal (Fig.A), first fit the seal
onto the drain joint, then insert the drain joint into the base pan
hole of outdoor unit. Rotate joint 90 degrees to secure.
To install drain joint as shown in Fig.B, insert the condensate
drain joint into the base pan hole of outdoor unit until it clicks
in place. Connect the condensate drain joint with a drain hose
(provided by installer) to facilitate drainage of water produced
by the outdoor unit during heating mode.

CONDENSATE DRAIN INSTALLATION

OUTDOOR UNIT INSTALLATION PRECAUTIONS

REFRIGERANT PIPE CONNECTION

1. Cut the pipe with a suitable pipe cutter.
2. Place flare nuts on pipe after completing

burr removal, then flare the pipe.

3. Firmly hold the copper pipe in a suitably

sized die as shown in the table below.

..

Align the pipes to be connected.
Finger tighten the flare nut, then tighten
properly with a spanner and torque
wrench as shown.
Excessive torque can break the nut.

Outer diam.

(mm)

A (mm)

Max.

Min.

6.35

1.3

0.7

9.52

1.6

1.0

12.7

1.8

1.0

12.7

15.9

1.8

2.2

1.0

2.0

Bar

Copper pipe

Clamp handle

Handle

Bar

Indoor unit pipe

Flare nut

Interconnecting

pipe

.

Outer

diam.

Tightening

torque(N.cm)

Additional tightening

torque(N.cm)

Ø6.35mm

Ø12.7mm

Ø15.9mm

Ø9.52mm

1500

(153kgf.cm)

1600

(163kgf.cm)

3500

(357kgf.cm)

4500

(459kgf.cm)

3600

(367kgf.cm)

4700

(479kgf.cm)

2500

(255kgf.cm)

2600

(265kgf.cm)

CHARGING, AIR PURGE AND TEST OPERATION

1. Remove the electrical control board cover from the outdoor unit by loosening the screw.
2. Connect the interconnecting cables to the terminals as identified with their respectively matched

numbers and colours on the terminal blocks of indoor and outdoor units.

3. Secure the cable onto the control board with the cord clamp.
4. To prevent the ingress of water, loop the interconnecting cable so that water cannot track along the

cable and enter the indoor and outdoor units.

5. Isolate any unused cables or wires correctly. Ensure that they cannot come into contact with any

other electrical components or metal parts.

Cover

Screw

Terminal block of outdoor unit

Liquid side: 6.35mm

Ø

R410A: (Pipe length-5)x20g/m

Liquid side: 9.52mm:

Ø

R410A: (Pipe length-5)x40g/m

Refrigerant pipe length

Less than 5m

More than 5m

Air purging method

Vacuum pump

Additional amount of refrigerant required

Open the valve stem until it hits the valve
stopper. Do not try to open further.
Securely tighten the valve stem cap with
a spanner to help prevent leaks.
Valve stem cap tightening torque. See
Tightening torque table.

.

.

.

.

Flare nut

Stopper

Cap

Valve body

Valve stem

Vacuum pump

Make sure that any refrigerant added to the refrigeration system is added in liquid form to
ensure correct charging levels.
When relocating the unit to another place, use a vacuum pump to perform proper evacuation.

.

.

.

.

The indoor unit and interconnecting pipe between the indoor and outdoor units must be leak tested
and evacuated to remove any non-condensables, contaminants or moisture from the system.
Check that each pipe (both liquid and gas side) between the indoor and outdoor units has

been properly connected and all wiring is complete and checked before testing.

Pipe length and refrigerant amounts:

Outdoor
unit

Indoor
unit

Refrigerant

Packed valve

Flare nut

Gas
Liquid

A

C

D

B

1. Completely tighten the flare nuts, A, B, C and D, and

attach the manifold valve charge hose to a charge port
of the valve on the gas pipe side.

2. Then connect the charge hose to the vacuum pump.
3. Fully open the Low tap of the manifold valve.
4. Switch on the vacuum pump to evacuate the system.

After starting the pump, slightly loosen the flare nut of
the gas side valve, and check that air is entering.
(Operation noise of the vacuum pump changes and
the compound gauge indicates 0 instead of minus).
Re-tighten the flare nut and evacuate the system.

5. After the evacuation is complete, fully close the Low

tap of the manifold valve and switch off the vacuum
pump.
Evacuate for 15 minutes or more and check that
the compound gauge indicates -76cmHg (-1.0x10 Pa).

5

6. Turn the stem of the liquid line valve B about 45 counter-

O

clockwise for 6~7 seconds. After allowing gas to escape,
tighten the stem of the liquid line. Make sure that the
pressure displayed on the pressure gauge is slightly
higher than atmospheric pressure.

7. Remove the charge hose from the Low pressure charge hose.
8. Fully open the Liquid and Gas valve stems B and A.
9. Securely tighten the cap of the valves.

Manifold valve

Compound meter

-76cmHg

Low tap

Hi tap

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Gas side valve

Perform test operation after completing gas leak check at the flare nut connections and after an
electrical safety check.

Check that all piping and wiring have been properly connected.
Check that the gas and liquid side service valves are fully open.

1. Switch on the power, and press the ON/OFF button on the remote control to turn the unit on.
2. Use the MODE button to select COOL, HEAT, AUTO and FAN to check if all of the unit functions

are operating correctly.

3. When the ambient temperature is lower than 17 C, the unit cannot be controlled by the

O

remote control to run in cooling mode, but manual operation can be employed. Manual operation
should only be used when the remote control is disabled or maintenance is necessary.
Hold the indoor unit front panel sides and lift up at an angle until the panels clicks and remains open.
Press the Manual control button to select the AUTO or COOL, the unit will now operate under Forced

AUTO or COOL mode (see User Manual for details).

4. The test operation should last for at least 30 minutes.

1. Air purging

2. Using the Vacuum Pump

4. Test running

3. Safety and leakage check

A: Liquid line valve B: Gas line valve
C and D are the ends of indoor unit connecting pipes.

CAUTION

1. Soapy water method:

Apply a soapy water solution, directly to the indoor

and outdoor unit connections with a soft brush to check
for leaks at the connection points of the refrigerant pipe.
If bubbles are observed, a leak is present.

2. Leak detector

Use the leak detector to check for potential leaks.

O

U

T

D
O
O
R

U
N

I

T

ELECTRICAL CONNECTION - OUTDOOR UNIT

CAUTION

Indoor unit
check point

D

B

C

A

Outdoor unit
check point

Cover

NOTE:

Angled

Rough

Burred

90

O

Manual control button

Connect the indoor unit first, then the
outdoor unit.
Do not allow the piping to be dislodged from the
back of the indoor unit.
Ensure that the condensate drain has a constant
fall to the outlet.
Insulate any condensate drain extensions.
Be sure that the drain hose is located at
the lowest part of the piping bundle. Locating it
on the upper side can cause drain tray to
overflow inside the unit.
Ensure that power wiring is routed separately
to any other wiring.

1. Pass the piping through the hole in the wall.
2. Hook the indoor unit onto the upper portion

of installation plate. Engage the indoor unit with
the upper edge of the installation plate. Ensure
the hooks are properly seated on the installation
plate by moving it left and right to check.

3. Positioning adjustment can be easily made by

propping the indoor unit with a cushioning material
between the indoor unit and the wall. Make sure
this is removed at completion.

4. Press the lower left and right hand sides of the

unit firmly against the installation plate until the
hooks engage with the relevant mounting slots.

CAUTION

Indoor unit installation

1. For left-hand or right-hand piping,

remove the pipe cover from the side panel.

2. For right rear and left rear pipe exits,

install the piping as shown.

NOTE:

When choosing the condensate

drain connection side, please enure that the
condensate drain connection on the other
side (if applicable) is plugged. The condensate
drain shall be installed by a qualified installer.

Right rear pipe exit

3. Bundle the pipes, connecting cables, and

condensate drain securely with tape, as
shown in Figure on the right.

Left rear pipe exit

Interconnecting pipe installation

Because the condensate water from
the indoor unit is collected in a tray
before flowing out, ensure that no foreign
objects are placed in the tray that may
cause a blockage.

I

N
D

O
O
R

U
N

I

T

To indoor unit

To indoor unit

Cord clamp

L

S

N

L

S

N

or

Condensate tray

Pipe cavity

Refrigerant pipes

Wrapping

Condensate pipe

Interconnecting

Cables

Reviews: