Table 1. Ventilation F Factors
Gas appliance location
Source of Ventilation
Factor F
Gas appliance in a room or enclosure
Directly to outside*
300
Via an adjacent room
600
Gas appliance in a plant room
Directly to outside*
150
Via an adjacent room
300
Gas appliance in a residential garage
Directly to outside*
300
*
Directly to outside
means through an external wall to outside, into a cavity vented to outside,
into an underfloor space vented to outside, or into a roof space vented to outside.
Installation of a gas appliance in a room or enclosure for properties approved for construction
AFTER
March 31
st
2014
a.
Determine if the rating per cubic metre of the space is greater than 0.4 MJ/hr per m³.
Example:
Unit rating (Ur)
= 120MJ/hr
Room volume (Rv) = 1m x 1m x 2.4m = 2.4m
3
Ur/Rv
= 120/2.4 = 50 MJ/hr per m
3
As the result is greater than 0.4 MJ/hr per cubic metre of the space, additional ventilation is required.
Refer to AS/NZS 5601 for natural ventilation requirements.
NOTE
For New Zealand ventilation requirements and all other applications, e.g. Mechanical Ventilation,
refer AS/NZS 5601.