Brink Air for life Installation Regulations Download Page 6

2 Technical specification

2.1 General product specification

Product description

Name:

Wireless Controller with humidity sensor

Technical product specifications

Operating voltage:

3 V

Protection class:

IP21

Type of battery :

CR2032.MRF Lithium (preferred manufacturer

Renata or Panasonic CR-2032/BS )

Not applicable if a permanent power connection

is used!

Frequency

868 MHz

Ambient conditions

Ambient temperature:

0 °C to 50 °C

Storage temperature:

-20 °C to 60 °C

Humidity:

0% to 90%

Other:

For indoor use

Max distance between USB transceiver and

Wireless Controller with humidity sensor

300 m (open field; 1 meter height)

2.2 Environment influences

The Wireless Controller with humidity sensor should be placed and used in a space with the correct ambient

conditions for proper operation. The Wireless Controller with humidity sensor may only be mounted indoors, but

not close to a heat source, a radiator, in a extreme humid environment. The Wireless Controller with humidity

sensor may also not be exposed to direct radiation heat (sun light). The Wireless Controller with humidity sensor

may also not be mounted close to a magnetic field. This could damage internal components.

Wireless Controller with humidity sensor 616880-B

Summary of Contents for Air for life

Page 1: ...Wireless Controller with humidity sensor English Installation regulations ...

Page 2: ...l bracket 10 3 3 Connecting the AC DC converter option 10 3 4 Using another frame option 12 4 Put into use 13 4 1 Connecting with USB Tranceiver Pairing 13 4 2 Back to factory setting Wireless Controller with humidity sensor 15 5 Information additional Wireless Controller with humidity sensor 16 5 1 Connecting additional RF sensor with USB Tranceiver Pairing 16 5 2 RH sensor general 17 5 3 Setting...

Page 3: ...ntroller with humidity sensor should only be used in combination with products that have been approved by Brink Climate Systems B V The Wireless Controller with humidity sensor can only be used with a HRU appliance which is equipped with a USB connection The Wireless Controller with humidity sensor is a wireless remote control to operate your ventilation system This remote control also displays wh...

Page 4: ...r more sensors are connected to the HRU appliance it will ventilate according to the set conditions of the connected sensor s If multiple controllers sensors are used the controller sensor that requests the highest ventilation level always has priority Boost function The boost function can be canceled at any time by pressing another button of the Wireless Controller with humidity sensor When the b...

Page 5: ...ame and wall bracket and one for the USB transceiver The delivery content of the Wireless Controller with humidity sensor consists of the following components 1 Wireless Controller with 1 humidity sensor 2 Frame 2 3 Wall bracket 3 4 Double sided adhesive tape 4 5 Mounting screws 5 6 USB transceiver 6 7 Short information with QR 7 code to on line manual Wireless Controller with humidity sensor 6168...

Page 6: ... between USB transceiver and Wireless Controller with humidity sensor 300 m open field 1 meter height 2 2 Environment influences The Wireless Controller with humidity sensor should be placed and used in a space with the correct ambient conditions for proper operation The Wireless Controller with humidity sensor may only be mounted indoors but not close to a heat source a radiator in a extreme humi...

Page 7: ...onform set requirements of the build in humidity sensor the white LED next to button 1 will flash once as button press confirmation Button 2 When button 2 is operated the HRU appliance will run for 30 minutes at ventilation level 3 boost function and then again at ventilation position 1 the white LED placed next to button 2 will flash once as button press confirmation Button 3 4 When the not visib...

Page 8: ...on the Wireless Controller with humidity sensor flashes with frequency of 1 Hz 1 blink per second This LED flashes for 10 seconds every 3 hours or for 300 seconds if any of the buttons are operated Wireless Controller with humidity sensor with battery power supply When the Wireless Controller with humidity sensor is equipped with a permanent power supply optional this LED flashes permanently See t...

Page 9: ...essary when a permanent power supply option is used The Wireless Controller with humidity sensor should be placed at a height of approximately 1 65 meters above the floor Screw or glue the wall bracket onto the wall in the correct position Take note The up arrow on the wall bracket must point upwards Backside wall bracket with position double sided adhesive tape Step 2 Remove the plastic isolation...

Page 10: ...g the AC DC converter When using the optional AC DC converter the wall bracket must be attached to a electrical wall box Ø 55 mm Connect the optional AC DC converter A with the Wireless Controller with humidity sensor B conform the wiring diagram The following actions should be performed to connect the optional 5V AC DC converter Step 1 Place the converter in the wall box The 230V power supply mus...

Page 11: ... Step 5 When the Wireless Controller with humidity sensor has been fitted on the wall the USB transceiver can be placed in the USB port of the appliance which must be connected with the Wireless Controller with humidity sensor To connect the USB transceiver with HRU appliance see Connecting with USB Tranceiver Pairing page 13 Connecting additional RF sensor with USB Tranceiver Pairing page 16 Wire...

Page 12: ... that a large number of frames from other vendors also can be used The following types of frames can also be used instead of the standard frame A Gira System 55 A B Busch Jaeger Reflex S1 B C Jung AS C D Siemens Delta D E Berker S 1 E F Merten System M F The above mentioned alternative frames are not included in the Brink delivery program Wireless Controller with humidity sensor 616880 B ...

Page 13: ... USB transceiver starts flashing 1x per second The pairing mode is active for 10 minutes Step 3 Press any button on the Wireless Controller with humidity sensor The LED s 4 pcs will flash 0 5 sec ON and 5 sec OFF max time 5 minutes Step 4 Press the pairing button 2 sec 10 sec on the bottom of the controller through a small hole for example with the end of a paper clip Pairing enabled when the LEDs...

Page 14: ...RH sensors to connect with the device press different button the number of the button is also the number of connected accessories in the menu of the device If pairing is not successful go back to Step 4 Check also the USB transceiver Button 3 button 4 are not visible but still can be used for configuring a note ID Wireless Controller with humidity sensor 616880 B ...

Page 15: ...ess the pairing button for example with end of a paper clip for more than 20 seconds To confirm this reset all LED s will flash two times All the pairing information has been deleted from the Wireless Controller with humidity sensor Factory setting USB transceiver Press the button for more than 20 seconds To confirm this reset the green LED will flash two times All the pairing information has been...

Page 16: ...SB transceiver starts flashing 1x per second The pairing mode is active for 10 minutes Step 3 Press any button on the extra Wireless Controller with humidity sensor or sensor The 2 LED s will flash 0 5 sec ON and 5 sec OFF max time 5 minutes Step 4 Press the pairing button 2 sec 10 sec on the bottom of the controller through a small hole for example with the end of a paper clip Pairing enabled whe...

Page 17: ...sor that requests the highest level Depending on the sensitivity of the humidity sensor the Wireless Controller with humidity sensor adjusts the air flow proportionally between the setting 1 set low and setting 3 set high The settings made in the menu of the connected appliance applies to all connected humidity sensors 5 3 Settings RH sensor Renovent 180 300 400 Excellent After installing one or m...

Page 18: ...r See RH value Information menu installer See the installation instructions Flair appliance After installing one or more RH sensors it must be activated in the settings menu step number 7 1 to ON Optionally the sensitivity of the sensor can be altered by means of step number 7 2 Process for adjusting the value s in the settings menu of the Flair appliance see the installation instructions Step no ...

Page 19: ... low Not applicable if the optional 230 volt power supply interface is used Replace battery with correct type CR2032 MRF battery manufacturer Renata or Panasonic CR 2032 BS Pay attention to the position of the battery The text marked must always be legible after inserting the battery For replacing battery take Wireless Controller with humidity sensor from the wall bracket see Remove Wireless Contr...

Page 20: ...r promoting re use recycling and other forms of recovering such waste in order to limit the amount of waste The WEEE logo on a product or on the packaging indicates that this product may not be disposed of or thrown away with domestic waste You should dispose of all your old electronic or electrical equipment via special collection points for such dangerous waste Separate collection and correct tr...

Page 21: ... writing via Brink Climate Systems B V P O Box 11 NL 7950 AA Staphorst The Netherlands The right to guarantee lapses in case of incorrect or improper use of the Wireless Controller with humidity sensor and failure to follow the user indications in this user s manual Warning Making changes to the Wireless Controller with humidity sensor hardware or software is not permitted This can have an effect ...

Page 22: ...equipment directive RoHS 2011 65 EU substances directive The product described above has been tested according to the following standards EN 62368 1 2020 EN 62479 2010 EN 60669 2 5 2016 EN 60730 1 2016 Safety EN 60730 2 2008 Safety EN 60950 1 2006 A11 2009 A1 2010 A12 2011 A2 2013 AC 2011 EN 301 489 1 V2 2 0 EMC EN 301 489 3 V2 2 1 EMC EN 300 220 1 RED V3 1 1 EN 300 220 2 RED V2 1 1 The product be...

Page 23: ...Brink Climate Systems B V P O Box 11 NL 7950AA Staphorst T 31 0 522 46 99 44 E info brinkclimatesystems com www brinkclimatesystems com 616880 B ...

Reviews: