DRAIN RATE ADJUSTMENT
If you installed the drain valve then the water will
drain when the sensor detects that the water
salinity is too high. Alternatively and if necessary,
the air cooler can be set to replace some water
after a set time of cooling operation with the
following procedure.
1. While the wall control is OFF, hold down AUTO
for at least 3 seconds.
2. Press while pressing AUTO.“A1” displays.
3. Release Auto. Press
until “A6” displays.
4. Press AUTO.
5. “00”will display. Press
until “01” displays.
6. Press AUTO.
7. “A6”will display. Press
until “A8”displays.
8. Press AUTO.
9. A number will be displayed. Press
or
until the number displayed corresponds to
the desired drain delay time in the table below.
10. Press AUTO to complete the adjustment. Exit
the programming mode by pressing the
POWER button.
Commissioning The Air
Cooler
CORRECT WATER LEVEL
With the water pump still disconnected, turn on
the water supply and allow the tank to fill. If you
have installed the drain valve instead of the bleed
funnel you will need to turn the water on by
pressing COOL on the wall control while it is in
the OFF state. The water inlet valve will now
remain open for 15 minutes.
When the tank is full the float valve will stop the
water entering the air cooler. Wait for this to
happen and observe the level.The correct water
level is approximately 5mm below the surface of
the tank the float valve is mounted on. If the level
is too high rotate the float clockwise. If it is too
low rotate the float anti-clockwise, as shown.
Display
05
07
11
15
Time between Drains
1.3 hours
2 hours
4 hours
10 hours
STANDARD
13