FLOOR PROTECTOR
Your wood stove should be placed on a 1 inch, non-combustible surface with a k factor of 0.84. For multiple layers,
add R-values of each layer to determine the overall R-value. Th
e R value for the required board is 1.03. If there
is a horizontal section of chimney connector, the fl oor protector should go under it and 2 inches beyond each
side
To calculate R-Values for alternative methods, see ALTERNATE FLOOR PROTECTOR CALCULATIONS
section in this manual.
Th
e fl oor protector should exceed the stove as follows:
Dimension
Inch
mm
H
⃰⃰
Front
16
635
J**
Left
6
153
K**
Right
6
153
L**
Back
1
25
M
Total Width
46
1169
N
Total Length
53.5
1359
* Canadian installations require 18” (457mm)
** Canadian installations require 8” (203mm)