4.4 FLOOR PROTECTOR
The stove must be placed on solid concrete, solid masonry, or when installed on a combustible
fl
oor, on a Type 2
fl
oor protector
listed to standard UL 1618 with a minimum R value of 1.03 and a minimum thickness of 1/2” or equivalent. The
fl
oor protector is
required to provide heat, live ember, and ash protection and must be of a non-combustible, continuous solid surface to protect against
in
fi
ltration of live embers and ash. For UL Listed
fl
oor protectors, refer to manufacturers instructions for installation directions.
Manufacturers of listed
fl
oor protectors include Imperial Metal Products and Hy-C among others. To calculate R-Values for alternative
methods, see Alternate Floor Protector Calculation Methods in the back of this manual.
Dimension
Inch
mm
H*
Front
9
229
J
Flue rear
2
51
K**
Left
8
203
L**
Right
8
203
M
Flue Side
2
51
⃰
Canadian installations require 18” (457mm)
⃰
⃰
Canadian installations require 8” (203mm)