background image

4.0 

 

     INSTALLATION

4.1 POSITIONING THE STOVE

It is very important to position the stove as close as possible to the chimney, and in an area that will favor the most ef

fi

 cient heat 

distribution possible throughout the house.  The stove must therefore be installed in the room where the most time is spent, and in 
the most spacious room possible.  Recall that stoves produce radiating heat, the heat we feel when we are close to a stove. A stove 
also functions by convection, that is through the displacement of hot air accelerated upwards and its replacement with cooler air. If 
necessary, the hot air distribution from the stove may be facilitated by the use of a fan or blower.

•  Do not place any combustible material within 4’ (1.2m) of 

the front of the unit.

•  The clearance between the 

fl

 ue pipe and a wall are valid only 

for vertical walls and for vertical 

fl

 ue pipe.

•  The chimney connector must not pass through an attic or roof 

space, closet or similar concealed space, a 

fl

 oor, or a ceiling.

•  For Canadian installations, where passage through a wall, 

or partition of combustible construction is desired, the 
installation must conform to CAN/CSA-B365.

• A 

fl

 ue pipe crossing a combustible wall must have a minimum 

clearance of 18” (457.2mm).

• To reduce 

fl

 ue clearances from combustible materials, contact 

your local safety department.

Back wall / Arrière Mur

Side wall / P

a

roi Lat

é

rale

Side wall / P

a

roi Lat

é

rale

Sd

e

a

/

a

o

at

éa

e

E

E

D

D

Back wall / Arrièr

e Mur

Ceiling / Plafond

Floor Protector / Protection de Plancher

g

F

G

Back wall / Arrière Mur

Side wall / P

a

roi Lat

é

rale

Side wall / P

a

roi Lat

é

rale

Sd

e

a

/

a

o

a

ae

C

B

A

Dimension

Inch

mm

A

Backwall to Stove

12

305

B

Sidewall to Stove

12

305

C

Sidewall to Flue

13

330

D

Wall to Stove (Angled Installation)

8

203

E

Wall to Flue (Angled Installation)

8

203

F

Ceiling Height

84

2133

G

Backwall to Flue

13

330

4.2 FREE STANDING STOVE INSTALLATION

A stove must never be installed in a hallway or near a staircase, since it may block the way in case of 

fi

 re or fail to respect required 

clearances. It is of the utmost importance that the clearances to combustible materials be strictly adhered to during installation of the 
stove.  Refer to the table and diagrams below for minimum required clearances.

SAFETY NOTICE

 

IF THIS STOVE IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. TO  REDUCE THE RISK OF 
FIRE, FOLLOW THE INSTALLATION INSTRUCTIONS. 

 

CONSULT YOUR MUNICIPAL BUILDING DEPARTMENT OR FIRE OFFICIALS ABOUT PERMITS, 
RESTRICTIONS AND INSTALLATIONS REQUIREMENTS IN YOUR AREA.

 

USE SMOKE DETECTORS IN THE ROOM WHERE YOUR STOVE IS INSTALLED.

 

SMOKE EXPELLED FROM THE UNIT, BY EITHER PAINT CURING, OPENING THE FUEL LOADING DOOR, 
OR A NEGATIVE PRESSURE INSIDE THE HOME, COULD TRIGGER THE SMOKE DETECTORS. MOUNT 
SMOKE DETECTORS AT LEAST 10’ FROM STOVE

 

NEVER USE GASOLINE, GASOLINE-TYPE LANTERN FUEL, KEROSENE, CHARCOAL LIGHTER FLUID, 
OR SIMILAR LIQUIDS TO START OR “FRESHEN UP” A FIRE IN THIS HEATER. KEEP  ALL SUCH LIQUIDS 
WELL AWAY FROM THE HEATER WHILE IT IS IN USE.

 

IN THE EVENT OF A CHIMNEY FIRE, PUSH THE AIR CONTROL FULL CLOSED TO  DEPRIVE THE FIRE OF 
OXYGEN. CALL THE FIRE DEPARTMENT.

 

A SOURCE OF FRESH AIR INTO THE ROOM OR SPACE HEATED SHALL BE PROVIDED WHEN REQUIRED.

 

ROOM HEATER, SOLID FUEL TYPE, ALSO FOR USE IN MOBILE HOMES.

Summary of Contents for SW180

Page 1: ...SE INSTRUCTIONS THIS MANUALWILLHELPYOU TO OBTAIN EFFICIENT DEPENDABLE SERVICE FROM THE HEATER AND ENABLEYOU TO ORDER REPAIR PARTS CORRECTLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE French version is...

Page 2: ...Flue Pipe Type Standard Single Wall or Double Wall Black or Blued Steel 2100 F 650 C Minimum Chimney Height 12 3 7m Maximum Log Length 12 304mm Electrical 110 Volt 60 Hz 31 Watt Dimensions Overall wi...

Page 3: ...e of the three offered kits A Pedestal Kit SA180P B Leg Kit SA180L C Fireplace Insert SA180i Refer to the instructions found inside each kit for proper assembly A 7 16 socket wrench A 5 16 socket Best...

Page 4: ...that you use cardboard or other means of padding to protect the finish on your new stove 3 2 FREESTANDING LEG ASSEMBLY 1 Unpack the kit and ensure all components are present Qty Description Part 4 Ca...

Page 5: ...panels 4 Realign the first side panel with the mark made previously 5 Using the predrilled holes in the facade panel as a guide mark and drill holes for the self tapping screws used to mount the faca...

Page 6: ...Mur Side wall Paroi Lat rale Side wall Paroi Lat rale S de a a o at a e C B A Dimension Inch mm A Backwall to Stove 12 305 B Sidewall to Stove 12 305 C Sidewall to Flue 13 330 D Wall to Stove Angled...

Page 7: ...ers of listed floor protectors include Imperial Metal Products and Hy C among others To calculate R Values for alternative methods see Alternate Floor Protector Calculation Methods in the back of this...

Page 8: ...he floor 2 To attach the leg model use two 3 8 16 UNC bolts through the floor The heater must be electrically grounded to the steel chassis of the mobile home with 8 GA copper wire using a serrated or...

Page 9: ...arrier and tight fitting windows and or has any powered devices that exhaust house air 5 There is excessive condensation on windows in the winter 6 A ventilation system is installed in the house If an...

Page 10: ...ft effect your stove s performance is directly dependent on an adequate draft from your chimney Do not connect this unit to a chimney flue serving another appliance The following recommendations may b...

Page 11: ...not weaken any structural components of the existing fireplace or chimney nor reduces protection of combustible materials required by national building codes Consult with your local building or fire a...

Page 12: ...y a professional Make sure there are no cracks loose mortar or other signs of deterioration and blockage Have the chimney cleaned before the stove is installed and operated When connecting the stove t...

Page 13: ...nector and a minimum 24 gauge ventilated wall thimble which has two air channels of 1 25 4 mm each construct a wall pass through There shall be a minimum 6 152 4 mm separation area containing fibergla...

Page 14: ...d horizontally must slope at least 1 4 inch per foot with the upper end of the section toward the chimney Any installation with a horizontal run of stove pipe must conform to NFPA 211 You may contact...

Page 15: ...same manufacturer and install the ceiling support package or wall pass through and T section package firestops where needed insulation shield roof flashing chimney cap etc Maintain proper clearance t...

Page 16: ...lackened windows Incomplete log combustion Smaller pieces of wood will dry faster All logs exceeding 6 in diameter should be split The wood should not be stored directly on the ground Air should circu...

Page 17: ...d combustion is the most efficient technique for wood heating because it enables you to select the type of combustion you want for each given situation The wood will burn slowly if the wood stove air...

Page 18: ...t should be removed to reduce the risk of a chimney fire We strongly recommend that you install a magnetic thermometer on your smoke exhaust pipe approximately 18 above the stove This thermometer will...

Page 19: ...hed only when cold 7 2 GASKETING It is recommended that you change the door gasket which makes your stove door air tight once a year in order to insure good control over the combustion maximum efficie...

Page 20: ...Possible Remedies Unplug blower first if equipped Cool exhaust flue gasses Use double or triple wall external chimney Burning unseasoned wet wood Use dry seasoned hardwood Smoke rolls out when feed o...

Page 21: ...530 FIREBRICK 4 5 x 7 5 x 1 25 2 18 891783 FIREBRICK 3 x 4 1 2 3 19 26706 RIGHT BRICK RETAINER 1 20 26705 LEFT BRICK RETAINER 1 21 69952 HEAT SHIELD 1 22 26703 WINDOW CLAMP 4 23 69953 DOOR ASSEMBLY 1...

Page 22: ...22 30 28 27 33 32 31 26 25 34 13 29 23 9 22 10 1 14 21 21 11 2 12 8 7 8 4 5 18 3 16 17 19 20 6 15 24 WIRING SCHEMATIC...

Page 23: ...1 39 26730 BACKING PLATE 1 SA180I Key Part Description Qty 60 26734 Surround Top 1 61 26735 Surround Left 1 62 26736 Surround Right 1 63 26414 Clamp Top Trim 1 64 892340 Trim Kit Sw180 1 65 83386 10...

Page 24: ...24 NOTES...

Page 25: ...given with a required thickness T in inches R 1 k x T c C factor is given R 1 C 2 Determine the R value of proposed alternate floor protector a Use formulas in step 1 above to calculate R value of pro...

Page 26: ...d to the stove When ordering repair parts always give the following information as shown in this list 10 0 HOW TO ORDER REPAIR PARTS 1 The part number SW180 2 The part description ____________________...

Page 27: ...______ Reason for Purchase Alternative Heat Main Heat Source Decoration Cost Other _________________________ What was the determining factor for purchasing your new appliance _______ I have read the o...

Page 28: ...28 CUT HERE CUT HERE Fold Here Fold Here Breckwell 227 Industrial Park Road South Pittsburg TN 37380 USA Fold Here PLACE STAMP HERE...

Reviews: