Braun D124.1S2 Instruction And Operation Manual Download Page 7

D124.1S2-Manual_EN_Rev03

2020_APR_28

7

Minimum Measuring Period 

All  rate  measurements  are  based  on  a  time  interval  measurement  over  a 
(variable)  number  of  input  signal  pulses.  A  programmable  minimum 
measuring  period  thus  will  be  maintained,  automatically  including  more 
input  pulses  into  every  measurement  with  increasing  input  frequency. 
This establishes an averaging over the programmed period of time, which 
helps  to  stabilize  the  measurements,  specifically  with    fluctuating  varia-
bles.  As  a  standard,    a  minimum  time  of  0.4    sec  is  recommended.  A 
shorter  period  should  only  be  selected    to  trace    a  fast    variation  (by  the  
analog  signal  or  alarm).  A  longer  period  however  reduces  the  maximum 
allowable input  frequency, as listed below. 
The parameter of P00.03 defines the minimum measuring period:of time, 
with a number of steps available: 
parameter  minimum time    max input frequency 
 

0 = 

 0.03 s 

100 kHz 

 

1 = 

0.07 s  

100 kHz 

 

2 = 

0.1 s 

             100 kHz 

 

3 =          0.4 s 

             100 kHz 

 

4 =          0.8 s 

              75 kHz 

 

5 =          2.0 s 

              30 kHz 

 

6 =          5.0 s  

             12 kHz 

 

7 =         10.0 s  

              6 kHz 

Note: 
The  updating  sequence  for  the  display  will  be  defined  in  a  separate  pro-
gram step (P02.01). 

Step P00.03 
minimum measuring time 

Group P01.xx 
Measurement Configuration 
I

nput Scaling 

Scaling defines  the relation  between the  input signal frequency (in terms 
of  Hz),  and  the  corresponding  display    (in  the    unit  term  and  decimal 
position as required by the application).  Both values are free programma-
ble by their decimals and numerical amount. Of course, they must refer to 
the  same  operation  level.  This  reference  point  is  recommended  at    the 
high  end    of  the  intended  operation    range,  but  can  be  surpassed  in  the 
later operation without error. 
Example: 
A  signal  frequency  of  13250  Hz  corresponds  to  a  speed  of  5000  RPM. 
Program as follows:  

in step P01.00 

parameter 0 

in step P01.01 

parameter 13250 

in step P01.02 

parameter 0 

in step P01.03 

parameter 5000 

General Note to the resolution: 
Do not use too many decimals! If there are more decimals  than justified 
by the operational fluctuation of the  variable, and the transmitter resolu-
tion,  the  minor    digits  in  display  will  fluctuate  accordingly. 
Note: 
The parameters as set on delivery, apply to 60 pulses per revolution. 

Step P01.00 
decimals for input frequency 

Step P01.01 
signal frequency at reference 

Step P01.02 
decimals for display 

Step P01.03 
speed value at reference 

Summary of Contents for D124.1S2

Page 1: ...ion Monitor Series D124 1S2 with analog output and setpoint alarm Instructions and Operation Manual valid for serial nos exceeding 211600 Contents page Specifications 2 Instructions for Use Short form...

Page 2: ...U1M 20 40Vac dc version U2 85 265Vac dc version U2M 85 265Vac dc Consumption 5 W resp 5 VA Signal input matching speed direction sensors series A5S3 to other sources response level on off 7 volts 4 vo...

Page 3: ...rmal operation the Analog Output and the Setpoints follow the input signal with the in step P00 03 programmed time The Display update rate additionally depends on step P02 01 After a sudden interrupt...

Page 4: ...ondition 0 forw 1 rev 1 reverse 03 8 minimum no of reverse pulses to release reverse alarm 05 04 8 time period for reset of reverse pulse counter xxx seconds 010 sec 05 8 forced direction at zero spee...

Page 5: ...relay control leads The ground terminal PE is internally separated from common zero but tied by a 100 k resistor to it EMI The unit complies with all relevant regulations as determined by the Policy...

Page 6: ...it will become valid touched instead leaves the parameter at its previous value Leave the programming phase by again touching The display returns to process readings Programmable Parameters Group P00...

Page 7: ...ined in a separate pro gram step P02 01 Step P00 03 minimum measuring time Group P01 xx Measurement Configuration Input Scaling Scaling defines the relation between the input signal frequency in terms...

Page 8: ...d in step P00 03 the display may have its own up dating programmable in steps of 0 1 seconds up to 9 9 sec Set the parameter to the desired time sequence A recommended value is 0 3 sec Step P02 00 num...

Page 9: ...r the display of the speed Step P04 00 setpoint SP1 Alarm Hysteresis The hysteresis is the margin between condition excess and no excess defined by its bandwidth and its position in reference to the s...

Page 10: ...hase Starter time elapse The starter time elapse is adjusted in program step P04 05 with range 000 999 sec Step P04 05 starter time period Relay output SP1 assigned to setpoint SP1 or to reverse alarm...

Page 11: ...l Display and keys reference control inputs high level 10 24volts vs ref or contact closure vs sensor supply Input section and sensor supply Sensor supply 100 k A2 A1 A3 1 2 38 screen not connected to...

Page 12: ...ion of 4 1999 Operating temperature range for version M extended to 20 C to 65 C Supply voltage for version U1M 20 40Vac dc 6 2009 for serial nos exceeding 211500 Voltage output is obsolete Plug in te...

Reviews: