Brant Radiant Heaters HL2 Series User Manual Download Page 6

6

HL2 

Series

LLTCL001-1M-8/13 (CDS)

!

!

DANGER

WARNING

Improper installation, adjustment, alteration,service 
or maintenance can cause property damage, injury 
or death.

This is 

NOT

 an explosion-proof heater.  Where there is the 

possibility of exposure to flammable vapors or dusts, consult 
the local fire marshall, your insurance carrier or authorities for 
approval of the proposed installation.  Do 

NOT

 install in 

residential or explosive environments.

This heater must be installed and serviced by trained gas 
installation and service personnel only.  The installation of this 
heater must conform with local building codes or, in the 
absence of such codes, the National Fuel Gas Code (NFPA 
54).

GAS CONNECTION

Allowances must be made for the system to expand.  A 
flexible gas connection of approved type is required. The 
connector shall be of Type 1 hose per Exhibit “A” Section B.4., 
and Figure 1 and 2.  Consult manual for further instructions.

Read and understand the installation, operating 
and maintenance instructions thoroughly before 
installing or servicing this equipment.

Des installation réglage, modification, maintenance 
ou entretien inappropriés peuvent causer des 
dommages matériels, des blessures ou la mort. 

Ceci n est 

PAS un radiateur antidéflagrant. En présence possible de 

vapeurs ou de poussi res inflammables, consulter le commissaire 
des incendies local, votre compagnie d assurance ou les autorités 
compétentes pour l approbat

ion de l installation projetée. NE

 

C N IENT PAS aux applications résidentielles ou   tout 
environnement sujet   explosion. 

Ce radiateur   ga  ne doit  tre installé et entretenu que par du
personnel formé et qualifié   cette fin.  installation de ce radiateur 
doit  tre conforme aux codes locaux du b timent ou, en l absence

 

de tels codes, du National Fuel Gas Code (NFPA 54)

RACCORDEMENT AU GAZ

Prévoir du jeu pour la dilatation du syst me.  n raccordement par
tube flexible approuvé pour le ga  est nécessaire.  e raccord 
flexible devra  tre de type 1 tel qu indiqué au schéma   A

, section

 

B.4., et aux figures 1 et 2 Se référer au manuel pour plus 
d information. 

 

ire et comprendre les directives d installation, de

 

fonctionnement et d entretien avant d installer ou

 

d entretenir cet équipement

.

!

WARNING. 

To ensure system performance and 

safety, this unit must be properly vented.

Improper installation, adjustment, alteration, service or 
maintenance can cause property damage, injury or 
death.

Des installation, réglage, modification,maintenance ou 
entretien inappropriés peuvent causer des dommages 
matériels, des blessures ou la mort.

This heater can be installed in various configurations as specified in the 
manual.  

AIRCRAFT HANGARS. 

This heater must be installed in accordance 

with the latest edition of the Standard for Aircraft  angars, ANSI NFP

4

.

PUBLIC GARAGES. 

This heater must be installed in accordance with 

the latest edition of the Standard for Par ing Structures, ANSI NFP

A, or the Code for Repair Garages, ANSI NFP

A or the Canadian 

Natural Gas and Propane Installation Code, CSA B14 .1. as per 
Clause 1.1.4.

VENTING.

 This heater s

 venting system must comply with the following 

requirements

  Do not exceed 2  feet vent length or place more than two (2) 

  

 

 

elbows in the venting system.

 

se 4-DS   ent  it for single sidewall venting  

 

  Common vented models (with  -fitting) must be wired on the same  

 

control.

  A minimum ventilation rate of 4.  cfm 1

 

Btu

 is required for unvented operation.

Ce radiateur peut  tre installé dans différentes configurations tel que 
spécifié dans le manuel. 

HANGARS À AVIONS. 

Ce radiateur doit  tre installé en conformité avec 

a derni re édition de la norme Standard for Aircraft  angars, ANSI NFP

4

.

GARAGES PUBLICS.

 Ce radiateur doit  tre installé en conformité avec 

la derni re édition de la norme Standard for Par ing Structures, 
ANSI NFP

, ou du Code for Repair Garages, ANSI NFP

A ou, au 

Canada, du Code d installation du ga  naturel et du propane,

 

CSA B14 .1., article 1.1.4.

ÉVACUATION.

  e syst me d évacuation de ce radiateur doi

t

satisfaire aux exigences suivantes  

   Ne pas dépasser 2  pi en longueur de conduit ou utiliser plus de 2 

    coudes   

 dans le syst me d évacuation.

    tilise  l ensemble d évacuation R

T P-4 pour une évacuation murale 

    unique. 

    es mod les avec évacuation commne (avec raccord en  ) doivent 

     tre reliés   une m me commande.

    n taux de ventilation minimal de 4 pcm 1

 Btu

 est nécessaire

 

    pour un fonctionnement sans syst me d évacuatio

n

AVERTISSEMENT.

 Pour assurer le rendement et le 

fonctionnement sécuritaire du syst me, cet appareil 
doit  tre ventilé de fa on appropriée.

65,000* - 75,000*

W 1 side shield
W 2 side shield

s

2  ft. from burner

50,000* - 60,000*

W 1 side shield
W 2 side shield

s

2  ft. from burner

105,000* - 125,000*

W 1 side shield
W 2 side shield

s

2  ft. from burner

80,000* - 100,000*

W 1 side shield
W 2 side shield

s

2  ft. from burner

155,000* - 175,000*

W 1 side shield
W 2 side shield

s

2  ft. from burner

130,000* - 150,000*

W 1 side shield
W 2 side shield

s

2  ft. from burner

180,000* - 200,000*

W 1 side shield
W 2 side shield

s

2  ft. from burner

45

45

45

45

45

45

45

152.4
152.4
152.4
152.4

.2

11 .4
11 .4
11 .4
11 .4

.2

1
1
1
1

.2

1

.

1

.

1

.

.1

.
.2

2

.

2

.

2

.

2

.

111.

2 5.
2 5.
2 5.
2 5.
111.

2

.

2

.

2

.

2

.

111.

CLEARANCE TO COMBUSTIBLES 

FIRE HAZARD

. Always maintain published clearance to combustibles.  In locations 

used for the storage of combustible materials, signs must be posted. Consult manual 
for additional guidelines.

MODEL 

BTU/h RANGE

MOUNTING 

ANGLE

FRONT

SIDE

BEHIND

TOP

BELOW

SIDE

SIDE

TOP

BELOW

0° MOUNTING ANGLE

FRONT

BEHIND

BELOW

45° MOUNTING ANGLE

TOP

BELOW

BEHIND

FRONT

0° W/1 SIDE SHIELD

TOP

SIDE

SIDE

BELOW

0° W/2 SIDE SHIELDS

TOP

IMPORTANT:

.

 

se high BT  output when determining clearances.   inimum end clearance for all models 

is 12 inches.   aximum mounting angle is 45 .   eep cover in place. 

22.

.1
.

22.
1 .

22.

.1
.

22.
1 .

5 .
14 .
1

.

5 .
1 .

5.

.1
.

4 .
1 .

.4

1
12

.2

2 .

1

14 .
1

.

5 .4
2 .

1 4.1
1
1

.2

.2

2 .

cm

in.

2

2

14

2
1

2
5
42
2

24

11

2

42

5

5

4

41

11

11

54

22.
2 .
2 .
22.
1 .

22.
2 .
2 .
22.
1 .

5 .
2 .
2 .
5 .
1 .

5.

2 .
2 .
4 .
1 .

.4

2 .
2 .

.2

2 .

1

2 .
2 .
5 .4
2 .

1 4.1

2 .
2 .

.2

2 .

cm

in.

14

2

24

2

2

1

11

4

11

41

11

15.2
25.4
15.2
15.2
15.2

15.2
25.4
15.2
15.2
15.2

15.2
25.4
15.2
15.2
15.2

15.2
25.4
15.2
15.2
15.2

15.2
25.4
15.2
15.2
15.2

15.2
25.4
15.2
15.2
15.2

15.2
25.4
15.2
15.2
15.2

cm

in.

1

1

1

1

1

1

1

cm

in.

4
4

4

4

44

1

1

1

1

2

2

44

44

4

2

2

4

4

4

RISQUE D’INCENDIE. 

Toujours respecter les dégagements prescrits de tout matériau 

combustible. Dans les endroits servant au stoc age de matériaux combustibles, des 
écriteaux doivent en avertir. Se référer au manuel pour des directives supplémentaires. 

*IMPORTANT: 

Déterminer les dégagements en fonction de la capacité nette de Btu maximale.  e 

dégagement minimal   l extrémité est de 12 po pour tous les mod les. angle d inclinaison maximal est de

 

45 . Garder le couvercle en place. 

 

(cm & in.)

!

CAUTION

MODEL /MODELE NO.

INPUT BTU/H

FOR USE WITH

NATURAL GAS

RADIATEUR A INFRAROUGE A FAIBLE INTENSITE

VOLTS A.C.

STARTING AMPS.

RUNNING AMPS.

120~60Hz

4.8

1.1

MANIFOLD PRESSURE

MIN. INLET PRESSURE

ORIFICE SIZE

3.5” WC

5.0” WC

#3 D.M.S

HEATER TYPE

VERSION

MIN. MOUNTING ANGLE:

COMBUSTION CHAMBER:
4” BC ALUMINUM

FOR INDOOR USE

BRANT RADIANT HEATERS LIMITED
34 SCOTT AVE., PARIS, ONTARIO
TEL: 1-519-442-7823 WWW.BRANTRADIANT.COM

ANSI Z83.20b - 2011 CSA 2.32b - 2011 Low - Intensity Infrared Htr. 
ANS Z83.20b - 2011 CSA - 2011 Low - Intensity Infrared Htr.

SERIAL NO. 

0870 XXXX XXXX 0001

RE-VERBER-RAY LOW INTENSITY INFRARED HEATER

FOR INDOOR INSTALLATION ONLY. NOT FOR USE IN RESIDENTIAL DWELLING.
INSTALLATION À L’EXTÉRIEUR SEULEMENT. NE PAS INSTALLER DANS UN LOGEMENT.

MAX. MOUNTING ANGLE:

0 DEGREES

45 DEGREES

FOR STAINLESS STEEL UPGRADES THE 

COMBUSTION TUBE IS UPGRADED TO 409 

STAINLESS STEEL.

C1

10/11

HL2-40-125N

125,000/95,000

SA

MP

LE

MODEL /MODELE NO.

INPUT BTU/H

FOR USE WITH

NATURAL GAS

RADIATEUR A INFRAROUGE A FAIBLE INTENSITE

VOLTS A.C.

STARTING AMPS.

RUNNING AMPS.

120~60Hz

4.8

1.1

MANIFOLD PRESSURE

MIN. INLET PRESSURE

ORIFICE SIZE

3.5” WC

5.0” WC

#3 D.M.S

HEATER TYPE

VERSION

MIN. MOUNTING ANGLE:

COMBUSTION CHAMBER:

4” BC ALUMINUM

FOR INDOOR USE

BRANT RADIANT HEATERS LIMITED
34 SCOTT AVE., PARIS, ONTARIO
TEL: 1-519-442-7823 WWW.BRANTRADIANT.COM

ANSI Z83.20b - 2011 CSA 2.32b - 2011 Low - Intensity Infrared Htr. 
ANS Z83.20b - 2011 CSA - 2011 Low - Intensity Infrared Htr.

SERIAL NO. 

0870 XXXX XXXX 0001

RE-VERBER-RAY LOW INTENSITY INFRARED HEATER

FOR INDOOR INSTALLATION ONLY. NOT FOR USE IN RESIDENTIAL DWELLING.

INSTALLATION À L’EXTÉRIEUR SEULEMENT. NE PAS INSTALLER DANS UN LOGEMENT.

MAX. MOUNTING ANGLE:

0 DEGREES

45 DEGREES

FOR STAINLESS STEEL UPGRADES THE 

COMBUSTION TUBE IS UPGRADED TO 409 

STAINLESS STEEL.

C1

10/11

HL2-40-125N

125,000/95,000

Air Metering Orifice

DO NOT REMOVE

TP-114

TP-3014

1 - 1/2"

Safety Labels and Their Locations

Back Panel

Top Panel

Bottom Panel

Rating 
Plate

Tube Safety Label 

F/N:  LLTCL001

F/N: LLLOGO1

Product safety signs or labels should be replaced by the product user when they no longer are legible.  
Contact either your local distributor or the product manufacturer for obtaining replacement signs or labels.

F/N: LLAC 
Air Metering Orifice

SAMPLE

Air Metering Orifice

Air Metering Orifice

T REM

T REMOV

OVE

E

TP-114

TP-114

TP-3014

TP-3014

SAMPLE

LLTCL001-1M-8/13 (CDS)

!

!

!

CAUTION

DANGER

WARNING

Improper installation, adjustment, alteration,service 

or maintenance can cause property damage, injury 

or death.

This is 

NOT

 an explosion-proof heater.  Where there is the 

possibility of exposure to flammable vapors or dusts, consult 

the local fire marshall, your insurance carrier or authorities for 

approval of the proposed installation.  Do 

NOT

 install in 

residential or explosive environments.
This heater must be installed and serviced by trained gas 

installation and service personnel only.  The installation of this 

heater must conform with local building codes or, in the 

absence of such codes, the National Fuel Gas Code (NFPA 

54).

GAS CONNECTION

Allowances must be made for the system to expand.  A 

flexible gas connection of approved type is required. The 

connector shall be of Type 1 hose per Exhibit “A” Section B.4., 

and Figure 1 and 2.  Consult manual for further instructions.

Read and understand the installation, operating 

and maintenance instructions thoroughly before 

installing or servicing this equipment.

Des installation réglage, modification, maintenance 

ou entretien inappropriés peuvent causer des 

dommages matériels, des blessures ou la mort. 

Ceci n’est PAS un radiateur antidéflagrant. En présence possible de 

vapeurs ou de poussières inflammables, consulter le commissaire 

des incendies local, votre compagnie d’assurance ou les autorités 

compétentes pour l’approbation de l’installation projetée. NE 

CONVIENT PAS aux applications résidentielles ou à tout 

environnement sujet à explosion. 

Ce radiateur à gaz ne doit être installé et entretenu que par du

personnel formé et qualifié à cette fin. L’installation de ce radiateur 

doit être conforme aux codes locaux du bâtiment ou, en l’absence 

de tels codes, du National Fuel Gas Code (NFPA 54)

RACCORDEMENT AU GAZ

Prévoir du jeu pour la dilatation du système. Un raccordement par

tube flexible approuvé pour le gaz est nécessaire. Le raccord 

flexible devra être de type 1 tel qu’indiqué au schéma  ‘A’, section 

B.4., et aux figures 1 et 2 Se référer au manuel pour plus 

d’information.  

Lire et comprendre les directives d’installation, de 

fonctionnement et d’entretien avant d’installer ou 

d’entretenir cet équipement.

!

WARNING. 

To ensure system performance and 

safety, this unit must be properly vented.

Improper installation, adjustment, alteration, service or 

maintenance can cause property damage, injury or 

death.
Des installation, réglage, modification,maintenance ou 

entretien inappropriés peuvent causer des dommages 

matériels, des blessures ou la mort.

This heater can be installed in various configurations as specified in the 

manual.  

AIRCRAFT HANGARS. 

This heater must be installed in accordance 

with the latest edition of the Standard for Aircraft Hangars, ANSI/NFPA 

409.

PUBLIC GARAGES. 

This heater must be installed in accordance with 

the latest edition of the Standard for Parking Structures, ANSI/NFPA 

88A, or the Code for Repair Garages, ANSI/NFPA 30A or the Canadian 

Natural Gas and Propane Installation Code, CSA B149.1. as per 

Clause 1.1.4.

VENTING.

 This heater’s venting system must comply with the following 

requirements:

• 

Do not exceed 20 feet vent length or place more than two (2) 90°    

  elbows in the venting system.

•  Use 4-DSK Vent Kit for single sidewall venting;  

•  Common vented models (with Y-fitting) must be wired on the same  

  control.

•  A minimum ventilation rate of 4.0 cfm/1000

  Btu/H is required for unvented operation.

Ce radiateur peut être installé dans différentes configurations tel que 

spécifié dans le manuel. 

HANGARS À AVIONS. 

Ce radiateur doit être installé en conformité avec 

a dernière édition de la norme Standard for Aircraft Hangars, ANSI/NFPA 

409.

GARAGES PUBLICS.

 Ce radiateur doit être installé en conformité avec 

la dernière édition de la norme Standard for Parking Structures, 

ANSI/NFPA 88, ou du Code for Repair Garages, ANSI/NFPA 30A ou, au 

Canada, du Code d’installation du gaz naturel et du propane, 

CSA B149.1., article 1.1.4.

ÉVACUATION.

 Le système d’évacuation de ce radiateur doit

satisfaire aux exigences suivantes: 

•   Ne pas dépasser 20 pi en longueur de conduit ou utiliser plus de 2 

    coudes à 90° dans le système d’évacuation.

•   Utilisez l’ensemble d’évacuation RTVP-4 pour une évacuation murale 

    unique. 

•   Les modèles avec évacuation commne (avec raccord en Y ) doivent 

    être reliés à une même commande.

•   Un taux de ventilation minimal de 4 pcm/1000 Btu/H est nécessaire 

    pour un fonctionnement sans système d’évacuation

AVERTISSEMENT.

 Pour assurer le rendement et le 

fonctionnement sécuritaire du système, cet appareil 

doit être ventilé de façon appropriée.

65,000* - 75,000*

W/1 side shield

W/2 side shields

20 ft. from burner

50,000* - 60,000*

W/1 side shield

W/2 side shields

20 ft. from burner

105,000* - 125,000*

W/1 side shield

W/2 side shields

20 ft. from burner

80,000* - 100,000*

W/1 side shield

W/2 side shields

20 ft. from burner

155,000* - 175,000*

W/1 side shield

W/2 side shields

20 ft. from burner

130,000* - 150,000*

W/1 side shield

W/2 side shields

20 ft. from burner

180,000* - 200,000*

W/1 side shield

W/2 side shields

20 ft. from burner

45º

45º

45º

45º

45º

45º

45º

152.4

152.4

152.4

152.4

76.2

119.4

119.4

119.4

119.4

76.2

193

193

193

193

76.2

167.6

167.6

167.6

.167.6

76.2

233.7

233.7

233.7

233.7

111.8

205.7

205.7

205.7

205.7

111.8

238.8

238.8

238.8

238.8

111.8

CLEARANCE TO COMBUSTIBLES 

FIRE HAZARD

. Always maintain published clearance to combustibles.  In locations 

used for the storage of combustible materials, signs must be posted. Consult manual 

for additional guidelines.

MODEL 

BTU/h RANGE

MOUNTING 

ANGLE

FRONT

SIDE

BEHIND

TOP

BELOW

SIDE

SIDE

TOP

BELOW

0° MOUNTING ANGLE

FRONT

BEHIND

BELOW

45° MOUNTING ANGLE

TOP

BELOW

BEHIND

FRONT

0° W/1 SIDE SHIELD

TOP

SIDE

SIDE

BELOW

0° W/2 SIDE SHIELDS

TOP

IMPORTANT:

.

 *Use high BTU output when determining clearances.  Minimum end clearance for all models 

is 12 inches.  Maximum mounting angle is 45°.  Keep cover in place. 

22.9

99.1

73.7

22.9

17.8

22.9

99.1

73.7

22.9

17.8

50.8

147.3

106.7

50.8

17.8

35.6

99.1

73.7

40.6

17.8

86.4

160

127

76.2

27.9

61

147.3

106.7

58.4

27.9

104.1

160

137.2

76.2

27.9

cm

in.

9

39

29

9

7

9

39

29

9

7

14

39

29

16

7

20

58

42

20

7

24

11

23

42

58

30

50

63

34

63

41

11

11

30

54

22.9

20.3

20.3

22.9

17.8

22.9

20.3

20.3

22.9

17.8

50.8

20.3

20.3

50.8

17.8

35.6

20.3

20.3

40.6

17.8

86.4

20.3

20.3

76.2

27.9

61

20.3

20.3

58.4

27.9

104.1

20.3

20.3

76.2

27.9

cm

in.

9

9

8

8

9

7

8

8

8

14

7

9

23

8

8

24

7

20

8

8

20

7

16

8

11

30

8

8

34

11

8

8

41

11

30

15.2

25.4

15.2

15.2

15.2

15.2

25.4

15.2

15.2

15.2

15.2

25.4

15.2

15.2

15.2

15.2

25.4

15.2

15.2

15.2

15.2

25.4

15.2

15.2

15.2

15.2

25.4

15.2

15.2

15.2

15.2

25.4

15.2

15.2

15.2

cm

in.

6

10

6

6

6

6

10

6

6

6

6

6

6

10

6

6

6

6

6

10

6

6

6

6

10

6

6

6

10

6

6

6

6

10

6

cm

in.

47

47

30

47

47

60

30

60

60

60

76

76

30

30

66

66

76

66

66

76

44

81

81

81

81

92

92

44

44

94

92

92

94

94

94

RISQUE D’INCENDIE. 

Toujours respecter les dégagements prescrits de tout matériau 

combustible. Dans les endroits servant au stockage de matériaux combustibles, des 

écriteaux doivent en avertir. Se référer au manuel pour des directives supplémentaires. 

*IMPORTANT: 

Déterminer les dégagements en fonction de la capacité nette de Btu maximale. Le dégage-

ment minimal à l’extrémité est de 12 po pour tous les modèles. L’angle d’inclinaison maximal est de 45°. 

Garder le couvercle en place. 

 

(cm & in.)

1.0

 Introduction 

 Safety Signs and Labels 

Summary of Contents for HL2 Series

Page 1: ...d clearances from the heater to the combustibles Signs must either be posted adjacent to the heater thermostats or in the absence of such thermostats in a conspicuous location Not for residential use...

Page 2: ......

Page 3: ...on 21 Burner Control Box Suspension 23 Reflector Assembly 24 Baffle Assembly and Placement 26 Final Heater Assembly 27 Venting 28 Combustion Air Requirements 35 Separated Combustion Systems 36 Combust...

Page 4: ...f the tube heater You must read and understand the instructions and safety warnings in this manual before installing the tube heater Additional literature on this and other products is available at ww...

Page 5: ...N or LP 125 000 95 000 40 11 22 8 190 235 13 to 23 Alum Alum 40 5 4 HL2 40 150 N or LP 150 000 100 000 40 11 22 8 190 235 14 to 25 Titan Alum 40 5 4 HL2 40 175 N or LP 175 000 125 000 40 11 22 8 190...

Page 6: ...Infrared Htr SERIAL NO 0870 XXXX XXXX 0001 RE VERBER RAY LOW INTENSITY INFRARED HEATER FOR INDOOR INSTALLATION ONLY NOT FOR USE IN RESIDENTIAL DWELLING INSTALLATION L EXT RIEUR SEULEMENT NE PAS INSTAL...

Page 7: ...rect LED STATUS FAULT One flash on Normal opertion 120V pwr up No flash on 24 volt transformer 120V pwr up Steady on Module 1 Flash Ignition 2 Flash Burner Ignition 3 Flash Exhaust Switch 4 Flash Gas...

Page 8: ...hly before installing or servicing this equipment Only trained qualified gas installation and service personnel may install or service this equipment Applications This is not an explosion proof heater...

Page 9: ...eas heaters shall be installed at least 10 ft 3 m from above the upper surface of wings or of the engine enclosures of the highest aircraft that may be housed in the hangar The measurement shall be ma...

Page 10: ...Guidelines Chart 2 2 Standards and Code Installation Guidelines Building Location Installation of this tube heater is approved without modifications for elevations up to 6 000 feet 1 829 m MSL sea le...

Page 11: ...Marshall fire insurance carrier or other qualified authorities on the installation of gas fired tube heaters for approval of the proposed installation Safety Signs and Labels It is important to provi...

Page 12: ...60 152 20 ft from burner 0 7 18 7 18 6 15 30 76 HL2 20 30 40 80 100 N P 0 14 35 14 35 6 15 66 168 45 39 99 8 20 10 25 66 168 with 1 side shield 0 29 74 8 20 6 15 66 168 with 2 side shields 0 16 41 16...

Page 13: ...When designing an infrared radiant heating system consider the following Has the building s heat loss been evaluated Does the design meet the needs of the space Have recommended mounting heights been...

Page 14: ...rved see Chart 3 1 Produces an uneven heat distribution Four burners 100 000 BTU each are placed in each corner Burner hotter ends direct heat to areas of highest heat demand Recommended mounting heig...

Page 15: ...imension A Distance Between Heater Rows ft Dimension B Maximum Distance Between Heaters and wall ft Dimension C Figure 3 3 Mounting Height Dimensions see Chart 3 1 for dimensions Dimension A Dimension...

Page 16: ...amber as the first tube downstream of the burner control box 2 Mark locations for hanging points NOTE If the available hanging points do not allow for the recommended spacing then additional hangers P...

Page 17: ...n chamber s is located in the middle of the tube models 150 200 MBH Remove paper band before starting up heater Stainless Steel Tube Clamp 150 200 MBH models only Refer to page 22 for U bend configura...

Page 18: ...it is securely attached NOTE Threaded rod and turnbuckles may be used 6 Attach hangers to chains Adjust chain lengths until radiant tubing is level and equal weight distribution is achieved Chains mus...

Page 19: ...45 degree angle with two suspension points using two Brass Knuckle P N BK fittings 1 double loop chains and S hooks U Tubes can be mounted from a single suspension point using a Single Mounting Brack...

Page 20: ...entification tag 2 Slide tube clamps onto radiant tubes see figure 3 9 Figure 3 8 Attach Hangers Figure 3 9 Attach Tube Clamps Hanger Welded seam faces down Swaged End Tube Clamp Radiant Tube IMPORTAN...

Page 21: ...towards exhaust end NOTE If it is difficult to mate the tubes they may be installed incorrectly 4 Center tube clamps over the seam where two radiant tube sections connect If necessary rotate tube cla...

Page 22: ...bow can be set in both directions Tube Clamp Tube Clamp Dimension A Dimension B P N TF1B 4 P N E6 4 8 Model Tube Length Dimension B Notes 20 ft 13 0 156 N A 30 ft 17 8 212 Requires P N 5EA SUB 40 ft 2...

Page 23: ...clamp screw hook or other type of suspension anchor to hanging point 3 Attach S hook and 1 double loop chain P N THCS to anchor Check that it is securely connected 4 Attach chain assemblies and S hook...

Page 24: ...1 4 VACUATION e syst me d vacuation de ce radiateur doit satisfaire aux exigences suivantes Ne pas d passer 2 pi en longueur de conduit ou utiliser plus de 2 coudes dans le syst me d vacuation tilise...

Page 25: ...U shaped reflector P N RU Used over a U bend accessory fitting 3 0 Installation Reflector Assembly Elbow Reflector 90 bend highly polished aluminum reflector elbow RE designed to fit atop one elbow ac...

Page 26: ...e tabs to the center of the keyhole and rotate the baffle 90 degrees to lock the baffle sections together 5 Repeat this process with all remaining baffle sections to complete assembly Figure 3 19 Asse...

Page 27: ...t Do not use tube clamp 20 Foot Final Heater Assembly 50 Foot 60 Foot 70 Foot Stainless steel clamp on 150 000 to 200 000 BTU h models P N TP 220 Stainless steel clamp on 150 000 to 200 000 BTU h mode...

Page 28: ...nized steel of a thickness that meets the National Fuel Gas Code Minimum thickness for connectors varies depending on the pipe diameter Never vent the HL2 Series with PVC or plastic pipe Gas fired hea...

Page 29: ...e materials For double wall vent pipe type B follow the vent manufacturer s clearance to combustibles The equivalent length for a 4 inch 90 elbow is 5 feet Avoid using more than two 90 directional cha...

Page 30: ...diameter 4 inches greater than the vent pipe diameter must be used If there is 6 feet or more of vent pipe prior to passing through the combustible wall or floor then the metal thimble need only be 2...

Page 31: ...nting is venting at a non positive pressure An appliance vented as a Category I is considered a fan assisted appliance and the vent system does not have to be gas tight It is recommended that the vent...

Page 32: ...ion of the vent run exceeds 75 of the vertical rise length e g If the vertical vent height is 10 feet the horizontal run is greater than 7 1 2 feet The vent terminates below 5 feet of the vent connect...

Page 33: ...ate a minimum of 7 feet above grade level The vent terminal must be installed to prevent blockage by snow and protect building materials from degradation by flue gasses The vent cap must be a minimum...

Page 34: ...ould be minimized Each elbow installed within the common portion of the vent carrying system reduces the maximum common vent capacity by 10 Refer to NFPA 54 IFEC tables 11 2 and 11 3 for capacity The...

Page 35: ...tight construction where the air infiltration rate is less than 0 40 air changes per hour If your application does not meet any of these criteria then room air may be used as supplying combustion air...

Page 36: ...ealant Wrap the tape two full turns around the vent pipe Slope air intake pipe inch per foot upward or downward away from the unit Flexible boot with band clamps recommended at heater s air inlet coll...

Page 37: ...t the factory for further determination of air infiltration rates Figure 3 26 Outside Combustion Air Vertical Intake Side View Roof Listed Exhaust Cap 18 in Min Combustion Air Intake Cap Burner Contro...

Page 38: ...ut of installed heaters NOTE Gravity or mechanical means may be used to accomplish the air displacement Local codes may require that the mechanical exhaust system be interlocked with the electrical su...

Page 39: ...d local codes along with guidelines in this manual In the United States refer to the latest edition of the ANSI Z223 1 NFPA54 Standard and in Canada refer to the latest edition of the CAN CGA B149 1 S...

Page 40: ...e to a new pipe Test all gas supply lines in accordance with local codes To connect the gas The HL2 Series heater is equipped to connect to the Type 1 rubber gas connector Included Do not connect the...

Page 41: ...onnection device that allows for the heater expansion must be used The gas outlet must be in the same room as the appliance is installed and must be accessible It may not be concealed within or run th...

Page 42: ...osion and cause serious injury or death Test in accordance with NFPA or local codes 9 14 23cm 36cm Gas Supply Gas Supply 9 23cm 9 23cm Gas Supply Gas Supply 3 4 Gas Connection Refer to Installation Ma...

Page 43: ...ed 14 Inches W C to the appliance Ball Valve Inlet Tap 7 14 Type 1 Hose Gas Connector formed into a U bend Adapter Drip Leg Sediment Trap Heater Movement Elbow Burner Control Box Side View Adapter Elb...

Page 44: ...e pressure NOTE All factory installed gas connections have passed an approved leak test For leak testing on pressures above 1 2 PSI When leak testing with pressures above 1 2 PSI 14 inches W C the uni...

Page 45: ...residential indoor spaces may result in property damage serious injury or death 120 Volt 60 Hz GRD 3 wire 24V thermostat connection Starting current 4 8 amps Running current 1 1 amps Electrical Requir...

Page 46: ...d with the suffix D on the heater s rating plate A yellow control wire replaces the external terminal plug on stainless steel models or models with water resistant upgrades NOTICE Connecting the therm...

Page 47: ...ntrol Box BURNER BOX observe polarity 120 Volt Power L1 N PANEL GROUND Additional wire needed on thermostats requiring constant power 24VAC High Low N NOTE If optional yellow control cord is installed...

Page 48: ...ELD SUPPLIED G G BK BK W BLOWER BL IGNITOR FLAME ROD TRANSFORMER PRESSURE SWITCH STATUS LIGHT MICRO 60U 24 BK BK BK W W PK PK APS1 NO G BL Y BK R W W BK IGNITION MODULE G G G G BK BL R GY GAS VALVE G...

Page 49: ...LD SUPPLIED STATUS LIGHT L1 N 120VAC T STAT TERMINAL MICRO 60U 24 IGNITION MODULE BLOWER PRESSURE SWITCH FIELD SUPPLIED LIGHT STATUS W R GY G TRANSFORMER W BK IGNITOR BK GAS VALVE R BK PK PK APS N O O...

Page 50: ...unit is properly grounded as per the National Electrical Code ANSI NFPA 70 or Canadian Electrical code CSA C22 1 Part 1 9 The unit is properly mounted to a permanent structure able to bear the weight...

Page 51: ...ned gas installation and service personnel only Failure to comply could result in personal injury asphyxiation death and fire or property damage Prior to leaving the Job Site Prior to leaving the job...

Page 52: ...to smell next to the floor because some gas is heavier than air and will settle to the floor Refer to page 1 If you smell gas and on safety label affixed to the heater Do not use this appliance if an...

Page 53: ...one second and a new trial sequence identical to the starting sequence is initiated If flame sense is not established within 8 5 seconds the heater will attempt two 2 additional ignition sequences bef...

Page 54: ...ttempt to light three times In the event of a failed attempt to light gas pressure valve no flame sense etc the heater will enter a soft lockout period for 30 minutes and then attempt to light three m...

Page 55: ...55 HL2 Series This page was intentionally left blank...

Page 56: ...the secondary side of the external transformer Is there 24V to the thermostat Yes Yes No Yes No No Yes Yes No Is the power across the left terminal of the 24V plug and ground screw on the burner cont...

Page 57: ...ntrol Box 24 Volts Repair thermostat or wiring from thermostat to heater Is there 24V across the TH and ground terminals on the circuit board Correct wiring Is the circuit board sending 120V to the fa...

Page 58: ...then shut off Does the burner come on and turn off immediately 1 or 2 seconds Check to make sure gas pressure is within minimum and maximum inputs as indicated on heater s rating plate Is gas pressur...

Page 59: ...re 24V across the GROUND and HIGH HIGH to COM on heaters with optional HLRB relay on the terminal strip located on the outside of the control box Repair or replace faulty wiring or thermostat Replace...

Page 60: ...er 1 500 hours of operation heavy duty Vent pipe system Check the outside termination and the connections at the heater Inspect the vent exhausts for leakage damage fatigue corrosion and obstructions...

Page 61: ...61 HL2 Series This page intentionally left blank...

Page 62: ...Box Cover TP 15 Sight Glass TP 68A Strain Relief Bushing TP 16 Sight Glass Washer TP 70 Control Box Cover Gasket per foot TP 17 Sight Glass Kit TP 76 Rubber Grommet TP 19B 4 Wire Hanger with Tension...

Page 63: ...ED Display Diagnostic Light TP 217 Pressure Switch Barb TP 828 Yellow Operational Indicator Light TP 218 Differential Switch Vinyl Sensing Tube exhaust TP 832 Thermostat Terminal Strip TP 219 Differen...

Page 64: ...d incidental damages is expressly disclaimed Brant Radiant Heaters Limited s liability in all events is limited to and shall not exceed the purchase price paid Warranty Disclaimer Brant Radiant Heater...

Page 65: ..._____________________________________________________________ ___________________________________________________________________________________ ______________________________________________________...

Page 66: ..._____________________________________________________________ ___________________________________________________________________________________ ______________________________________________________...

Page 67: ..._____________________________________________________________ ___________________________________________________________________________________ ______________________________________________________...

Page 68: ...une modification une r paration ou un entretien incorrect peut entra ner des dommages mat riel des blessures ou la mort lisez attentivement les instructions d installation de fonctionnement et d entr...

Reviews: