6. Set the DIP switches to meet system requirements.
Switch Label
Function
1
Non-HP / Heat Pump
Set to NON-HP for conventional equipment. Set to HEAT PUMP for
heat pump equipment.
2
Normal / Dual Fuel
Heat pump 1st stage lockout when 2nd stage calls
3
Rev Valve B/O
O/B terminal active in heating (B position) or cooling (O position)
4
Fan Gas / Elec & HP
Fan controlled by HVAC system or panel
5
Opp Call 20 / 15
Opposite call answer time in minutes
6
Lockout None / Active
2nd stage lockout without 2 zones calling
7
Priority All / Zone 1
Changeover priority zone 1 or first call
8
G2 W/2-Zones / 2 Stages
2nd stage fan activation requires 2 zones or 2 stages
5
System Checkout
After the wiring and configuration is complete, use the following checklist to verify the panel operation
is correct.
[ ]
Make sure the Emergency Heat Switch is in the Off (right) position.
[ ]
Open jumper J2 by moving cap from both pins to only one pin.
[ ]
Use table and diagram in section 4 of this installer guide or inside the zone panel cover to
verify DIP switches are set properly.
[ ]
Make sure the supply temp sensor is wired to terminals SA1 and SA2. The zone dampers
will not close if the supply sensor is missing.
[ ]
Make sure no zones are calling by turning off all thermostats.
[ ]
Apply 24 VAC power to the panel.
HEAT PUMP
DUAL FUEL
O
ELEC/HP
15
ACTIVE
ZONE1
2-STAGES
NON HP
NORMAL
REV VALVE B
FAN GAS
OPP CALL 20
LOCKOUT NONE
PRIORITY ALL
G2 W/2-ZONES