Installation 

S19-324D1

Bradley • 

215-1848 Rev. G: ECO 20-05-028 

6/11/2020

1 Install the Flow Switch and Mount Signaling Assembly

The flow switch will attach to the mounted alarm via a 6, 12 or 50 foot waterproof cable. 
Keep the location for mounting the alarm in mind when choosing the flow switch location.

A

Choose a location for mounting the 
flow switch in a horizontal run of the 
water supply line.

B

Mount the flow switch assembly in 
the water supply line.
•  The switch body must be in the 

vertical position with the water 
pipe horizontal.

•  The water flow must be in the 

direction marked by the arrow on 
the flow switch body.

•  Use teflon tape or pipe sealant 

(supplied by installer) on all water 
pipe connections.

C

Choose a location for mounting the 
alarm. For best visibility, the signaling 
system should be mounted at least 7' 
above ground level.
•  The signaling system may be 

mounted directly to the drench 
shower piping using the supplied 
U-bolts and nuts.

•  The signaling system can also be 

bolted to a flat surface such as 
a wall (hardware for this type of 
installation is NOT supplied).

NOTICE!  If the water supply line will be exposed to 

temperatures at or below freezing, the inlet supply 

must be freeze-protected 6 inches above the flow 

switch tee (freeze protection by others).

16" (406mm)

min. ceiling

clearance

To 1" Water 

Supply

Flow Switch

1¼" to 1" 

Reducing 

Bushing 

required

Piping supplied by 

installer (must be 

minimum 6 inches 

from any fittings)

Flow Switch 

optional location

(recommended 

location for brass 

flow switch is 

inside of wall)

To 1¼" Water 

Supply

Recommended Location 

for Flow Switch

Piping supplied 

by installer 

(must be 

minimum 6 

inches from any 

fittings)

Flow Switch

Clearances Needed

1/2" Piping 

supplied by 

installer (must be a 

minimum 3 inches 

from any fittings)

If multi-tone horn option is selected, it must be mounted 
separately following horn manufacturer's instructions. 
Mounting hardware is supplied by installer.

Summary of Contents for S19-324D1

Page 1: ...n Proof Emergency Signaling System Table of Contents Pre Installation Information 2 3 Assembly of Components 4 Install the Flow Switch and Mount Signaling Assembly 5 Connect Signaling Assembly to Flow...

Page 2: ...eginning installation and after installation is complete Test the unit for leaks and adequate water flow Main water supply should be ON at all times unless system is being serviced Provisions shall be...

Page 3: ...require a minimum of 30 PSI 0 21MPa flowing pressure Weekly activation must be conducted on all plumbed emergency equipment to ensure a suitable flushing fluid supply is present and any sediment buil...

Page 4: ...Sensor Body Brass Adapter and Tee 2 7 8 73mm 1 5 8 41mm NEMA 4X Junction Box and Cover Electrical Quick Disconnect Male 3 13 16 97mm 5 5 16 135mm Red Blue Black Remote Sensing 13 1 8 334mm System is...

Page 5: ...m may be mounted directly to the drench shower piping using the supplied U bolts and nuts The signaling system can also be bolted to a flat surface such as a wall hardware for this type of installatio...

Page 6: ...clockwise and sealing the control box The cable may be cut to any length required A Wire the flow switch to the control box with one of the provided cables and conduit hubs supplied per the wiring sch...

Page 7: ...ill automatically reset the silence feature The signaling system is designed to work properly even if both the eyewash and drench shower are used simultaneously The signaling system will continue to o...

Page 8: ...that water flow is sufficient 2 4 gallons per minute is required Installation error Check all electrical connections including power supply at the quick connect cable from the signal station to the fl...

Page 9: ...9 324D1 Bradley 215 1848 Rev G ECO 20 05 028 6 11 2020 S19 324D1 Service Parts 30 32 31 32 33 34 37 34 38 76 84 62 34 33 34 20 38 77 63 61 41 43 32 33 34 39 36 34 37 34 36 33 34 2 1 60 64 65 38 84 36...

Page 10: ...Surface Mount 60 140 1157 1 Plate PM Pipe Mount 60 S70 176 1 Mounting Plate Heat Trace Item Part No Qty Description 61 160 514 5 Screw 3 8 16 x 1 0 BTNCA 62 161 157 5 Nut 3 8 16 Hex Jam 63 140 1158 1...

Reviews: