background image

Installation 

P.O. Box 309

Menomonee Falls, WI 53052 USA

800 BRADLEY (800 272 3539)

+1 262 251 6000

bradleycorp.com

215-1857 Rev. E: ECO 19-05-034B

© 2020 Bradley

Page 1 of 23 

4/9/2020

Heat Trace Combination Drench 

Shower and Eyewash Unit (includes 

120V and 208/240V versions)
Câble chauffant d’unité de douche 

d’urgence et de douche oculaire 

combinées (comprend les versions  

120 V et 208/240 V)

Unidad de combinación de ducha 

y lavaojos con cable calentador 

(incluye versiones de 120 V y 

208/240 V)

S19-304D2 

Top or Bottom Supply 

Class I, Division 2, Groups B, C and D
Canalisation supérieure ou inférieure Classe I, 

Division 2, Groupes B, C et D
Suministro superior o inferior  

Clase I, División 2, Grupos B, C y D

S19-304C2 

Top or Bottom Supply 

Class II, Division 1 and 2, 

Groups E, F and G
Canalisation supérieure ou inférieure 

Classe II, Divisions 1 et 2, Groupes E, 

F et G
Suministro superior o inferior  

Clase II, División 1 y 2, Grupos E, F y G

Read the instructions in this manual before beginning installation. Save these instructions and refer to 

them for inspection, maintenance, and troubleshooting information.

For questions regarding the operation, installation or maintenance of this product, visit bradleycorp.com or call 800.BRADLEY (800.272.3539).
Product warranties and parts information may also be found under “Resources” on our website at bradleycorp.com.

Lire les instructions du présent manuel avant de commencer l’installation. Sauvegarder ces instructions 

et s’y reporter pour obtenir des renseignements relatifs à l’inspection, à l’entretien et au dépannage.

Lea las instrucciones de este manual antes de comenzar la instalación. Guarde estas instrucciones y 

consúltelas para obtener información sobre la inspección, el mantenimiento y la solución de problemas.

Pour toute question concernant le fonctionnement ou l’installation de ce produit, consulter le site  

www.bradleycorp.com ou appeler le 1-800-BRADLEY.
Les garanties de produits figurent sous la rubrique « Resources » (Ressources) sur notre site Internet à www.bradleycorp.com.

Para consultas sobre la operación o instalación de este producto, visite www.bradleycorp.com o llame al 1-800-BRADLEY.
Las garantías del producto se pueden encontrar en “Resources” (Recursos) de nuestro sitio Web, www.bradleycorp.com.

Summary of Contents for S19-304C2

Page 1: ...refer to them for inspection maintenance and troubleshooting information For questions regarding the operation installation or maintenance of this product visit bradleycorp com or call 800 BRADLEY 800...

Page 2: ...ents de s curit 10 Composants 11 Fournitures requises 11 Dimensions 12 Fixer l unit au sol 13 Raccorder l alimentation en eau 13 Asembler les composants 13 Raccorder l alimentation lectrique 14 Joints...

Page 3: ...of 30 psi flowing pressure in order to function as designed and meet the ANSI ISEA Z358 1 standard Self closing spring loaded valves are not UL classified to ANSI ISEA Z358 1 Before installation make...

Page 4: ...w 10 24 x 1 2 qty 2 Pull Rod 128 156A 128 157 316 SS Stainless Steel Showerhead Plastic Showerhead Heat Trace Unit S19 304T top supply S19 304B bottom supply Optional Shower Shroud and Retaining Nut O...

Page 5: ...PT 9 229mm Flange with 3 3 8 10mm Holes on a 8 203mm Bolt Circle 58 9 16 1488mm 90 1 2 2299mm 85 7 8 2181mm 65 5 8 1666mm 15 3 8 391mm 34 5 16 872mm 23 1 8 587mm 9 5 8 245mm 4 3 8 111mm 6 152mm 90 3 8...

Page 6: ...4 supplied by installer NOTICE In extreme cold weather run water long enough to warm non freeze protected components of the unit to allow proper drainage Assemble Components 3 A Install the showerhead...

Page 7: ...xtension cable is pre powered through the system Average power consumption of the unit is 0 7 amp 80 watts at 120 VAC 0 40 amp 80 watts at 208 VAC or 0 35 amp 80 watts at 240 VAC at 50 F 10 C internal...

Page 8: ...8 4 9 2020 Bradley 215 1857 Rev E ECO 19 05 034B S19 304D2 S19 304C2 Installation Wiring Diagrams S19 304C1D2 C2 Without Options S19 304C1D2 C2 With Options...

Page 9: ...d replace if check fails activates at 50 F 10 C factory set Defective freeze valve if the water temperature from the valve is above 40 F 4 C Replace the freeze valve NOTE A water supply that is at lea...

Page 10: ...ion d coulement d au moins 30 lb po2 pour fonctionner tel que calcul et se conformer la norme ANSI ISEA Z358 1 Les soupapes ressort fermeture automatique ne sont pas classifi es UL selon ANSI ISEA Z35...

Page 11: ...ESES GER T 1ST W CHENTLICH ZU PR FEN ESSAI HEBDOMADAIRE Test le fonctionnement des valves chaque semaine et signe en bas S il y quelque chose qui ne va pas fait un rapport imm diatement Composants AVI...

Page 12: ...8 po sur une circonf rence de boulon de 203mm 8 po 1488mm 58 9 16 po 2299mm 90 1 2 po 2181mm 85 7 8 po 1666mm 65 5 8 po 391mm 15 3 8 po 872mm 34 5 16 po 587mm 23 1 8 po 245mm 9 5 8 po 111mm 4 3 8 po...

Page 13: ...du tuyau ne doit pas tre inf rieure 1 1 4 po fourni par l installateur AVIS Par temps tr s froid laisser couler l eau suffisamment pour r chauffer les composants de l unit non prot g s contre le gel a...

Page 14: ...rallonge est pr aliment dans tout le syst me La consommation moyenne d lectricit de l unit est de 0 7 A 80 watts 120 V c a 0 4 A 80 watts 208 V c a ou 0 35 A 80 watts 240 V c a une temp rature intern...

Page 15: ...MOIN INDICATEUR VIS DE MASSE SUR LA TIGE DE MONTAGE S19 304C1D2 et C2 avec options SP CIFICATIONS DU BORNIER Puissance d entr e Puissance de sortir Nombre de conducteurs par bornier Fil CU calibre AWG...

Page 16: ...ieure 4 C 40 F V rifier la continuit et le remplacer si la v rification choue activer 10 C 50 F r glage d usine Vanne antigel d fectueuse si la temp rature de l eau de la vanne est sup rieure 4 C 40 F...

Page 17: ...de flujo m nima de 2 1 bar 30 psi para que funcionen seg n fueron dise ados y cumplan con la norma ANSI ISEA Z358 1 Las v lvulas con funcionamiento a resorte de autocerrado no cuentan con clasificaci...

Page 18: ...ofort melden DIESES GER T 1ST W CHENTLICH ZU PR FEN ESSAI HEBDOMADAIRE Test le fonctionnement des valves chaque semaine et signe en bas S il y quelque chose qui ne va pas fait un rapport imm diatement...

Page 19: ...8 en un c rculo de orificios para pernos de 203 mm 8 1488 mm 58 9 16 2299 mm 90 1 2 2181 mm 85 7 8 1666 mm 65 5 8 391 mm 15 3 8 872 mm 34 5 16 587 mm 23 1 8 245 mm 9 5 8 111 mm 4 3 8 152 mm 6 2372 mm...

Page 20: ...tama o del tubo no debe ser menor que 1 1 4 proporcionado por el instalador AVISO En climas extremadamente fr os deje correr agua por el tiempo suficiente para calentar los componentes de la unidad q...

Page 21: ...ad El cable de extensi n viene alimentado previamente a trav s del sistema El consumo de energ a promedio de la unidad es de 0 7 A 80 W a 120 V CA 0 40 A 80 W a 208 V CA o 0 35 A 80 W a 240 V CA a una...

Page 22: ...DE EMPALMES VERDE ROJO NEGRO ROJO VERDE OPCI N DE SISTEMA DE SE ALIZACI N OPCI N DE LUZ INDICADORA TORNILLO DE CONEXI N A TIERRA EN EL V STAGO DE MONTAJE S19 304C1D2 y C2 con opciones ESPECIFICACIONE...

Page 23: ...50 F establecido en f brica V lvula contra congelamiento defectuosa si la temperatura del agua de la v lvula es superior a 4 C 40 F Sustituya la v lvula contra congelamiento NOTA Un suministro de agua...

Reviews: