background image

3

Installation 

S19-130SS

Bradley • 

215-292 Rev. F; ECN 12-05-016G 

11/12/2012

Installation

Supplies Required:

• 

Pipe sealant

• 

Piping to 1" NPT water supply inlet

• 

Adequate supply pipe supports

• 

Minimum 4" (102 mm) drain to 
accommodate 30 gallons (115 liters) per 
minute discharge for shower waste

• 

Sign-mounting hardware

Step 1: Assemble components

1.  Assemble components as shown on page 4.

• 

Apply pipe sealant (supplied by installer) 
to all male-threaded pipe joints.

• 

The bottom edge of the showerhead 
should be 84" (2134 mm) from the floor.

Step 2: Connect water supply

IMPORTANT!  Do not rely on Bradley’s Drench 

Shower to support supply piping.

1.  Connect water supply piping to 1" NPT inlet 

on unit (piping supplied by installer). Provide 
adequate supports (supplied by installer) 
for supply pipe using pipe hangers or other 
means.

2.  Mount the safety sign to the wall using sign-

mounting hardware supplied by installer.

9"

(229mm)

84"

(2134mm) 

Suggested 

Height to 

Floor

25-1/2"

(648mm)

6"

(152mm)

7-3/4"

(197mm)

Ø 1-1/2" 

(38mm)

 

All dimensions assume standard thread 
engagement. Variations in manufacturing allow 
for +/- 

¹⁄₈

” (3mm) per threaded joint. To find 

the tolerance of a dimension, add the number 
of thread joints in between a dimension and 
multiply it by 

¹⁄₈

” (3mm).

Reviews: