3
Installation
S19-110SS
Bradley Corporation •
215-145SS Rev. H; ECN 08-517
8/11/08
Installation
Supplies Required:
• (3) 3/8" floor anchors and bolts
• Pipe sealant
• Piping to 1-1/4" NPT water supply inlet on unit
• Adequate supply pipe supports
• Min. 4" drain to accommodate 30 gallons per minute
discharge for shower waste
• OPTIONAL: sign-mounting hardware
Step 1: Secure base to floor
1. Install three suitable anchors (supplied by installer)
for 3/8" bolts in the floor.
2. Bolt the base to the floor anchors using 3/8" bolts
(supplied by installer).
Step 2: Assemble components
1. Assemble the remaining unit components as
shown on page 4.
• Apply pipe sealant (by installer) to all male-
threaded pipe joints.
• Use the rubber grip pad provided or a strap
wrench around pipes when tightening to prevent
marring. Place the grip pad on the pipe, then
put the wrench over the grip pad and turn the
pipe with the wrench.
• Bottom edge of showerhead should be 7'-0"
(2134mm) from floor.
Step 3: Connect water supply
IMPORTANT: Do not rely on Bradley’s
Combination Unit to support supply piping.
1. Connect water supply piping to 1-1/4" NPT inlet
on unit (piping by installer). Provide adequate
supports (by installer) for supply pipe using pipe
hangers or other means.
2. Hang the safety sign from the unit with the curtain
hooks provided (or mount it to the wall using sign-
mounting hardware by installer).
3. Open water supply lines. Test for leaks and
adequate water flow.
NOTE: All dimensions assume standard thread
engagement. Variations in manufacturing allow for
+/- 1/8" (3mm) per threaded joint. To fi nd the tolerance
of a dimension, add the number of thread joints in
between a dimension and multiply it by 1/8" (3mm).
Ø
9" (229mm) Flange with
(3)
Ø
3/8" (10mm) Holes on
Ø
8" (203mm) Bolt Circle
9"
(229mm)
26-1/2"
(673mm)
7'-0"
(2134mm)
to Floor
24"
(610mm)
3.7"
(94mm)
41-1/2"
(1054mm)