background image

SS-3N/BIR3/STD, SS-3N/BIR3/WH 

Installation

12

 

9/7/2018

 Bradley 

• 215-1496 Rev. J; ECN 17-08-026

Troubleshooting  – BIR3 Components

Problem

Cause

Solution

An individual 

operating 

station fails 

to shut off 

and drips.

Debris is trapped between the 

diaphragm and the valve seat.

Remove debris between diaphragm and the valve seat.

1.  Disconnect the plug from the battery to the circuit board of the problem 

valve.

2.  Remove the three #8 Phillips-head screws that hold the solenoid valve 

assembly together. Be careful not to lose the armature or spring.

3.  Remove the diaphragm. Remove any particles that have been trapped 

between the diaphragm and the valve seat. Rinse off the diaphragm and 
inspect for damage. Make sure the center orifice and both small side orifices 
are open.

4.  Reassemble in reverse order (do not overtighten the Phillips-head screws 

or the plastic valve body may crack). Tighten until the armature plate makes 
contact with the plastic body.

5.  Reconnect the battery plug. Turn on water supplies to the unit.

An individual 

operating 

station fails 

to turn on or 

off.

A dead or faulty battery.

Test the station to determine the cause and replace battery if required.

1.  Disconnect the sensor cable from the circuit board of the problem valve. 

Disconnect the sensor cable from the circuit board of an adjacent working 
valve.

2.  Connect the battery plug from the adjacent working valve to the problem 

valve. Wait for ten seconds. Activate the problem station’s sensor ten times. 
The station should turn on.  

If the adjacent station turns on, and cycles normally, replace the battery.

Faulty sensor eyes.

Test the station to determine the cause and replace sensor eyes if required.

1.  Disconnect the plug from the battery to the circuit board of the problem 

valve. Disconnect the plug from the battery to the circuit board of an 
adjacent valve.

2.  Connect the sensor cable from the adjacent working valve to the problem 

valve. Activate the problem station’s sensor. The station should turn on.  

If the adjacent station turns on, and cycles normally, replace the sensor eyes.

Faulty solenoid valve.

Test the station to determine the cause and replace solenoid valve if required.

1.  Remove the screw, circuit board and standoff from the problem valve. 

Remove the battery holder.

2.  With a good working battery, briefly contact the solenoid valve directly 

with the battery. The contact should cause the valve to open. With the 
battery holder removed, briefly contact the solenoid valve with the battery 
in the position shown. This should cause the valve to close. If the valve 
does not operate when directly contacted with a good battery, and the 
solenoid valve has already been cleaned as outlined at the beginning of this 
troubleshooting section, replace the solenoid valve.

If problems persist:
Pass your hand in front of the problem station, while at the same time looking to 

see if the indicator light on the circuit board flashes (the indicator light is located 

near the hole in the circuit board where the standoff is mounted).  If it does not 

flash, and the battery and sensor eyes have already been tested as outlined above, 

the problem may be with the circuit board.  Make a note of the numbers printed on 

the circuit board, then contact your Bradley representative for assistance.

WARNING  Turn off water supplies to the unit before troubleshooting.

CLOSED

VALVE

OPEN

VALVE

Summary of Contents for Express SS-3N/BIR3/WH

Page 1: ...SD 3 SS 3N BIR3 WH LSD 3 Table of Contents Pre Installation Information 2 Components 3 Supplies Required 4 Dimensions Front and Top Views 4 5 Rough Ins 6 Mount the Frame 7 Install the Bowl 7 Connect the Supply Hot and Cold Supply 8 Connect the Supply Single Tempered Supply 8 Install the Drains 9 Connect Electrical and Sprayhead Supplies 9 Adjust the Temperature 10 Cleaning and Maintenance 11 Troub...

Page 2: ... water supply first then turn on the electrical power Installer s hardware must be appropriate for wall construction Wall anchors must have a minimum pull out rating of 1 000 pounds NOTICE Overtightening fasteners can damage the Terreon material Use caution when tightening bowl and sprayhead fasteners IMPORTANT Read this entire installation manual to ensure proper installation When finished with t...

Page 3: ...al Bradley Representative for part number LockWasher 142 002BK Nut 5 16 18 161 036 Scuff Base S17 324 Used with Standard Height Frame Only Scuff Panel Fasteners 160 450 Washers 142 002CA 4 Places Scuff Base Panel Coal 185 033B Panel Fasteners 160 450 Washers 142 002CA 8 Places Bolt 5 16 18 160 371 8 32 Screw 160 319 Strainer P16 075 Drain Plug P16 072 1 8 Rubber Washer 125 001DP Waste Shoe 111 062...

Page 4: ...00 lbs STD HEIGHT ONLY 2 3 8 wall anchors bolts and 1 min O D washers to mount scuff base to wall nominal copper tubing for hot and cold supplies and 1 NPT drain piping Dimensions Front and Top Views SOAP SOAP SOAP SOAP Top View 80 2032 Front View Standard Frame Front View Wall Hung Frame 8 5 8 219 30 762 8 203 51 1 4 1302 58 1473 64 1626 68 1 4 1734 8 203 68 1 4 1734 58 1473 64 1626 8 203 Radius ...

Page 5: ...ades 6 through 8 or 9 Wall Hung Mounted at TAS Height Grades Pre K through 5 or 6 21 1 8 537 38 1 2 978 34 864 30 762 13 1 4 311 11 1 2 292 Scuff Base on Standard Height Only 3 76 8 5 8 219 38 1 2 978 34 864 30 762 8 5 8 219 21 1 8 537 11 1 2 292 13 1 4 311 8 5 8 219 21 1 8 537 11 1 2 292 8 5 8 219 21 1 8 537 11 1 2 292 8 5 8 219 21 1 8 537 11 1 2 292 36 1 2 927 32 813 28 711 11 1 4 286 35 1 2 902...

Page 6: ... 2 F On the bowl back measure the distance between the bowl mounting holes Divide this measurement in half Measure and mark this dimension on the wall to the left and the right of the centerline Install two 3 8 wall anchors with a minimum pull out rating of 1 000 lbs supplied by installer at locations marked 2 RIM HEIGHT VERTICAL HEIGHT ADJUSTMENTS FOR CODES A E H C and W FIXTURE STYLE 34 None Sta...

Page 7: ...Height Frame Only Scuff Base Frame Standard Height Frame Only B Once you have positioned the frame such that it is level and flat against the wall or shimmed mount the frame to the wall at six places using 3 8 bolts and 1 min O D washers 3 Install the Bowl The sprayhead body has slotted holes for adjusting the fit up with the bowl and wall For clarity the scuff base frame and drain are not shown T...

Page 8: ...s A Loosen but do not remove the two mounting screws holding the valve bracket to the frame Slide the valve bracket up and lift it from the frame B Attach the stops to the hot and cold water wall stub outs C Connect one end of flexible hose to the tempered line adapter Connect the other swivel end to the stop valve 4b Connect the Supply Single Tempered Supply A Loosen but do not remove the two mou...

Page 9: ...eries into the battery holder If the cable is connected or disconnected while the batteries are installed the station will activate and continue running for 75 seconds Red Supply Tubing Green Supply Tubing Black Supply Tubing To Drain Stub Out 5 Install the Drains 6 Connect Electrical and Sprayhead Supplies B Insert the batteries into the battery holders D Loosen the compression nuts Push the spra...

Page 10: ...ust the Temperature A Loosen the cap screw about 4 6 turns and lift up the cover do not remove B Using the cover turn the cartridge gently until desired water temperature is reached Do not turn past stops as this may damage the unit Push the cover down and tighten the screw C Reinstall the valve bracket Turn on the water supply to the Express and check for leaks Push the operating buttons of each ...

Page 11: ... and work your way toward the more complicated Routine cleaning Daily or as often as needed use a solution of warm water and soap detergent or ammonia Apply the cleaning solution per the manufacturer s instructions and always use a soft cloth or sponge to avoid damaging the finish Stubborn Stains To remove stains from stainless steel use a stainless steel cleaner and polish such as Ball stainless ...

Page 12: ... Faulty sensor eyes Test the station to determine the cause and replace sensor eyes if required 1 Disconnect the plug from the battery to the circuit board of the problem valve Disconnect the plug from the battery to the circuit board of an adjacent valve 2 Connect the sensor cable from the adjacent working valve to the problem valve Activate the problem station s sensor The station should turn on...

Page 13: ...g 2 013 Solenoid Valve w Circuit Board Closed Body S07 082 Thru Body S07 082A Circuit Board S83 178 Pan Head Screw 6 19 x 160 451 Valve Assembly Closed Body S07 072 Thru Body S07 072A WARNING Turn off water supplies to the unit before troubleshooting Stop Valve Troubleshooting Problem Cause Solution Water dribbles or does not flow from the sprayhead Stop Valves may not be functioning properly 1 Cl...

Page 14: ...lean the strainer It is not required to grease cartridge however if desired use silicone grease only Do not use grease on check valves Parts List Item Part No Description Quantity S59 4000 1 160 463 Cap Screw 1 2 107 582 Cover 1 3 269 1927 Thermostatic Cartridge 1 4 198 014 Check Valve 2 5 132 051 Retaining Ring 2 6 118 319 Valve Body 1 7 146 079 U Clip 1 Included with Prepack S65 326 1 2 3 4 5 4 ...

Page 15: ...shroom cleaning routine and general maintenance program Clean exterior Use warm water and soap to clean the exterior of the soap dispenser Dry with a soft cloth Clean interior Inspect the interior of the tank for residue or coagulation of soap If necessary clean the tank according to the following procedure 1 Pour out any remaining soap in the tank 2 Full the tank half full of hot water and shake ...

Reviews: