Installation Instructions

TO fILL THe WATeR HeATeR

WARNINg:

 

Risk of Unit Damage - 

The 

tank must be full of water before heater is turned on. The 

water heater warranty does not cover damage or failure 

resulting from operation with an empty or partially 

empty tank.

Make certain the drain valve is completely closed. 
Open the shut-off valve in the cold water supply line.
Open each hot water faucet slowly to allow the air to 

vent from the water heater and piping. 
A steady flow of water from the hot water faucet(s) 

indicates a full water heater.

F11” fault code during installation: 

If the unit is 

powered on without a full tank, the error code “F11” will 

show in the display.  Turn off the power, fill the tank with 

water (see above), then turn the power back on.

Note: 

 the DRY TANK DETECTION feature on tank is for the 

aid of installer and should NOT be used as the primary 

control to prevent operation with an empty or partially 

filled tank.  Power should NEVER be applied to the water 

heater until installer has verified tank is filled and  all air 

has been purged from system.

NOTICe:

Do not mis-wire electrical connections. 240V AC or 208AC 

must be applied across L1 and L2 wires as shown in 

‘Water heater junction box’ illustration. Failure to do so 

will VOID the warranty, and can result in 120V applied to 

water heater, which may damage the compressor or other 

electrical components.

If 4-conductor wire is supplied to the water heater, cap the 

neutral, and connect the remaining wires as illustrated.
NOTE REGARDING UTILITY POWER-MANAGEMENT DEVICES 

(Sometimes called Peak Load Reduction Switches):
Some power-management switching devices or even some 

basic timer switches exist that  REDUCE voltage from 240V 

to 120V during high-electricity-demand periods.  These 

devices must be removed from the circuit providing power 

to the water heater because of the potential unit damage 

noted above.  
However, switching devices which cut power from 240V to 

0V on a periodic basis are acceptable.

“bAd linE” fault code during installation:

 If “bAd linE” is 

shown on the display, the unit is not receiving the correct 

voltage as a result of incorrect wiring.  To correct this fault, 

turn the power off to the unit, correct the wiring issue, then 

turn the power back on.

ReLIef VALVe

WARNINg:

 

Risk of Unit Damage - 

The 

pressure rating of the relief valve must not exceed 150 

PSI (1.03 kPa), the maximum working pressure of the 

water heater as marked on the rating plate

A new combination temperature and pressure-relief 

valve, complying with the Standard for Relief Valves and 

Automatic Gas Shut-Off Devices for Hot Water Supply 

Systems, ANSI Z21.22, is supplied and must remain installed 

in the opening provided and marked for the purpose on 

the water heater. No valve of any type should be installed 

between the relief valve and the tank. Local codes shall 

govern the installation of relief valves.
The BTUH rating of the relief valve must not be less than the 

input rating of the water heater as indicated on the rating 

label located on the front of the heater (1 watt=3.412 BTUH).
Connect the outlet of the relief valve to a suitable open drain 

so that the discharge water cannot contact live electrical 

parts or persons and to eliminate potential water damage. 

Piping used should be of a type approved for hot water 

distribution. The discharge line must be no smaller than the 

outlet of the valve and must pitch downward from the valve 

to allow complete drainage (by gravity) of the relief valve 

and discharge line. The end of the discharge line should 

not be threaded or concealed and should be protected 

from freezing. No valve of any type, restriction or reducer 

coupling should be installed in the discharge line.

CAUTION:

 

To reduce the risk of excessive pressures and 

temperatures in this water heater, install temperature 

and pressure protective equipment required by local 

codes and no less than a combination temperature and 

pressure relief valve certified by a nationally recognized 

testing laboratory that maintains periodic inspection of 

production of listed equipment or materials, as meeting 

the requirements for Relief Valves and Automatic Gas 

Shutoff Devices for Hot Water Supply Systems, ANSI 

Z21.22. This valve must be marked with a maximum set 

pressure not to exceed the marked maximum working 

pressure of the water heater. Install the valve into an 

opening provided and marked for this purpose in the 

water heater, and orient it or provide tubing so that 

any discharge from the valve exits only within 6 inches 

above, or at any distance below, the structural floor, and 

does not contact any live electrical part. The discharge 

opening must not be blocked or reduced in size under 

any circumstances.

Summary of Contents for RE2H50R10B-1NCWT

Page 1: ...___ Serial __________________ You can find them on the rating label on the front side of your water heater RE2H50R10B 1NCWT RE2H80R10B 1NCWT Owner s Manual Installation Instructions Chauffe eau r side...

Page 2: ...th from scalding Be sure to read and follow the warnings outlined on the label pictured below This label is also located on the water heater near the top of the tank Time Temperature Relationship in S...

Page 3: ...line or other flammable vapors and liquids in the vicinity of this or any other appliance Keep rags and other combustibles away FOR INSTALLATIONS IN THE STATE OF CALIFORNIA California Law requires tha...

Page 4: ...heater is equipped with a temperature limiting control TCO that is located above the heating element in contact with the tank surface If for any reason the water temperature becomes excessively high t...

Page 5: ...ode Selector Use this button to alternate between available modes Arrow Pads Use these buttons to adjust the temperature setting Enter Key Filter Reset The filter is dirty and requires cleaning when t...

Page 6: ...egulations the controls are factory preset to 120 F 49 C and Hybrid Mode It is recommended that the unit be set to Heat Pump only mode to maximize energy savings Operating in Hybrid mode provides a ba...

Page 7: ...bout 10 seconds 140 F 60 C Less than 5 seconds 145 F 63 C Less than 3 seconds 150 F 66 C About 1 1 2 seconds 155 F 68 C About 1 second Table courtesy of Shriners Burn Institute Risk of Scalding Remind...

Page 8: ...mode the green LED light will flash after 48 hours as an indication that the unti is not operating in the most energy efficient mode The unit will continue to operate in this mode and does not indica...

Page 9: ...air normally discharged during heat pump operation Q Why does the Electric Only green LED flash A In this mode the green LED light will flash after 48 hours as an indication that the unit is not oper...

Page 10: ...o a suitable drain to prevent injury or property damage NOTE If the temperature and pressure relief valve on the hot water heater discharges periodically this may be due to thermal expansion in a clos...

Page 11: ...and result in a reduction of efficiency and possible damage to the system In order to get the best energy efficiency available make sure your filter is clean The main drain is intended to carry all co...

Page 12: ...lift out to inspect as show in Illustration D 6 To install the anode rod seal the threads with soft set sealant thread into the port and using the torque wrench tighten to 50 5 ft lbs of torque Plug i...

Page 13: ...experience lower performance LOCATION Locate the water heater in a clean dry area as near as practical to the area of greatest heated water demand Long uninsulated hot water lines can waste energy and...

Page 14: ...air cushion built in that compresses as the system pressure increases thereby relieving the over pressure condition and eliminating the repeated operation of the relief valve Other methods of control...

Page 15: ...for suggested typical installation The HOT and COLD water connections are clearly marked and are NPT on all models When connecting to the inlet outlet ports the use of female NPT tapered thread fitti...

Page 16: ...lief Valve WARNING Risk of Unit Damage The pressure rating of the relief valve must not exceed 150 PSI 1 03 kPa the maximum working pressure of the water heater as marked on the rating plate A new com...

Page 17: ...tallation Instructions The manufacturer s warranty does not cover any damage or defect caused by installation attachment or use of any type of energy saving or other unapproved devices other than thos...

Page 18: ...T FOR NORMAL STARTUP In Hybrid mode After the unit has been installed with all electrical and water connections secure and checked then the unit should be filled with water vent tank by opening a hot...

Page 19: ...usage may have Wait for the water heater to recover after an abnormal exceeded the capacity demand of the water heater Ambient temperature is For the water heater to work properly its location needs t...

Page 20: ...leaning the filter may be an indication of a fan failure Contact service The heater is beeping There is an issue with the The unit will automatically switch to another available and the screen says he...

Page 21: ...his provides an early indication of a re frigerant leak Note Target superheat is generally 10 F and EEV generally operates at a position much lower than 450 Check sealed system for refrigerant leak Ch...

Page 22: ...mode F13 1 Stuck Key fault This indicates there is a button on the front panel that is stuck down This button is inoperable Other buttons work normally If the button becomes free the fault code will c...