Condensing PDV Series
7
Vent Tables
2" Diameter (5.1 cm) Vent Connector Lengths
Terminating
# of
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
1
45 (13.7)
2 (.6)
Through the Wall
2
40 (12.2)
2 (.6)
Through the Wall
3
35 (10.7)
2 (.6)
Through the Wall
4
30 (9.2)
2 (.6)
Through the Roof
0
50 (15.2)
7 (2.1)
Through the Roof
1
45 (13.7)
7 (2.1)
Through the Roof
2
40 (12.2)
7 (2.1)
Through the Roof
3
35 (10.7)
7 (2.1)
Through the Roof
4
30 (9.2)
7 (2.1)
3" Diameter (10.2 cm) Vent Connector Lengths
Terminating
# of
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
1
115 (35.0)
10 (3.1)
Through the Wall
2
110 (33.5)
10 (3.1)
Through the Wall
3
105 (32.0)
10 (3.1)
Through the Wall
4
100 (30.5)
10 (3.1)
Through the Wall
5
95 (29.0)
10 (3.1)
Through the Roof
0
120 (36.6)
15 (4.6)
Through the Roof
1
115 (35.0)
15 (4.6)
Through the Roof
2
110 (33.5)
15 (4.6)
Through the Roof
3
105 (32.0)
15 (4.6)
Through the Roof
4
100 (30.5)
15 (4.6)
4" Diameter (10.2 cm) Vent Connector Lengths
Terminating
# of
Elbows
Maximum Straight
Length ft. (m)
Minimum Straight
Length ft. (m)
Through the Wall
1
180 (54.9)
10 (3.1)
Through the Wall
2
175 (53.3)
10 (3.1)
Through the Wall
3
170 (51.8)
10 (3.1)
Through the Wall
4
165 (50.3)
10 (3.1)
Through the Wall
5
160 (48.8)
10 (3.1)
Through the Roof
0
180 (54.9)
15 (4.6)
Through the Roof
1
175 (53.3)
15 (4.6)
Through the Roof
2
170 (51.8)
15 (4.6)
Through the Roof
3
165 (50.3)
15 (4.6)
Through the Roof
4
160 (48.8)
15 (4.6)
7