Operating the water heating

unit

IMPORTANT

Before switching “on” the power at the main circuit breaker panel make sure that the hot
water circuit is free of air pockets or premature failure of the heating element will occur.
To do this open all hot water faucets one at a time for a minute or two until the water flow
is continuous and free from “gulping” and from visible air pockets.

1) With inlet and outlet BALL VALVES fully open, turn on a hot water outlet.

2) Run for 1 minute.

3) Switch on electric supply at circuit breaker panel.

4) The power indicator light should now illuminate (see Fig. 1), pulsing at first. Allow  40 

seconds for the indicator lights to remain illuminated, the unit is now operating at full power.
NOTE: At this point water temperature may not be hot.

5) Using the OUTLET BALL VALVE slowly reduce water flow  until desired water temperature

is achieved at hot water outlet.
NOTE: The water temperature is regulated by the flow  through the heater. The lower the
flow the higher the water temperature and vice versa.

MINIMUM SETTING

MAXIMUM SETTING

THE TEMPERATURE CONTROLLING
POTENTIOMETER IS A PRECISION
COMPONENT. ADJUST GENTLY AND
DO NOT TURN BEYOND THE MIN.
AND MAX. STOP POINTS

6) Turn the water temperature adjustment screw on the first module counter clockwise 

1/8 of a turn, wait for 10-15 seconds and see if the indicator light begins to pulse. If  the 
indicator does not, turn another 1/8 of a turn, wait and again see if the lamp begins to pulse. 
Repeat until  the light is pulsing regularly which indicates that the temperature has stabilized 
at the set temperature. Repeat with modules two and three. Check that the outlet temperature

6

Summary of Contents for EFT-18000-2-T-10

Page 1: ...R INSTALLATION AND OPERATION THE WARRANTY SHALL BE VOID IF THE DESIGN HAS BEEN ALTERED IN ANY WAY WHATSOEVER THE MANUFACTURER OF THIS UNIT WILL NOT BE LIABLE FOR ANY DAMAGES BECAUSE OF FAILURE TO COMP...

Page 2: ...bly rated three pole breaker The maximum voltage which can be applied across any heating module is 277 volts It is recommended that a Pressure Relief Valve be installed as close as possible to the hea...

Page 3: ...ing system in such a way that there is no tendency for the unit to be starved of water for example by an excessive draw off of cold water just before the unit Also do not fit an unrestricted hot water...

Page 4: ...l valve type on both inlet and outlet pipes This allows the unit to be isolated for maintenance purposes 4 When all plumbing is complete inspect the system for water leaks at all plumbing connections...

Page 5: ...OCKETS OR PREMATURE FAILURE OF THE ELEMENT WILL OCCUR TO DO THIS OPEN ALL HOT WATER OUTLETS ONE AT A TIME FOR A MINUTE OR TWO UNTIL THE WATER FLOW IS CONTINUOUS AND FREE FROM GULPING AND FROM VISIBLE...

Page 6: ...s point water temperature may not be hot 5 Using the OUTLET BALL VALVE slowly reduce water flow until desired water temperature is achieved at hot water outlet NOTE The water temperature is regulated...

Page 7: ...at the set temperature Check that the temperature is what is required The thermostat is now set and the water temperature will remain constant when the indicator light is pulsing 6 Check the performa...

Page 8: ...6 7 OHMS 7 8 OHMS 10 11 OHMS IF RESISTENCE OF THE ELEMENT IS MUCH GREATER THAN THESE READINGS CALL TECHNICAL SUPPORT NO HAET OR LOW TEMERATURE INDICATOR LIGHT ON A WATER FLOW TOO HIGH REDUCE WATER FLO...

Page 9: ......

Page 10: ...connection with a maximum of 277 volts across each element REPLACEMENT PARTS DIAGRAM THERMOSTATIC PCB PART EX100 VOLTAGE HEATER CORE ASSEMBLY FOR TRIAC PART EX18 8 EFT 18000 T 10 277V EX1280 EFT 1800...

Reviews: