![BPC HP-206P User Manual Download Page 34](http://html.mh-extra.com/html/bpc/hp-206p/hp-206p_user-manual_2798769034.webp)
28
The configuration flow in Hyperteminal will be as follows:
ATS0=1 <enter>
OK answer from the modem
AT&K0 <enter>
OK answer from the modem
AT&D0 <enter>
OK answer from the modem
AT&Y0 <enter>
OK answer from the modem
AT&N3 <enter> (US ROBOTICS ICIN)
OK answer from the modem
AT&W0 <enter>
OK answer from the modem
8.3.3.1 Smart Modem (SM) configuration (programming)
Smart modem will configure itself from the program when using TMON.
The default settings are as follows:
B0 E1 F1 M1 Q0 V1 X3
BAUD = 2400
PARITY = N
WORDLEN = 8
DIAL = PULSE
(TONE which can be programmed)
&A3 &B1 &C1 &D0 &H1 &I0 &K1 &M4
&N0 &R2
&S0 &T5 &Y1
This configuration is done by TMON program.
8.3.4 Modem connection cables
A standard modem connection cable is used to connect SM to a PC. This cable is required if an external
modem is used, but instead if an internal modem is used then no need for this cable.
The connection cable between the UPS and DM must as follows:
UPS DB9 Pin
MODEM
DB25 Male
6
3
7
7
9
2
8.4 UPS Remote monitoring panel connection
Remote monitoring panel is used to monitor the UPS from 400m distance. This panel is installed to
control/monitor room. If the distance is less than 25m then RS232 cable is used, and RS485 for larger
distances. Additional adaptor is required for RS485.
The remote monitoring panel transfers the data to the user from the UPS. The remote monitoring panel
requires 230Vac 50Hz AC voltage to operate, and it is better to use the output of the ups as a power supply.